VISTA-128FBP VISTA-250FBP Commercial Fire and Burglary Partitioned Security System with Scheduling Programming Guide K0376PRV2 7/09 Rev.
Table of Contents Relay Voice Descriptors and Custom Word Substitutes Vocabulary........................................ 40 System Layout Worksheets.................................... 42 Output Devices Worksheets ................................... 58 Scheduling Menu Prompts ..................................... 64 Scheduling Worksheets.......................................... 65 Programming Field Settings for UL864 Compliance 2 Recommended Programming Procedure................. 6 Program Field Index ...
Program feature or option ✱54 UNATTENDED MODE ✱56 DYNAMIC SIGNALING DELAY ✱77 AUTO TROUBLE RESTORE ✱80 ZONE TYPE RESTORES FOR TYPES 9, 10 & 14 1✱12 PROGRAM NOTIFICATION SIGNAL 1✱13 SYSTEM SENSOR REVERSING RELAY Permitted in UL864? Y/N N Y Y N Y N 1✱18 AFFECTS LOBBY N 1✱19 ARMS LOBBY N 1✱22thru 1✱25 CROSS-ZONING PAIRS (1 – 4) 1✱28 RF TRANSMITTER LOW BATTERY SOUND 1✱29 RF TRANSMITTER LOW BATTERY REPORTING 1✱30 RF RECEIVER SUPERVISION CHECK-IN INTERVAL N 1✱31 RF TRANSMITTER CHECK-IN INTERVAL N 1✱35 A
Program feature or option Permitted in UL864? Y/N Possible settings Settings permitted in UL 864 2✱18 ENABLE GOTO FOR THIS PARTITION (partitionspecific) 2✱21 SUPERVISION PULSES FOR COMMUNICATIONS DEVICE 2✱22 DISPLAY FIRE ALARMS OF OTHER PARTITIONS 2✱23 DISPLAY BURG, PANIC AND CO ALARMS FOR OTHER PARTITIONS 2✱24 DISPLAY TROUBLES OF OTHER PARTITIONS 2✱30 - 2✱88 (PAGER OPTIONS) 3✱01 EVENTS DISPLAY LOCK N 0 = disable 1 = enable Must be set to “0” (disable) for partition 1.
NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and the event log capacity, use the VISTA-250FBP’s features. The following table lists the differences between the VISTA128FBP and the VISTA-250FBP control panels. All other features are identical.
Recommended Programming Procedure The following is a step-by-step procedure recommended for programming your VISTA-128FBP/VISTA-250FBP system. 1. Set the keypads (and other peripheral devices) to the appropriate addresses. 2. Set factory defaults by pressing ✱97. This will automatically enable keypad addresses 00-01, so be sure at least one keypad is set to one of these addresses. 3. Program system-wide (global) data fields.
Program Field Index On the following pages, the programming fields have been arranged in numerical order. Use this index to cross-reference the fields on the programming form.
VISTA-128FBP/VISTA-250FBP Programming Form Some fields are programmed for each partition (shown as shaded fields). If you are programming a multiple-partition system, see the Partition-Specific Fields section for programming these fields. Standard default (*97) values are shown in brackets [ ]; otherwise, default = 0. *00 INSTALLER CODE | | | *17 AC LOSS KEYPAD SOUNDING Enter 4 digits, 0-9 [5140] [1] 1=enable; 0=disable Must be "1" for Commercial Fire installations.
*33 PRIMARY PHONE NUMBER *46 LOW SPEED FORMAT (Primary) [0] 0= ADEMCO Low Speed; 1=Sescoa/Radionics *47 SECONDARY FORMAT [1] 0=Low Speed; 1=Contact ID; 2= ADEMCO High Speed; 3= ADEMCO Express Enter 0-9 for each digit. Enter #11 for *, #12 for #, #13 for 2-second pause *48 LOW SPEED FORMAT (Sec.) *34 SECONDARY PHONE NUMBER [0] 0= ADEMCO Low Speed; 1=Sescoa/Radionics *49 CHECKSUM VERIFICATION [0] [0] 1=enable; 0=disable *50 SESCOA/RADIONICS SELECT Enter 0-9 for each digit.
