Previous Menu VISTA”20HW 2-PARTITIONED SECURITY SYSTEM INSTALLATION INSTRUCTIONS Principal changes in this issue are indicated by margin lines, N7526-2V14/96
HOW TO USE THIS MANUAL .............................................................................................................. 6 CONVENTIONS USED IN THIS MANUAL ........................................................................................ 7 RECOMMENDATIONS FOR PROPER PROTECTION ................................................................... 8 Section 1. GENERAL DESCRIPTION Section 2. INSTALLING THE CONTROL ...........................................................................
Section 7. RELAY OUTPUTS & POWERLINE CARRIER DEVICES ....................................... 31 Relay/Powerline Carrier Device Basics ...........................................................................3 I Nos. 4204 And 4229 Output Relay Modules ................................................................... 31 4204/4229 Setup .......................................................................................................... 31 Powerline Carrier Devices ...................................
Section 15. SYSTEM COMMUNICATION .....................................................................................6l Report Code Formats .......................................................................................................6l Table of Contact ID Codes ..........................................................................................63 Communication Programming .........................................................................................64 Section 16.
LIST OF FIGURES Figure 1. Installing the Cabinet Lock ................................................................ 12 Figure 2. Mounting the PC Board in the Cabinet .............................................. 13 Figure 3. Telephone Line Connections ............................................................... 14 Figure 4. Connection of 4300 Transformer to the Control Board ..................... 15 Figure 5. Keypad Connections to the Control Board .........................................
HOW TO USE THIS MANUAL This manual is written to accommodate both the new and the experienced installer of Ademco products. A general description of the entire system is located at the beginning of the manual. The wiring and physical setup of the hardware follows. The sections at the core of the manual include both hardware setup and programming requirements of each device to make that specific device operational in the system. A checkout procedure is included at the end of each section.
CONVENTIONS USED IN THIS MANUAL Before you begin using this manual, it is important that you understand the meaning of the following symbols (icons). Many system options are programmed in an interactive mode by responding to Alpha keypad dmplay prompts. These prompts are shown in a double-hnebox. II *OO When programming the system, data fields are indicated by a “star” (*) followed by the data field number.
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommen dations For The Location Of Fme And Burglary Detection Devicee Help Frovfde Proper Coverage For The Protected Premieee. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association’s (NFPA) Standard #72 noted below.
The VISTA-20HW is a 2-partition control that supports up to 16 zones using basic hard-wired and wired expansion zones, plus 3 keypad zones. Baeic Hardwired Zones (8) Provides 8 basic hardwired zones having the following characteristics: ● EOLR supervision supporting N.O. or N.C.
Keypad Panic Keys “ Up to 3 programmable panic key fimctions are provided. ● Designated as Zones 95, 96, 99. “ Reported separately by partition, distinguished by subscriber ID number Zone Morntor Feature s The control will sense a high resistance in the loops on hard-wired zones 2-8 if it is present, and will display a trouble message for the affected zone when the system is in the disarmed mode. This feature also prevents the system from being armed while this high resistance condition exists.
● ● The telephone lin;vofiage can be monitored to supervise the phone line connection. The panel must be connected to a proper earth ground or you will get a false line cut indication if this feature is enabled. The loss of the line can optionally cause a local display, or a display and trouble sound. Event Logging ● Event Logging feature keeps a record of selected events in a history log (UP to 48 events). All control and readout from the log is done via Ademco V-LIN@ downloading software only.
This section provides instructions for mounting the control cabinet, and installing the cabinet lock (if used). Also included in this section are instructions for the following “ Installing the main PC board. ● Standard phone line connections. “ Installing the back-up battery in the cabinet. c Connecting the AC transformer. s Making earth ground connections.
Mounting The Control’s Ckuit Board In The Cabiiet (F@ 2) 1. Hang two short Black mounting clips (provided) on the raised cabinet tabs (see Detail Bin Fig. 2). 2. Insert the top of the circuit board into the slots at the top of the cabinet. Make sure that the board rests on the correct row (see Detail A ). 3. Swing the base of the board into the mounting clips and secure the board to the cabinet with the accompanying screws (see Detail B in Fig. 2). Figure 2.
Standard Phone Line Connections Incoming phone line and handset wiring is connected to the main terminal block (via a RJ31X jack) as follows (also see Figure 3): Term. 21: Local Handset (TIP - Brown*) Term. 22: Local Handset (RING - Gray*) Term. 23: Incoming Phone Line (TIP – Green*) Term. 24: Incoming Phone Line (RING – Red*) * Colorsof wires in Direct ConnectCord.
b. Wire the other three terminals (Sync, Data, Corn) on the 43oO transformer. Wires from these terminals must be connected to a 9-pin connector on the control board (using a 4142TR cable supplied with the 4300 transformer), as shown in Figure 4. These particular wires can be 24 gauge or larger, and can be run along with the AC and ground wires to the control panel. The complete wiring for the 4300 transformer is also covered in Section 7. RELAY OUTPUTS & POWERLINE CARRIER DEVICES.
