SECURITY ACCESS AND SURVEILLANCE SECTION 13850 VISTA 250FBP ARCHITECT AND ENGINEER SPECIFICATION FOR SECURITY SYSTEM ADEMCO Group 165 Eileen Way Syosset, New York 11791 1-800-645-7568
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. B. C. 1.02 Section Includes 1. Control Panel 2. Associated Equipment Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring Devices 2. Section 16530 - Emergency Lighting Related Sections 1. Section 13700 - Security Access and Surveillance 2. Section 13800 - Building Automation and Control REFERENCES A. B. C. Underwriters Laboratories (UL): 1.
1.03 2. NFPA 72 – National Fire Protection Code The system shall be a Burglary/Access Control/CCTV Switching System that includes the following capabilities: 1. Listed for UL Commercial Fire and Burglary. 2. Supports up to 250 zones. 3. Supports up to eight (8) separate partitions. 4. Supports up to 250 users. 5. Supports commercial wireless devices. 6. Provides integrated security, access control, and CCTV switching capability. 7. Provides supervision of peripheral devices. 8.
A. Control Panel - The control panel shall be an eight (8)-partition, UL commercial fire and burglary control panel that supports up to 250 zones using basic hardwired, polling loop, and wireless zones. It shall also provide supervision of two (2) notification appliance output circuits (NAC), RF receivers, and relay modules. In addition, the control shall provide the ability to schedule time-driven events, and allow certain operations to be automated by pressing a single button.
(5) b. 3. Wireless Expansion – The control shall support up to 250 wireless zones using a 5800 series RF receiver (fewer if using hardwire and/or polling loop zones). Wireless zones shall have the following characteristics: (1) Supervised by control panel for check-in signals (except certain non-supervised transmitters). (2) Tamper-protection for supervised zones. (3) Individually assignable to one of eight (8) partitions. (4) Individually assignable to bell outputs and/or auxiliary relays.
capable of being assigned the same or a different level of authority for each partition that it will operate. 5. 6. 7. b. Opening/Closing central station reporting option. c. Specific partitions that the code can operate. d. Global arming capability (ability to arm all partitions the code has access to in one command). e. Use of an RF (button) to arm and disarm the system (RF key must first be enrolled into the system).
8. 9. c. Activated manually. d. Assigned an alpha descriptor. e. Used for Class B, Style-Y supervised bell outputs (4204CF module). f. A combination of 4204 (ECP) and 4101SN (polling loop) relays. Optional Vista Interactive Phone Module – The control shall support the ADEMCO 4285/4286 VIP Modules, which permit access to the security system in order to perform the following functions: a. Obtain system status information. b. Arm and disarm the security system. c. Control relays.
13. 14. a. Providing a command that activates relays to allow access doors to open (e.g., lobby door), lights to be turned on or off, etc. b. Becoming a fully integrated access control system by using numerous VistaKey Single-Door Access Control Modules. c. Supporting up to 15 VistaKey Access Control Modules. The VistaKey Access Control Modules shall use the same Compass Downloader as the Vista-250BP and shall be programmable from the Compass Downloader or the Keypad/Annunciators. d.
e. ADEMCO 5869 Wireless Hold Up Switch/Transmitter - This device shall be UL 636 listed for commercial burglary applications. 15. Optional Keyswitch – The control shall support the ADEMCO 4146 Keyswitch on any one of the system's 8 partitions. If used, zone 7 is no longer available as a protection zone. 16. Voltage Triggers – The system shall provide voltage triggers, which change state for different conditions.
b. c. (2) Sescoa/Radionics. (3) ADEMCO Express. (4) ADEMCO High Speed. (5) ADEMCO Contact ID. Backup reporting – The system shall support backup reporting via the following: (1) Secondary phone number. (2) ECP long-range radio (LRR) interface. (3) Option to select long range radio (LRR) or dialup as the primary reporting method (dynamic signaling feature). Internet reporting – The system shall be capable of communicating with the central station via the internet using Alarmnet-i.
25. 26. 27. 28. a. Bypass the faulted E/E zone(s) and/or interior zones and arm the system. b. Generate an Exit Error report by user and by zone so the central station knows it was an exit alarm and who caused it. Enhanced Fire Walk-Test Mode – The Control Panel shall provide the installer with the following features: a. Automatic test of all integrated remote point module (RPM) devices, equipped with an automatic test feature. b.
29. Automation Software - The Control shall be capable of interfacing with automation software via an RS232 input on a single partition. The control panel shall be the ADEMCO VISTA-250FBP Commercial Burglary Partitioned Security System or equivalent. 2.02 ENCLOSURE A. 2.03 The Control Panel shall be enclosed in a metal cabinet, suitable for wall mounting. The dimensions shall not exceed 18 inches (45.7 cm) in height, 14.5 inches (36.8 cm) in width or 4.3 inches (10.9 cm) in depth.
4. Electromagnetic Interference – The system shall meet or exceed the requirements of FCC Part 15, Class B devices, FCC Part 68, IEC EMC directive. PART 3 EXECUTION 3.01 3.02 EXAMINATION A. Submission of a proposal confirms that the Contract Documents and site conditions are accepted without qualifications unless exceptions are specifically noted. B.
2. The Contractor shall provide staff to test all devices and all operational features of the System for witness by the Owner’s representative and the Authority having jurisdiction. The Contractor shall provide two-way radio communications to assist in the testing. All testing must be witnessed by the owner’s representative, prior to acceptance. 3. The testing and certification shall take place as follows: 4. a. System shall be tested in conjunction with the manufacturer’s representative. b.