*77 AUTO TROUBLE RESTORE Zones that were in a bypassed state at the time a System Shutdown is sent from the Compass Downloading software will be unbypassed when the System Shutdown is removed. [1] 0=disable, 1=enable *79 ZONE TYPE RESTORE ENABLES FOR ZONE TYPES 1*12 PROGRAM NOTIFICATION SIGNAL [1] 1=yes; 0=no Must be "1" for Commercial Fire installations. 1-8 1 2 3 4 5 6 7 1*13 SYSTEM SENSOR REVERSING RELAY – Not Used.
1*29 RF TX LOW BATTERY REPORTING 1*53 DOWNLOAD CALLBACK [0] 1=enable; 0=disable Must be 1 for UL installations. 1*30 RF RCVR CHECK-IN INTERVAL 1=callback not required; 0=callback required. Must be "0" for Commercial Burglary and Commercial Fire installations. | [02] 1*55 EUROPEAN DATE FORMAT 02-15 times 2 hours; 00 disables supervision Maximum is 2 (4 hr) for UL installations. 1*31 RF XMITTER CHECK-IN INTERVAL [0] 0=disable (mm/dd/yy); 1=enable (dd/mm/yy).
1*76 CONTROL RELAY | [00] 2*10 ALLOW DISARMING ONLY DURING Relay will be pulsed for 2 seconds whenever code + [0] is pressed. Enter relay number 01-96; 00=none. Must be "00" for Commercial Burglary and Commercial Fire installations. 1*77 LOG FIRST MAINTENANCE SIGNAL ARMING/DISARMING WINDOWS 0=disable; 1=enable See system-wide field 2*11 if enabling field 2*10. This feature adds high security to the installation.
3*13 FIRE SUPERVISORY RESPONSE TO OPEN/SHORT (Applies to Zone Type 18) 3*59 ENABLE BELL 2 & AUX RELAY [0] CHIME ANNUNCIATION 3*60 BELL 2 & AUX RELAY TIMEOUT 0=silence on code = off; 1=silence when waterflow restores NOTE: Must be set to “0” for Commercial Fire Installations. 3*61 AUX RELAY FUNCTION Enter 00-15 times 2 seconds Delay cannot exceed 90 seconds in UL installations. NOTE: Must be "00" for Commercial Fire installations.
Partition-Specific Fields (Duplicate this page for each partition in the installation.) To program these fields, 1. Press *91 to select a partition. 2. Enter a partition-specific field number (ex. *09). 3. Make the required entry. 4. Repeat steps 1-3 for each partition in the system.
1*45 EXIT DELAY SOUNDING 2*18 ENABLE GOTO FOR THIS PARTITION [1] 1=enable; 0=disable Produces quick beeping during exit delay if enabled. NOTES: Must be set to “0” in partition 1 for fire systems. Must be enabled “1” for SIA installations. See page 32, “SOUND OPTION”, prompt for disabling the entry/exit beeps on individual 1*47 CHIME ON BELL 1 1=Allow log-on from other partitions; 0=disable NOTE: Must be disabled (0) for partition 1 in Commercial Fire installations.
Programming With #93 Menu Mode NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should be programmed via Device programming. After programming all system related programming fields in the usual way, press #93 while still in programming mode to display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.
PROMPT EXPLANATION OUTPUT PGM? 1 = YES 0 = NO For defining output relay functions. 0 Not Used. Must be set to “0”. RLY VOICE DESCR? 1 = YES 0 = NO 0 CUSTOM INDEX? 1 = YES 0 = NO 0 Not Used. Must be set to “0”. Not Used. Must be set to “0”. ACCESS POINT PGM 1 = YES 0 = NO 0 ACCESS GRP PGM 1 = YES 0 = NO 0 Not Used. Must be set to “0”. Not Used. Must be set to “0”. EVENT/ACTION PGM 1 = YES 0 = NO 0 For defining the schedule for the system to automatically call the downloader.