This section lists the wired keypads that may be used and provides instructions for wiring and mounting the keypads. A preliminary check-out procedure is also provided to ensure that the connected keypads are fi.mctioning properly in the system.
3. Connect remote Keypads for Partition 1 to terminals 4, 5,6, and 7 on the control board, as shown in Figure 5. 4. Connect remote Keypads for Partition 2 to the 4-pin connector on the control board (see the Summary of Connections diagram for location of the 4-pin connector for partition 2). KEYPAD CONNECTOR CABLE(SUPPLIED WITH VISTA-20HW) o5 GREEN 0 6 YELLOW 07 CONTROL TERMINALS PARTITION 2 KEYPADS PARTITION 1 KEYPADS CONNECTOR PINS FOR PARTITION 2 ON CONTROL BOARD Figure 5.
Figure 6. Using A Supplementary Power Supply For Keypads . . Pdmmmrp Check-out Procedure If you want to check that the system is working before connecting field wiring fi-om zones and devices, do the following: 1. Temporarily connect a 2000 ohm end-of-line resistor across each of the basic hard-wire zones 1–8, as shown in the Summary of Comections diagram. Without actual zone wiring or EOL resistors connected, the keypads in each partition of the system will not display the “Readfl message. 2.
This section provides information on how programming is performed in this system. It will enable you to understand how to enter and exit the programming mode, and how to program the data fields and the user-friendly interactive modes (*56, *80, *81, *82, *83). We therefore urge you to read and understand the following before proceeding with the installation.
3. If the number of digits that you need to enter in a data field is less than the maximum digits available (for example, the phone number field), enter the desired data, then press * and the next data field number to be programmed. 4. If you try to enter a non-existent field, the keypad will display EE or Entry Error. Simply re-enter [*] plus a valid field number. Reviewing a Data Field/Erasing an Entry in a Data Field Press [#] plus Field No. Data will be displayed for that field number.
This section provides general information for the hard-wired zones in the system, plus specific instructions for installing 2-wire smoke detectors, 4-wire smokekombustion detectors, and 2-wire latching type glass break detectors. Also included is a procedure for programming the hard-wired zones.
Turning Off Fire Alarm Sounding You can turn off Fire alarm sounding by pressing the OFF key on any keypad or other arming/disarming device in that partition. To clear the “memory of alarm” and to reset the detector’s alarm, enter the security code plus OFF again.
+ COMPATIBLE 4-WIRE SMOICWCOMBUSTION DETECTORS 1412 System Sensor, 4-wire ionization .m’oducts of combustion I detector. 2412 System Sensor, 4-wire photoelectric smoke detector 2412TH System Sensor, 4-wire photoelectric smoke detector w/135QF (57QC) heat detector A77-716B System Sensor, EOL relay module (supervisory module for wired 4wire fire zone).
Progr amming Hard-Wwed Zones 1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the Partition 1 keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system. 2. Enter the programming mode by keying the following on the Alpha keypad Installer code (41 12) + 8 + O + O.
n Enter the partition to which this zone is assigned, “l” or “2”. The factory default is partition 1. Press [*] to continue. The report code consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of 3C , enter [0][3] for1~ad[l][2]f0rC. Re~er~oSectio7z15 SYSTEM COMMUNICATION for complete information on report codes, if necessary. Enter the desired report code and then press [*I to continue. -1 Enter the desired response time for the zone.
Check-Out Procedure For Hard-Wwed Zones After installation of all hard-wired devices is completed, each partition of the security system should be checked, as follows. 1. Make certain that all devices and sensors connected to the hard-wired zones are not in a faulted state. Doors and windows with contacts should be closed, PIRs should be covered (use a cloth to mask them temporarily if necessary). 2. Plug in the AC Transformer if you have not already done so.. w 3.
This section provides information regarding the use of expansion modules for expanding the number of wired zones in the system, the modules that can be used and their wiring connections, plus a procedure for programming the wired expansion zones. Installing Zone Expansion Units You can add an additional 8 wired EOLR zones to the basic control’s 8 zones, for a total of 16 wired zones, by using a No. 4219 Wired Expansion Unit, or 4229 Wired Expansion/Relay Unit.
Programming Wined Expansion Zones 1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the Partition 1 keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system. 2. Enter the programming mode by keying the following on the Alpha keypad: Installer code (41 12) + 8 + O + O. 3. Press *56.
10 Report Code 1st 03 2nd 12 3C The report code consists of 2 hexadecimal digits, each in turn consisting of 2 numerical digits. For example, for a report code of “3C”, enter [0][3] for “3” and [1][2] for “C”. Refer to Section 15. SYSTEM COMMUNICATION for complete information on report codes, if necessary. Enter the report code and then press [*] to continue. Typicalsummarydisplay A summary display will appear, showing the data for the zone that was just programmed.
