Setup guide

Vista 120 Training Guide 39
6.1 4208 Hard Wired Expansion Training Module
Connect 4208 via twisted pair to the Polling Loop terminals, Positive + 24 and Negative 25. Observe
Polarity.
Set 4208’s DIP switch to select the appropriate block of 8 zones as Serial Numbered Zones
Use console to enter programming mode: installer code + 8 0 0 0.
Press, #93 to move to “Zone Programming” mode.
Enter 1 to enter “Zone Prog?”.
Enter the 3 digit Zone Number (010 128) and press *.
A summary screen showing present configuration will be displayed.
Press * to move to “Zone Response Type
Enter required Zone Type
Press * to move to Partition
Enter the Partition this Zone belongs to (1 8).