PROMPT EXPLANATION 010 ZONE TYPE PERIMETER Each zone must be assigned a zone type, which defines the way in which the system responds to faults in that zone. Refer to the Zone Type Definitions section in the VISTA-128FBP/VISTA-250FBP Installation and Setup Guide for detailed definitions of each zone type. Enter the zone type desired (or change it, if necessary). Available zone types are listed below.
PROMPT EXPLANATION 010 Silent ? 1 = YES 0 = NO 1 If you selected response type 1, 2, 3, 4, 5, or 10, this prompt will appear. Enter 1 to enable. The zone follows all the selected response type’s characteristics, except in the alarm condition, the alarm output and the keypad sounder do not sound and the keypad does not display the alarm condition. Enter 0 to disable. Press [✱] to continue.
PROMPT EXPLANATION 010 V-PLEX RELAY? 1 = YES 0 = NO If you selected input type 6, this prompt is displayed. Enter 1 if using a 4101SN Relay Module for this zone. Otherwise enter 0. Press [✱] to continue. 010 CONS ECP ADDR (00-30) 01 If you selected input type 09, this prompt is displayed. Enter the ECP address of the keypad that is being used for entry/exit for this access point (00-30). Press [✱] to continue. 010 ACCESS POINT (01-15) 01 If you selected input types 06 this prompt is displayed.
5800 Series Transmitters Loop Designations PROMPT EXPLANATION XMIT TO CONFIRM PRESS ✱TO SKIP Confirmation Option: This prompt only appears if you answered “Yes” at the first prompt. The system enters a confirmation mode so that the operation of the actual programmed input can be confirmed. Activate the loop input or button that corresponds to this zone. At any time during this step, you may press the [✱] key on the keypad to save the serial and loop number combination without confirming.
Expert Mode Zone Programming Expert mode allows you to program zones using the minimum number of screens and keystrokes. Expert Mode Zone Programming does not provide the capability to program some of the zone’s attributes, such as Arm w/Fault, Vent Zone, STAY mode, Auto-STAY, Bypass Group, etc. If you want to program a zone for any of these attributes, you must use Zone Programming. Enter the Programming mode with [Installer Code] + 8 0 0 0 Before programming your zones, do the following: 1.
PROMPT EXPLANATION ZN B M V A C E AD 010 2 1 1 0 1 1 01 Enter the remainder of the zone’s information, or press the [C] key to copy the zone attributes on this screen from the last saved zone. B = Bell/Relay Assignment M = Maintenance (only used if “In” = 3 or 6) V = Do Not Use. Must be set to “0”. AC = Access Point (only used if In = 6) E = Do Not Use. Must be set to “0”.
Report Code Programming All report codes are entered using #93 Menu Mode Programming, either through Report Code Programming, or through Zone Programming while entering other zone information. In the VISTA-128FBP/VISTA-250FBP, reports are divided into six categories. These categories represent the main menu options in Report Code Programming.
Restore/Supervisory Codes PROMPT EXPLANATION RESTR, SUPV. CODE 1 = YES 0 = NO 0 Press [1] (Y) to enter Restore and Supervisory Codes for zones. ENTER ZN FOR GRP 000 = QUIT 001 Enter one zone for each group of 16 zones (001-016, 017-032, etc.). ALARM RESTORE GRP 001-016 00 Enter the first digit of the Alarm Restore Report Code for this group of zones (double-digit entry).
PROMPT EXPLANATION Enter the rest of the codes in the same manner. Other report codes in System Group #1 are: • Opening (Disarm) Also, enable this if you desire Callback Requested reports (the panel answers a phone call from the downloader). • System Low Battery • Low Battery Restore • AC Loss • AC Restore • Periodic Test • Power • Cancel • Program Tamper Once you have entered these report codes, the system prompts you with the Quit menu.