Check-Out Procedure For Wired Expansion Zones After you have completed installation of all devices, all expansion zones in each partition of the security system should be checked as follows: 1. Make certain that all devices and sensors connected to the wired expansion zones are not in a faulted state. Doors and windows with contacts should be closed, PIRs should be covered (use a cloth to mask them temporarily if necessary). 2.
Relay/Powerline Carner Device Basics Relays and Powerline Carrier devices (ex. X-10 brand devices) are programmable switches that can be used to perform many different fbnctions. They can be used to turn lights on and off, control sounders, or for status indications. In this system, each device must be programmed as to how to act (ACTION), when to activate (START), and when to deactivate (STOP).
4229 GRN DATA OUT ~ TO CONTROL GROUND — (-) B (+) 12V YEL — DATA IN FROM CONTROL (TERM 6) (TERM 4) (TERM 5) (TERM 7) R ZONES A’ Figure c’ B“ 11. 4229 ~ E“ F’ G“ ~ Connection to Control TS2 R51AY .4204 4 = + MPS~H i FOR SEillNG DEVICE ADDRESS AND ENASUNGIDISASUffi TAMPER TYPICAL (SHOWN WF’) COVER TAMPER (REED) SWITCH 1 4-PIN CONSOLE PLUG & 0 Tsl L L Figure 12. 4204 ~ DATA IN FROM CONTROL (term. T) Bti [-) GROUND (tmm4) OATA OUT TO CONTROL RED (term. 6) (+) 12V (tWII.
Wting Connection 1. Splice one end of a 3-conductor cable to the wire ends of the 4142TR cable supplied with the 4300 transformer. 2. Connect the 4142TR cable plug to the 9-pin connector on the control (see SUMMARY OF CONNECTIONS diagram for location of the 9-pin connector), 3. Connect the other end of the 3-conductor cable to the 4300 transformer, as indicated in the table below and in the diagram that follows. 4300 TRANSFORMER WIRE CONNECTIONS 4300 TERMINAL ITO ‘IX-AL ON CONTROL 1 (AC) 1 (16.
Programming Options Defined The following will help you understand the programming of OUTPUT DEVICES when using *8O and *81 modes. The options used to start and stop these devices are described below, followed by the actual screen prompts and available entries. w The letter(s) in parentheses after each fiction described below, such as (A) after ACTION, are those that appear in the various summary displays of programmed data during programming.
If a “SYSTEM OPERATION” is chosen (e.g., End of Exit Time), that operation will cause the device to activate as selected in “ACTION.” The different choices for “ZONE TYPE” and “SYSTEM OPERATION” are listed in “Programming Output Relays & Powerline Carrier devices” later in this section, and in the Programming Form. 2 PARTITION No. (P). The device’s “Start” ZONE TYPE/SYSTEM OPERATION may be limited to an occurrence on Partition 1, Partition 2, or any partition (A).
Programming Output Relays and Powerline Carrier Devices — 1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the Partition 1 keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system. 2. Enter the programming mode by keying the following on the Alpha keypad: Installer code (41 12) +8+ O + O. ❑ 3. Press *7.
CHOICES 00= NotUsed 01= Entry/Exit #l 02= Entry/Exit #2 03= Perimeter Arming+tay 36= **AtBellTimeout*** 21. Arming-Away 38= Chime 22. Disarming (Code+ OFF) 39= AnyFireAlarm 31= EndofExitTime 40= Bypassing 32= Startof EntryTime 41= **ACPowerFailure 33= AnyBurglary Alarm Enter (if applicable) the partition number 1 or 2 (or Press the [*] key to continue. 20= ~ 02 stop: No List Zn List o 02 stop: Not Used Zn Typ 02 .AEVZLZT S1-roooool 08=24 HrAux 09= FireTrouble I 10= Interiorw/Delay 23.
To stop the Device action and turn off the lamp, we do not want to use a restore of any zone, so a “O”will be programmed for the Restore of Zone List (ZL). We will use a manual entry of User Code + [#] + [8] + Device # to turn off. Therefore, we do not need to program a STOP event. Press [*I to continue. - The system will display a summary screen for the START programming for device 01. Press [*I to continue. The system will display a summary screen for the STOP programming for device 01.
This section provides instructions for mounting the 4285 VIP(VISTA Interactive Phone) module, wiring the 4285 Module and for programming the system for phone access via the 4285 Module. Installing the 4285 Module General Information The 4285 VIP module is an add-on accessory for the VISTA-20HW that permits access to the security system via a Touch-tone phone (either on premises or by a call-in when away).
4285 Module WIMg The 4285 is wired between the control panel and the premises handset(s). It listens for touch tones on the phone line and reports them to the control panel. During on-premises phone access, it powers the premises phones; during off-premises phone access, it seizes the line from the premises phones and any answering machines. Note: The phone lines must be in service for the 4285 module to function, even when accessing the system from an on-premises phone. 1.
