Troubleshooting guide

*29
OUTPUT TO LONG RANGE RADIO
u
If output to LRR is selected here, all messages that are programmed
to go to the primary telephone line receiver will also be sent to the
7720 PLUS or 7820 radio. These messages will always be in Contact
~
ID format (not affected by entry in field *48). The data line is
supervised as well as certain functions in the radio. If
communication is lost or a trouble develops, a message will be
attempted to be sent via both radio and telephone to the central
station.
Note: Normal trouble restore report (*71) is sent on restore of the
condition.
Entry is first digit of Trouble Dialer Report; enter Trouble code 1–9,
B (# +11), C (# +12), D (# +13), E (# +14), or F (# +15). The 2nd digit
of Trouble Dialer Report is automatically the 2nd digit from field %0.
For UL installations, Long Range Radio must be disabled
(enter ‘O”).
I
*30
Notes
ZONE SOUNDS AND
*32
(*3;
*33
*34
II
Note: Entry Delay
I
*35
must be set for a
I Imaximum of 20 seconds I
I Iin ULinstallations.
Note: The Radio should be programmed for device address 3 on the -
keypad lines.
KEYSWITCH ENABLE
This field must be enabled (enter 1) if using a keyswitch. The
keyswitch must be connected to zone 7, which can then not be used
for any other purpose.
Default is O (no keyswitch).
If keyswitch is enabled, in menu mode *56 the Zone Type (ZT) for
zone 7 will show “77”, and the zone will not be accessible for
programming.
If the 4146 keyswitch is used with only Red and Green LEDs
comected (no lock switch and tamper switch)
to simply provide
an arming/ready status indicator panel, zone 7 can then be used
as a hard-wired protection zone, provided you do not enable
this field.
SINGLE ALARM SOUNDING PER ZONE (per armed period)
Thisfield limits alarm sounding to once per arming period for a given
zone.
Enter 1 for yes; default is O(no).
FIRE SOUNDER TIMEOUT
This field determines whether the external sounder will shut off after
time allotted, or continue until manually turned off. Enter O for
sounder timeout, or 1 for no timeout. Default is O.
This control complies with NFPA requirements for temporal
puke sounding of fire notification appliances.
Temporal pulse sounding for a fire alarm consists of the following
3 pulses - pause -3 pulses - pause -3 pulses. . .
ALARM BELL TIMEOUT
This field determines whether the extermll sounder will shut off after
time allotted, or continue until manually turned off. Enter as follows
O= No timeout 1 = 4 min (default); 2 = 8 rein; 3 = 12 min.
Alarm bell timeout must be set for a minimum of 4 rnin (“1”)
for UL installations.
ZONE TYPE 01 ENTRY DELAY Partition1 Partition2
System will wait the time allotted before sounding alarm upon
entering. May be selected individually for each Partition.
o = O seconds 2 = 30 seconds 4 = 60 seconds
1 =20 seconds 3 = 45 seconds 5 =90 seconds
Default is 2 (30 seconds).
Zone Type 02 Entry Delay= Zone Type 01 Entry Delay+ 30 seconds.
(EmT delays= Zone type 01 Entry delay plus 40 seconds).
-72-
%!