PROMPT EXPLANATION Enter the rest of the codes in the same manner. Other codes in System Group #3 are: • Early Close • Late Open • Late Close • Failed to Open • Failed to Close • Auto-Arm Failed • Schedule Change Once you have entered these report codes, the system prompts you with the Quit menu. QUIT REPORT MENU 1 = YES 0 = NO 0 If you have completely finished entering report codes, press [1] (Y) to quit Report Code Programming.
Alpha Descriptors Programming You can program a user-friendly English language description/location for all protection zones, relays, keypad panics, polling loop short, and RF receiver supervision troubles. Each description can be composed of a combination of words (up to 3) that are selected from a vocabulary of 244 words stored in memory, and any word can have an "s" or " 's " added to it.
4. 5. 6. 7. Accept the word. To accept the word, press [6], which switches back to the alphabet list for the next word, or press [8] to store the complete descriptor and then exit. Select the next word. For selection of the next word (DOOR), repeat step 3a (word #057) or 3b, but selecting the word "DOOR.” To accept the word, press [6], which again switches back to alphabet list. Store the descriptor. When all desired words have been entered, press [8] to store the description in memory.
3. 4. 5. 6. 7. Type the word using one of two methods as follows: a) Press [#], followed by the 2-digit entry for the first letter you would like to display (e.g., 65 for "A"). When the desired character appears, press [6] to select it. The cursor will then move to the right, in position for the next character. Press [#] plus the 2-digit entry for the next letter of the word. or b) Press 3 to advance through the list of symbols, numbers, and letters. Press 1 to move back through the list.
Alpha Descriptor Vocabulary (For entering alpha descriptors. To select a word, press [#] followed by the word's 3-digit number.) NOTE: This vocabulary is not to be used for relay voice descriptors. See the Relay Voice Descriptors section when programming relay voice descriptors.
Device Programming This menu is used to program keypads, receivers, and relay modules, etc. Device Address 00 is always set as an alpha keypad assigned to Partition 1 with no sounder suppression options, and these settings cannot be changed. From Data Field Programming mode, press #93 to display "ZONE PROG?" Press [0] repeatedly to display "DEVICE PROG?" PROMPT EXPLANATION DEVICE PROG? 1=YES 0=NO Press [1] to enter Device Programming.
RF Expander PROMPT 01 RF EXPANDER HOUSE ID EXPLANATION 00 If you selected device type 03 (RF receiver), this prompt appears. Enter the 2-digit House ID (00-31). Press [✱] to accept entry. Output Relay Module PROMPT EXPLANATION 01 SUPERVISED CF? If you selected device type 04 (relay module), this prompt appears. Enter 1 if the unit is a 4204CF. If not, enter 0. If you enter 1, only Relay 1 (Output A) and Relay 3 (Output B) on each module may be programmed for functions.
The 6160/6160CR-2 Keypad displays the following prompts, which are sent by the Communicator to the control. NOTE: These prompts are for the 7845i-ent Communicator only. If you are using a different communicator, refer to the communicator’s instructions for the correct prompts. PROMPT EXPLANATION DEVICE ADDRESS Enter the device address of the Communicator. The default address is 3. ID # Enter the 4-digit customer account number, 0001-9999.
Output Programming The system supports up to 96 outputs. Outputs can be used to perform many different functions and actions. Each output must be programmed to begin one of four types of ACTIONS at a designated START event, and end that ACTION at a designated STOP event. The options used to start and stop these devices are described below, followed by the actual screen prompts and available entries. NOTE: If you are using outputs on the polling loop (e.g.
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a "RESTORE ZONE LIST," you can select a specific zone (response) type or system operation action to de-activate the device. If you choose a specific "ZONE TYPE," any zone of that response type that restores from a previous alarm, trouble, or fault condition will cause the device to de-activate. If you choose a "SYSTEM OPERATION," that operation causes the device to de-activate.