4285 WIRING NOTES 1. Wire the 4285 moduleexactlyas shown,usinga direct-connectcord and RJ31Xjack. 2. If Touch-tonesare not heard whenpressingkeys followingphone access to the security system viu an on-premisesphone, try reversingthe pairof wires connectedto terminals3 & 4 on the 4285, and the pair of wires comected to terminals21 & 22 on the control. 3. If an error signal (fast busy signal)is heardwhen tryingto accessthe systemvia the phone, check for correctline seizurewiring,as describedin note 4. 4.
Programming The Control For Phone Access 1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the 2. 3. Partition 1 keypad terminals on the control, power up the system temporarily. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system. Enter the programming mode by keying the following on the Alpha keypad: Installer code (41 12) + 8 + O + O. Press *28. VOICE MODULE ACCESS CODE.
Checking the Operation of the 42?35 VIP Module To Check Operation From an On-Premiees Phone: 1. Pick up phone and enter the programmed 2-digit phone code. Annunciation of a system status report should automatically start. See the User’s Guide accompanying the 4285 module for detailed information regarding the nature of the status report, if necessary. 2.
This section provides a Iist of compatible sounders, comection information for an external sounder and programming procedures for those options that affect the operation of external sounders. Compatible Sounders Ademco AB-12M 10” Motorized Bell & Box Ademco 1011BE12M 1(Y Motorized Bell& Box Ademco 702 Outdoor Siren Motor bell & box. UL Grade A. 100 mA current draw. Motor bell & box. UL Listed. 100 mA current draw. Self-contained 6-12 volt siren (driver builtiin) and weatherproof for outdoor use.
Sounder Connections The VISTA-20HW provides a 12 VDC output which can power external alarm sounders (bells or sirens, see compatible sounders listed previously). This output will activate a sounder when an alarm occurs in partition 1 or 2. Make connections to alarm output terminals 3 (+) and 4 (-). See diagram below. Non-UL hMttdkttiOllS The total current drawn from this output cannot exceed 2 amps. A battery must be installed since this current is supplied by the battery. CONTROL BOARD No.
After installation of the sounder is completed, each partition of the Security System should be carefully tested, as follows. 1. Connect the battery wires from the control board to the battery, observing correct polarity. 2. Enter the installer code (4112) and press the TEST [5] key on the keypad. The external sounder should sound for 1 second if the sounder is good and proper connections have been made. Note that if the backup battery is discharged, the sounder will not turn on. 3.
Generel Information Check availability of Model 7720PLUS or 7820 long range radio. I If output to long range radio is selected, all messages that are programmed to go to the primary telephone line receiver will also be sent to the 7720 PLUS or 7820 long range radio. These messages will be in Contact ID format (not fiected by entry in field *48). I The data line is supervised, as well as certain functions in the radio.
This section provides instructions for the connection of an optional remote 4146 keyswitch for remote arming and disarming of the system, and the programming necessary when a keyswitch is used. Also included is a description of how the keyswitch operates in the system. Installing the Keyswitcb The remote 4146 keyswitch (with red and green LEDs to indicate status) is connected to zone 7. Note that you can use a keyswitch in one partition only. Remote Keyswitch Connections 1.
9 PIN CONNECTOR ON CONTROL BOARD m F4-----------a; BROKEN LINES REPRESENT INSTALLER WIRING CONNECTIONS f (ARMED) ~..-. ---.. ----...-. 4142TR CABLE \ (REAOY) - . . ..-. .--... RED ~m j i THESE WIRES NOT CONNECTEO IF 4300 INTERFACE TRANSFORMER IS m BEING USED. { \ + AUX POWER \ -------- GREEN ---- 62022 ~------- 620Q ----++---J ~----------- \ l—? --------------7 fiFik-----------j TO ZONE 7 I ! : LOCK SWTCH(N.O.
Programming For The Remote Keyswitch 1. With at least one 2-line Alpha keypad (5137AD or 6139) connected to the Partition 1 terminals, power up the system. If you had previously connected the AC transformer to the control panel, you need only plug in the transformer (to 120VAC outlet) to power up the system. 2. Enter the programming mode by entering: Installer code (41 12) + 8 + O + Okeys.
Enter the desired response time for zone 7. The recommended entry for keyswitch 1 II operation is “1” (the factory default). I Selections available are: “0” (10 msec), “1” (350 msec), or “2” (700 msec). Enter the desired numbers and then press [*I to continue. Typicalsummarydisplay A summary display will appear, showing the data for zone 7 that was just programmed. If it is programmed satisfactorily, press [*I to m continue.
General Information An Audio Alarm Verification (AAV) module, such as the Eagle 124~ is an add-on accessory that permits voice dialog between an operator at a central station and a person at the alarm installation, for the purpose of alarm verification. I Mter all messages have been sent during a reporting session to the primary phone number, the control will trigger the AAV if at least one of the messages was an alarm report.
