User`s manual

22-1
SECTION 22
Data Field Descriptions
•••••••••••••••••••••••••••••••••••••••••••••••••
The following is a description of all data fields provided by this control. If you have followed
earlier instructions during the installation of the various devices, some of these fields may
already have been programmed.
If you need more information about actual programming procedures, see
The Mechanics of
Programming
section
.
*00 INSTALLER CODE
[4140]
|||
The Installer’s Code is a 4-digit code reserved for installation company use. This is the
only code that can be used to enter the Program Mode from the keypad. This code
cannot be used to disarm the system if not used to arm the system. This code cannot
reenter Programming Mode if exited by the *98 command.
*09 ENTRY DELAY #1 (partition-specific)
[02]
|
Entry delay defines the delay time which allows users to re-enter the premises through
a door that has been programmed as an entry delay door and disarm the system without
sounding an alarm. The system must be disarmed within this period or an alarm will
occur. Enter the entry delay time (
01-15
multiplied by 15 seconds, or
00
for no delay),
up to a maximum delay of 225 seconds (entry
15
multiplied by 15 seconds), for zones
assigned to Zone Type 01.
*10 EXIT DELAY #1 (partition-specific)
[03]
|
Exit delay defines the delay period that allows users to leave the premises through a
door that has been programmed as an entry/exit delay door after arming the system
without setting off the alarm. Enter the exit delay time (
01-15
multiplied by 15 seconds
or
00
for no delay), up to a maximum delay of 225 seconds, for zones assigned to Zone
Type 01.
*11 ENTRY DELAY #2 (partition-specific)
[06]
|
Entry Delay #2 is used for a secondary door requiring a longer delay than those
assigned to Entry Delay #1. This delay may not exceed 45 seconds for UL commercial
burglary installations.
*12 EXIT DELAY #2 (partition-specific)
[08]
|
Exit Delay #2 is used for a secondary door requiring a longer delay than those assigned
to Exit Delay #1. This delay may not exceed 60 seconds for UL commercial burglary
installations.
*13 BELL TIMEOUT (partition-specific)
[04]
|
Defines the length of time Bell Output 1 and the keypad's sounder will sound for all
audible alarms (multiply entry 01-15 by 2 minutes for actual duration).
Must be a minimum of 16 minutes for UL commercial burglary installations.