Choices for Start/Stop Zone Types and System Operations: 00 = No Response (Not Used) 22 = Disarming (Code + Off) 01 = Entry/Exit #1 23 = No Alarm Response 27 = Access Point (allows more than one 02 = Entry/exit #2 03 = Perimeter relay to be controlled by activation if access 04 = Interior Follower point request) - Not Used 05 = Trouble Day/Alarm Night 28 = MLB Supervision - Not Used 06 = 24-Hr. Silent 29 = Momentary Exit - Not Used 07 = 24-Hr. Audible 30 = On Second Code + Off 08 = 24-Hr.
PROMPT EXPLANATION 02 RELAY TYPE V-PLEX Enter 0 for V-Plex (polling loop) devices. Enter 1 for (ECP) relay modules (4204/4204CF). Press [✱] to continue. 0 02 V-PLEX ZONE # 000 For polling loop trigger outputs (4101SN), enter the protection zone number (001-250) linked to each output, if used. Be sure to enroll the module’s serial number (see Zone Programming). Press [✱] to continue.
Relay Voice Descriptors Each voice descriptor can consist of up to 3 words selected from the Relay Voice Descriptors and Custom Word Substitutes Vocabulary list (later in this section). The index numbers from this vocabulary list are to be used for relay voice descriptors only. For normal system voice annunciation (e.g., alarms, troubles, status), use the highlighted words in the alpha vocabulary list in the Alpha Programming part of this guide. To enter relay voice descriptors, do the following: 1.
Relay Voice Descriptors and Custom Word Substitutes Vocabulary Word Index Air ............................ 116 Alarm ....................... 255 And .......................... 067 Apartment ................ 117 Appliances ............... 161 Area ......................... 118 Attic.......................... 119 Back......................... 121 Bar ........................... 122 Basement................. 021 Bathroom ................. 051 Battery ..................... 053 Bedroom ..................
Scheduled Check-in The system can be programmed to call the downloader automatically, at a scheduled time. Once the connection is made, the downloader can perform any and all functions (arm, disarm, upload, etc.). The downloader determines the functions it performs. To enter scheduled check-in, do the following: 1. From Data Field Programming mode, press #93 to display the "ZONE PROG?" prompt. 2. Press [0] (NO) to each menu option until the "SCHEDULED CHK-IN" prompt is displayed.
System Layout Worksheets Before programming any security system, you should first define the installation. To help you lay out a partitioned system, use the following worksheets. This will further simplify the programming process. NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and the event log capacity, use the VISTA-250FBP’s features.
PRINTER OPTIONS Parallel or Serial printer 12- or 24-hour Time format Printer On-Line (yes/no) 1200 or 300 baud Printer Baud Rate Addr Type Part Sound Opt 00. 01. 02. 03. 04. 05. 06. 07. 08. 09. 10. 11. 12. 13. 14. 15. 16. 17. 18. 19. 20. 21. 22. 23. 24. 25. 26. 27. 28. 29. 30.
ACCESS CODES and USER DEFINITIONS FOR PARTITIONS 3 and 4 4-digit Security Code Access Group 0; 1-8 4-digit Security Code Access Group 0; 1-8 4-digit Security Code Access Group 0; 1-8 3-Digit User # Auth. Level Partition 3 Open/ Group Close Bypass RF Key Global Arm 3-Digit User # Auth. Level Partition 4 Open/ Group Close Bypass RF Key Global Arm RF Key Global Arm RF Key Global Arm ACCESS CODES and USER DEFINITIONS FOR PARTITIONS 5 and 6 3-Digit User # Auth.