L,INCCMNQ TELCO LINE .- lERMINALS ON CONTROL I NWTTRIGGER NOTE 00 NOT USE REIAY 1 ~R ANY OTNER WRFQSE. III&l REUY1. SNOWN I@ure 18. Connection Of AAV Unit When Not Using A 42S5 VIP Module 1. 4 1 NOTE 00 NOT USE RELAY 1 FOR ANY oTHER PURPOSE. Figure 19.
In Section 2, you made temporary power connections for the purpose of programming and testing the keypads. This section provides information about final power-up procedures and battery size calculations. ~ Earth Ground Connections The designated earth ground terminal (25) must be terminated in a good earth ground for the lightning transient protective devices in this product to be effective. It also must be grounded to enable the telephone line fault indicator to work properly.
Making the BatteryConnections 1. Use the battery standby formula (above) to select the appropriate battery for the installation. Attach the Red and Black wires on the battery connector cable as follows: a) Red to the positive (+) battery tab on the contiol board. b) Black to the negative (-) battery tab on the control board. 2. See the SUMMARY OF CONNECTIONS diagram for location of the (+) and (–) battery tabs on the control board. 3.
y This section provides instructions for programming Alpha descriptors. This is recommended for systems using Alpha keypads, and necessary if a 4285 module is used. If using a 4285 module, select from those words in the Alpha Vocabulary list shown in boldface type. The 4285 module will not provide annunciation of the other words. .<, ~“ 1$ g 4283 module is zidiled @ an exis$$ng,~S~A-26HW system; the;Alpha ,#
4. Press “O” (No).* The system will then automatically display the descriptor for zone 1. * The procedurefor addingcustomwordsto the built-invocabularywill be found later under“AddingCustomWords”. SummuryModeDisplay DefaultDescriptor$ p), ZONEOI FlashingCursor(systemis readyfor entryof word). 4 +i+ZNOl~ When entering Zone ~ Descriptors usin~Method z, the keypad keys perform the following function= [3] Scrolls both alphabet and actual words in ascending alphabetical order.
9. Press “6” to accept the selected word. Note: If these are the only words you are using for the descriptor, press “8” instead of “6” to save them in memory. t Flashing Cursor if “6” is pressed (system ready for next word). 10. The two words in our example have now been entered. that up to three entered (provided characters will fit Press “8” to save memory. SummaryDisday +$ ZN II 01 Note, however, words may be the number of on the screen).
4. For selection of the next word (e.g., DOOR), repeat step 3, as follows. . Press key [3] until the first letter of the next word appears (e.g., “D”). Then press [6] to display the first available word beginning with that letter (e.g. DAUGHTERS). Press [3] repeatedly until the desired word (e.g., DOOR) appears. To accept the word, press [61,which toggles back to the alphabet list. 5. When all desired words have been entered, press [8] to store the description in memory. 6.
ALPHA VOCABULARY LIST (For Entering Zone Descriptors) 000 (WordSpace) A ● 001 ● 002 003 004 005 006 007 008 009 010 011 ● ● ● AIR ALARM ALCOVE ALLEY ● ● AMBUSH ● AREA APARTMENT ● ART AITIC AUDIO AUXILIARY ● ● ● ● ● ● ● 016 017 018 019 020 021 022 023 024 025 026 027 ● BASEMENT BATHROOM BED BEDROOM BELL BLOWER BOILER BOITOM BOX BREAK BUILDING BURNER ● ● ● ● 065 066 067 068 069 070 071 072 ● ● ● ● ● CABINET CALL CAM-ERA ● ● CAR CASE CASH CCTV CEILING CELLAR CENTRAL CIRCUIT C
This section provides an for reporting alarms and process of a successful communication between and the actual way the station. explanation of formats this system accommodates other system conditions to the central station.
The following describes each format in greater detail. 3+1 and 4+1 Standard Formats Comprise a 3- (or 4-) digit subscriber number and a single digit report code (e.g. Alarm, Trouble, Restore, Open, Close, etc). 3+1 and 4+1 Expanded Formats Comprise a 3- (or 4-) digit subscriber number, and a two-digit report code. The first digit is displayed on the first line, followed by a second line where the first digit is repeated 3 (or 4) times and followed by the second digit. This is the “expanded” digit.
Ademco Contact ID Reporting takesthe following format: CCCC Q EEE GG ZZZ where: CCCC = Customer (subscriber) ID Q= Event qualifier, where: E = new event, and R = restore EEE = Event code (3 hexadecimal digits) Note: For a complete list of event codes, refer to the central office receiver manual. GG= Partition Number (system messages show “00”) Zzz = Zone/contact ID number reporting the alarm, or user number for opeticlose repoi-ts. SyStem status messages (AC Loss, Walk Test, etc.
Communication Programming Introduction This sectionprovidesinstructionsfor programmingthosefields that affectcommunications betweenthe controlandthe centralstation. \ Keypad Programming Procedure 1. With at least one Alpha keypad (5137AD or 6139) connected to the system, power up the system. If necessary, refer to the POWERING THE SYSTEM section for the power-up procedure.
