User`s manual

VISTA-50PEN Installation and Setup Guide
20-2
Type 02: Entry/Exit #2 Burglary
Provides a secondary entry delay whenever the zone is faulted and the system is armed in
the AWAY and STAY mode. When the panel is armed in the INSTANT or MAXIMUM mode,
no entry delay is provided. Secondary exit delay begins whenever the control is armed,
regardless of the arming mode selected. These delays are programmable.
Assign this zone type to zones that are used for entry and exit of the facility and require more
time than the primary entry and exit point. Delay times for this zone type must be greater
than zone type 01 (e.g., a garage, loading dock, or basement door).
Type 03: Perimeter Burglary
Provides an instant alarm if the zone is faulted and the system is armed in the AWAY, STAY,
INSTANT or MAXIMUM mode.
Assign this zone type to all zones of exterior doors and windows.
Type 04: Interior, Follower
Provides a delayed alarm (using the programmed entry delay time) if an entry/exit zone is
faulted first. Otherwise it produces an instant alarm. It is active when the system is armed in
the AWAY or MAXIMUM mode, but the MAXIMUM mode eliminates the entry delay.
Interior Follower zones are
automatically bypassed when the panel is armed in the
STAY or INSTANT mode
.
Assign this zone type to a zone covering an area such as a foyer, lobby, or hallway through
which one must pass upon entry or exit (to and from the keypad).
Type 05: Trouble by Day/Alarm by Night
Provides an instant alarm if the zone is faulted and the system is armed in the AWAY, STAY,
INSTANT or MAXIMUM mode. During the disarmed state (day), the system annunciates a
latched trouble sounding from the keypad (and a central station report, if desired).
Assign this zone type to a zone that contains a foil-protected door or window (such as in a
store), or to a zone covering a “sensitive” area such as a stock room, or drug supply room. It
can also be used on a zone in an area where immediate notification of an entry is desired.
Type 06: 24-Hour Silent Alarm
Sends a report to the central station but provides no keypad display or sounding. Assign this
zone type to a zone containing an Emergency button.
Type 07: 24-Hour Audible Alarm
Sends a report to the central station and provides an alarm sound at the keypad and an
audible external alarm.
Assign this zone type to a zone containing an Emergency button.
Type 08: 24-Hour Auxiliary Alarm
Sends a report to central station and provides an alarm sound at the keypad only.
(No bell
output is provided.)
Assign t
his zone type to a zone
an Emergency button
, or one
containing monitoring devices such as water sensors, or temperature sensors.
Type 09: Supervised Fire (Without Verification)
Provides a fire alarm on a short circuit and a trouble condition on open circuit. A fire alarm
produces a pulsing of the bell output. A zone of this type is always active and cannot be
bypassed.