— 45 — 25 24 23 22 21 20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 001-025 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 46 — 50 49 48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33 32 31 30 29 28 27 26 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 026-050 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 47 — 75 74 73 72 71 70 69 68 67 66 65 64 63 62 61 60 59 58 57 56 55 54 53 52 51 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 051-075 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 48 — 100 99 98 97 96 95 94 93 92 91 90 89 88 87 86 85 84 83 82 81 80 79 78 77 76 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 076-100 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 49 — 125 124 123 122 121 120 119 118 117 116 115 114 113 112 111 110 109 108 107 106 105 104 103 102 101 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 101-125 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 50 — 150 149 148 147 146 145 144 143 142 141 140 139 138 137 136 135 134 133 132 131 130 129 128 127 126 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 126-150 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 51 — 175 174 173 172 171 170 169 168 167 166 165 164 163 162 161 160 159 158 157 156 155 154 153 152 151 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 151-175 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 52 — 200 199 198 197 196 195 194 193 192 191 190 189 188 187 186 185 184 183 182 181 180 179 178 177 176 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 176-200 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 53 — 225 224 223 222 221 220 219 218 217 216 215 214 213 212 211 210 209 208 207 206 205 204 203 202 201 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 201-225 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
— 54 — 250 249 248 247 246 245 244 243 242 241 240 239 238 237 236 235 234 233 232 231 230 229 228 227 226 Zone No. Zone Type Part 1-8 Input Type Arm w/Fault Vent Zone STAY Mode AutoSTAY Silent Bypass Access Panel Tamper Group Point ID # Serial # / Loop ZONE DEFINTION FOR ZONES 226-250 Bell/Relay Activation Rpt. Code Zone Information & Alpha Descriptor (3 words max.
ZONE DEFINITIONS FOR KEYPAD PANIC ZONES 995, 996, and 999 Enter yes/no for each partition-field *22 Zone No. Zone Type 1 2 3 4 5 6 7 8 Bell/Relay Activation Report Code Zone Information and Alpha Descriptor (3 words max.) 995 (see note below) 996 999 NOTE: Do Not Use Zone No. 995 in a Fire Alarm application. ZONE DEFINITIONS FOR SYSTEM ZONES; 970 − 975, 988; 990 and 997 Zone No. Zone Type Bell/Relay Activation Zone Information and Alpha Descriptor (three words max.
ZONE DEFINITIONS FOR RELAY SUPERVISORY ZONES 601-632 Zone No. Zone Type Report Code Zone Information and Alpha Descriptor (3 words max.) Zone No. 601 617 602 618 603 619 604 620 605 621 606 622 607 623 608 624 609 625 610 626 611 627 612 628 613 629 614 630 615 631 616 632 Zone Type Report Code Zone Information and Alpha Descriptor (3 words max.) NOTE: Only the relays on 4204CF modules may be supervised.
ZONE DEFINITIONS FOR SUPERVISORY OF ECP DEVICE ZONES 800-830 Zone No. Zone Type Zone Information and Alpha Descriptor (3 words max.) Report Code Zone No. 800 816 801 817 802 818 803 819 804 820 805 821 806 822 807 823 808 824 809 825 810 826 811 827 812 828 813 829 814 830 Zone Type Report Code Zone Information and Alpha Descriptor (3 words max.
Output Devices Worksheets Applicable only if relays (4204/4204CF) or V-Plex are used. Output Devices – Programmed in the #93 Menu Mode in the Output Programming Section. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence. For 4204/4204CF, the Device Programming section must be programmed for the device address. Set the NOTES: 1. DIP switches on the device for that address. 2.