Press *48 REPORT FORMAT, PRIMARYJSECONDARY Primary ❑ Secondary ❑ Determines which format is to be used to report to the central station. O= 3+1; 4+1 ADEMCO Lo Speed Standard (this is the default) 1 = 3+1; 4+1 Radionics Standard 2 = 4+2 ADEMCO Lo Speed Standard 3 = 4+2 Radionics Standard 6 = 4+2 ADEMCO Express 7 = ADEMCO Contact ID Reporting 8 = 3+1; 4+1 ADEMCO Lo Speed Expanded 9 = 3+1; 4+1 Radionics Expanded (Enter *as the 4th digit of* 43 through* 46, if 3+1 dialer report ing is to be used.
TO PROGRAM SYSTEM STATUS AND RESTORE REPORT CODES (*59-*76,&*89) The following is a set of guidelines to be used for programming report codes, The actual digits that you enter depend upon the particular installation, and should be in agreement with you and the central station office receiving the signals. Use these guidelines to program this entire section. With a 3+1 or 4+1 Standard Format: Enter a code in the first box 1-9, A, B, C, D, E, or F.
❑ Part’n In Part’n 2 OPEN REPORT CODE This is sent upon disarming of the system. 2nd digit. User No., if expanded or 4+2 reporting is selected. See TO PROGRAM SYSTEM STATUS AND RESTORE REPORT CODES explanation on previous page for fields %6-*76, and *89. Press Press Press *65 W ARM AWAY/STAY REPORT CODE Part’n 1 Part’n 2 ❑ ❑ 0 0 A~A~ S!l’AY AWAYS’1’A~ This option allows for independent programming of AWAY and STAY reports for each partition. 2nd digit of Report is User No.
Press *9O EVENT LOGGING •1 O= None; 1 = Alarm/Alarm Restore; 2 = Trouble/Trouble Restore; 4 = Bypass/Bypass Restore; 8 = Open/Close. Default is “3”. Exampku To select “Alarm/Alarm Restore”, and “Open/Close”, enter 9 (1+ 8); to select all, enter #15. Note: System messages are logged when non-zero selections are made. See Fields *89 and *9O in Section 17. DATA FIELD DESCRIPTIONS for a more detailed description of Event Logging.
General Information Type 00 Zone Not Used You must assign a zone type to each zone, which will then define the way in which the system will respond to faults in that zone. Zone types are defined below. Program a zone with this zone type if the zone is not used. Type 01 Entry/Exit Burglary #1 This zone type provides exit and entry delays whenever the zone is faulted if the control is armed in the Away or Stay modes. When the panel is armed in the Instant or Maximum modes, no entry delay is provided.
Type 06 24-hour Silent Alarm This zone type sends a report to the Central Station but provides no keypad display or sounding. This zone type is usually assigned to a zone containing an Emergency button. Type 07 24-hour Audible Alarm This zone type sends a report to the Central Station, and provides an alarm sound at the keypad, and an audible external alarm. This zone type is usually assigned to a zone that has an Emergency button.
Descriptions of System Data Fields THE BLANK PROGRAMMINGFORMSHOULDBE USEDTO RECORDTHE DATAFOR THIS INSTALLATION Defaults (where applicable) Are Indicated In Text The following is a table containing a list of all data fields in this control (presented in numerical order).
*29 OUTPUT TO LONG RANGE RADIO u If output to LRR is selected here, all messages that are programmed to go to the primary telephone line receiver will also be sent to the 7720 PLUS or 7820 radio. These messages will always be in Contact ~ ID format (not affected by entry in field *48). The data line is supervised as well as certain functions in the radio. If communication is lost or a trouble develops, a message will be attempted to be sent via both radio and telephone to the central station.
DIALER PROGRAMMING ❑ Partition1 AUDIBLE EXtT WARNING Partition2 If enabled, this field provides exit warning sound when armed AWAY it can be selected for either or both Partitions. Warning sound consists of slow continuous beeps until last 5 seconds, when it changes to fast beeps. The warning sound will end at the termination of Exit time. O = no; 1 = yes. Default is 1.
..,. -4ti SECONDARY SUBS ACCOUNT. No. (Partition. 2) See notes previously. 1~/ SecondW Receiver. *47 PHONE SYSTEM SELECT Default is O. •1 Enter 1 digit. If Central Station Receiver is not on WATS line: O= Pulse Dial, 1 = Tone Dial. If Central Station Receiver is on WATS line: 2 = Pulse Dial, 3 = Tone Dial *48 Primary Secondary REPORT FORMAT Determine which format is to be used to report to the central station. Enter 1 digit (O-9).
*56 ZONE ASSIGNMENT/ALARM REPORT CODES REFER TO THE ZONE ASSIGNMENT T)4.BLE FOR *56 IN THE CENTERFOLD PROGRAMMING FORM . This is an interactive menu mode that is used to program zone numbers, zone types, partition numbers, alarm and report codes, and to identify the type of loop input device. This mode can also be used for entering Alpha descriptors for zones (we recommend entering descriptors in menu mode *82.
Custom Alpha Editing: For all zone types, the next request is to enter Alpha descriptors for the zones. The entry may be done now (enter 1), or maybe done at a later time via *82 mode (enter O). See Section procedure. DESCRIPTION PROGRAMMING for When all entries to be made for the zone at this time are complete, the next zone number can be entered for programming, or zone programming can be ended by entering [0][0] as the next “zone number”. Enter Zn Num. (00 = Quit) 14. ALPHA 00 Notes: 1.
SYSTEM STATUS REPORT CODES (*59-W3) *59 EXIT ERROR REPORT CODE (Seebox previously) *60 TROUBLE REPORT CODE (Seebox previously) m *61 BYPASS REPORT CODE (Seeboxpreviously) m *62 AC LOSS REPORT CODE m See box on previouspage. Reportswith Partition 1 SubscriberNo. Timing of this reportis random with up to a 4-hour delay. If AC restoresbeforethe reportgoesout,thereis no AC restorereport. *63 LOW BAT REPORT CODE See box. ReportswithPartition1 SubscriberNo. m *64 TEST REPORT CODE See box.
RESTORE REPORTCODES (*6=76) *69 ❑ GROUP RESTORES FOR TROUBLE, BYPASS Enter O for no (report for ~ restore), or 1 for yes (report after M zones restored). Default is “O”. Note: “1“ not applicable to Contact ID reporting. *7O ALARM RESTORE REPORT CODE, 1st DIGIT •1 2nd digit is automatically sent as the 2nd digit of the zone alarm report code programmed in field *56, if expanded or 4+2 reporting is selected. *71 TROUBLE RESTORE REPORT CODE m See box on previous page.
*W ❑ EVENT LOGGING The VISTA-20HW system has the ability to record various events in a history log (48-event capacity). The types of events to be logged can be selected as indicated below. At any time, the downloader operator can then upload the log and view or print out all or selected categories of the log. The log can also be cleared by the downloader operator. The display/printout at the central station will show the date, time, event, and description of the occurrences.
4285 Module Answering Machine Yes No No Set for value other than “O”(1–15). This will enable the control panel to answer the phone call. Otherwise, it will not be possible to access the 4285 module Yes Yes No Set for a value higher than the number of of rings for which the answering machine is set. Example: if machine is set for 4 rings, use a value of 5 or higher.
General Information The VISTA-20HW can be remotely programmed horn an IBM compatible Personal Computer (PC), a HAYES Modem, and Ademco’s V-LINK@ Soflnvare (as specified below). Programming the control from a remote location is protected against compromise by someone attempting to defeat the system, using multi-levels of security protection 1. Security Code Handshake: An 8-digit download ID code must be matched between the control and the dowriloader. The installer or subscriber initi2.
Command the System to Upload a Copy of its Resident Program to the office. . Read: Arming Status, AC Power Status, Lists of Faulted Zones, Bypassed Zones, Zones Currently in Alarm, Zones Currently in Trouble. ● Notes: After the control and the PC have established valid communication, each keypad on the system will become inactive and will display “CC” or “MODEM COMM.”. The control, however, will still be scanning its zones and looking for alarms.
Test Procedure After installation is completed, each partition of the Security System should be carefully tested, as follows. 1. With the System in the disarmed state, check that all zones are intact. If a NOT READY message is displayed, press the [*I key to display the faulted zone(s). Restore faulted zone(s) if necessary, so that READY message is displayed. Fault and restore every sensor individually to assure that it is being monitored by the system. 2. Enter the security code and press the TEST key.
Security Codes w Installer Code The installer programs the 4-digit Installer Code initially as part of the programming procedure. The factory default Installer code is “4-l-l-2”, but may be changed in field *20. The Installer code is the only code that can enter programming mode and also, in normal operation mode, is used to enter the Master code for each partition, which allows access to the normal fimctions of the system. See Section 4.
General Information Notethat if you enabled QUICK ARM for the partition (field *21), the [#] key can be pressed instead of entering the partition’s security code, for any of the arming procedures (Away, Stay, Instant, Maximum, etc.). The security code is always required, however, when disarming the system. The keypad allows the user to arm and disarm the system, and perform other system functions, such as bypassing zones, and display zone descriptors.
Panic Keys There are three lettered keys or (on some keypads, panic key pairs) that, if programmed, can be used to manually initiate alarms and send a report’ to the central station. Each can be individually programmed for 24-hour Silent, Audible, Personal or Fire Emergency responses. The panic function is activated when the appropriate lettered key is pressed for at least 2 seconds, or the appropriate key pair are pressed at the same time.