OUTPUT DEVICES WORKSHEET (cont’d) S T A R T OUTPUT DEV # A EV/ZL Zone S T O P ZT / P ZL ZT / P 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 — 59 — Relay Group Restrict 0=V-Plex 1=4204/ 4204CF V-Plex Zone # or Dev Add 4204/4204CF Relay # for 4204/ 4204CF
OUTPUT DEVICES WORKSHEET (cont’d) S T A R T OUTPUT DEV # A EV/ZL Zone S T O P ZT / P ZL ZT / P 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 — 60 — Relay Group Restrict 0=V-Plex 1=4204/ 4204CF V-Plex Zone # or Dev Add 4204/4204CF Relay # for 4204/ 4204CF
OUTPUT DEVICES WORKSHEET (cont’d) S T A R T OUTPUT DEV # A EV/ZL Zone S T O P ZT / P ZL ZT / P 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 — 61 — Relay Group Restrict 0=V-Plex 1=4204/ 4204CF V-Plex Zone # or Dev Add 4204/4204CF Relay # for 4204/ 4204CF
A = DEVICE ACTION 0 = No Response; 1 = Close for 2 sec; 2 = Close and stay closed; 3 = Pulse on and off; 4 = Toggle alternately between START and STOP events EV = EVENT 0 = Not used; 1 = Alarm; 2 = Fault; 3 = Trouble; 4 = Restore ZL = ZONE LIST 01-15, 00 = Not Used "START" ZONE LIST: Upon alarm, fault, trouble or restore of ANY zone in this list, device action will START. "STOP" ZONE LIST: Upon restore of ALL zones on this list, device action will STOP. It need not be same list as used for START.
Zone List 5: Started or stopped by zone numbers (enter 000 to end entries). Zone List 6: Started or stopped by zone numbers (enter 000 to end entries). Zone List 7: Started or stopped by zone numbers (enter 000 to end entries). Zone List 8: Started or stopped by zone numbers (enter 000 to end entries). Zone List 9: Started or stopped by zone numbers (enter 000 to end entries). Zone List 10: Started or stopped by zone numbers (enter 000 to end entries).
Scheduling Menu Prompts To program schedules, enter Scheduling program mode by pressing [User Code] + # + 80 to display the first choice of the menu driven programming functions. NOTE: Only users with an Installer or Master level user code may enter the #80 mode. Press 0 (NO) or 1 (YES) in response to the displayed menu selection. Pressing 0 will display the next choice in sequence.
Scheduling Worksheets Time Windows Definitions Worksheet. The system provides 20 time windows that are defined with start and stop times. They are programmed in the #80 Menu Mode. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Holiday Schedule Worksheet: The system provides up to 16 holidays that can be assigned for the system. Each holiday can be assigned to any combination of partitions. Fill in the required data on the worksheet below and follow the procedure in the installation instructions as you enter the data during the displays and prompts that appear in sequence.
Automatic Refresh: The system automatically updates the status of all Time-Driven Events upon any of the following occurrences: • Changing of the time or date via #63 mode • Exiting #80 Scheduling Menu mode • Exiting Program mode • After a disconnect from the downloader • On a power-up • At Daylight Saving Time adjustment. Below is a list of the "Action" codes (desired actions) used when programming time-driven events.
Activation time: Refers to when the action is to take place relative to the time window. 1 = Beginning of time window 4 = Beginning and end of time window 2 = End of time window 5 = Random Start of the time window ✳ 3 = During time window active period only (On at 6 = Random End of the time window ✳ beginning of window, off at end). 7 = Random During the time window ✳ ✳ The activation time of the window is randomized up to 30 minutes and is initialized by either of two methods: a.
Partition/Windows 3 Mon Tue Wed Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window 4 Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window 5 Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window 6 Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window 7 Start Time HH:MM Stop Time HH:MM Disarm Window Start Time HH:MM Stop Time HH:MM Arm Window 8
NOTES — 70 —
8 Seconds 8 Seconds 8 Seconds Control Unit Delay, Seconds Model BL BL OUTPUT 1 + 2k 2k (NOTE 5) 5. Maximum Loop Impedance is 1.17 ohms. 4. No more than one (1) wire per terminal may be connected. 6. 2k EOLR is Ademco Model EOL20. 6 + + 6 7 8 13 Blk Grn 12 KEYPAD PORT #1 Red 11 10 9 5 9 14 Yel ECP Bus: Max. Line Impedance: 50 Ohms Special Application Circuit. Fire & Burglary Devices on the ECP Bus must be isolated using an ECP Isolator.
2 Corporate Center Drive, Suite 100 P.O. Box 9040, Melville, NY 11747 Copyright © 2009 Honeywell International Inc. www.honeywell.com/security ÊK0376PRV26Š K0376PRV2 7/09 Rev.