Trouble Conditions (See Troubleshooting Guide also) General Information “Check” and “Batte@’ Displays The word “CHECK on the Keypad’s display, accompaniedby a rapid “beeping”at the Keypad, indicatesthat there is a trouble conditionin the system. The audible warning sound can be silenced by pressing any key. Instructusers to call for serviceimmediatelyupon seeingany of the following messages.
SYSTEM SYMPTOM 1. Low Batterymessageon keypad. POSSIBLE CAUSE or “System Lo Bat” (no zone Nos.) la. “Bat” mode. 2. Periodic beep(s)from keypad. 3. Nuisanceor phantomalarm. 3a. Sensors not properly installed, wired, or 2a. System is in TEST REMEDY la. 2a. Enter “Code” + OFF to exit TEST mode. 3a. Check installation to see if in accordance with established procedure. monitored. 4. Intrusion alarmfornoapparentreason. 4a. Protected door or window opened while system armed. 4b.
CONTACTING TECHNICAL SUPPORT PLEASE, Before you call Technical Support, ● READ THE INSTRUCTIONS! ● Check all wiring connections. ● ● ● ● be sure you: Determine that the power supply and/or backup battery are supplying proper voltages. Veri& your progr amming information where applicable. Note the proper model number of this product, and the version level (if known) along with any documentation that came with the product. Note your ADEMCO customer number and/or company name.
REGULATORY AGENCY STATEMENTS UL NOTICE: This is a “Grade A“ residential system. FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT This equipment has been tested to FCC requirements and has been found acceptable for use.
specifications V-ISTA-20HW SECURITY CONTROL 1. Physicak 12-W” W x 14-1/2° H x 3“ D (318mm x 368mm x 76mm). 2. Electrical VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321/TF2 (in U.S.A.). RECHARGEABLE BACK- UP BATTERY: 12VDC, 4AH (Gel type) minimum. Charging Voltage: 13.8VDC. ALARM SOUNDER: 12V, 2.o Amp output can drive 12V BELLS or can drive one or two 702 (series connected) self-contained 20-watt sirens. Do not connect two 702s in parallel. AUXILIARY POWER OUTPUT: 12VDC, 600mA max.
6127 REMOTE KEYPAD 6128 REMOTE KEYPAD 6137 REMOTE KEYPAD 6138 & 6139 REMOTE KEYPADS 4219 WIRED EXPANSION MODULE 4204 REI.AY MODULE 4229 WIRED EXPANSION/ RELAY MODULE 4285 VIP MODULE 1. Physical: 5-3/4” W x 4-3/4” H x 1“ D (146mm x 121mm x 26mm), 2. Electrical: Voltage Input: 12VDC; Current Drain: 20mA. 3. Interface Wiring: Same as 4127. 1. Physical: 5-3/4” W x 4-3/4” H x 1“ D (146mm x 121mm x 26mm). 2. Electrical: Voltage Input: 12VDC; Current Drain: 30nA. 3. Interface Wirin~ Same as 4127.
16.5VAC, 25VA Plug-In Transformer. Powerline Carrier device Interface AC Transformer. No. 1321/TF2 No. 4300 Sounders Compatible Z-Wire Sm-oke Detectors Ademco AB-12M 10” Motorized Bell & Box Motor bell & box. UL Grade A. 100 mA current draw. Ademco 10I133E12M 10” Motorized Bell & Box Motor bell & box. UL Listed. 100 mA current draw. Ademco 702 Outdoor Siren Self-contained 6–12 volt siren (driver built-in) and weatherproof for outdoor use. Can be wired for either a steady or warble sound.
l-Minute 74 ............................................................................ 44, 93 745x3 ........................................................................u. 93 747 ................................................................................. 93 747UL ....................................................................... 44, 93 7720 PIUS . . . . . . . . . . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
cc ............................................................................. 87,68 Central Station Character (Ascii) Chati . .................................... .. ............. 60 Character Chart Character Charging -F- .................. ................... ............ .............. . 76 Facto~Defaults ..............................................................2O Fast Busy 5gnal ............................................................. 41 FC ... ......................................
Monitored Telephone Line .............................................. 87 Relays ............................................................................. 31 Remote Keypads .............................................................. 9 Remote Programming ..................................................... 81 Report Code .............................................................. 75,77 Report Code Formats ..................................................... 61 Report Codes ...................
-x- -v“Verification” Feature ...................................................... 24 “Verify” Operation ........................?................................... 21 V-Link@ Downloading Software .......................... 11, 19, 81 V-Link@ Downloading Software Diskette ........................ 82 Vocabulary List ..............................................................- 60 Voice Module Access Code ............................................
THE LIMITATIONS WARNING OF THIS AUUtM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, tire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: ● Intrusion detectors (e.g., passive infkared detectors), smoke detectors, and many other sensing devices will not work without power.
Figure 20.
ADEMCO LIMITED WARRANTY Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates (“Seller”), 165 Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free born defects in materials and workmanship under normal use and service for 18 months from the date stamp control on the product or, for products not having an Ademco date stamp, for 12 months from date of original purchas