Specifications
7-8 Error Messages
600561-A
E0 A cartridge is stuck in the Gripper Assembly
Perform the following:
• Turn off the main power Switch located on the lower panel of the rear door of
all modules.
• Open the front door of the module where the Accessor is located.
• Lift the Accessor to the top of the Y axis rail and insert an allen wrench to stop
the Accessor from sliding down.
• Pull open the Insert/Eject Station.
• If necessary, gently move the Accessor along the X axis rail until the Accessor
is directly in front of the opened Insert/Eject Station.
• Gently pry apart the Accessor gripper fingers while moving the cartridge
from side to side.
• After the cartridge is free, close the Insert/Eject Station, remove the allen
wrench from the Accessor Y axis rail, close the front door, and apply power
to the Scalar 1000 modules.
If the problem is not corrected or persists, contact ATAC.
E1 The Insert/Eject Station door is not fully closed, Operator Intervention is
required to close the door.
Close the Insert/Eject Station door.
E2 The front door(s) are not fully closed, Operator Intervention is required to
close the door(s).
Close all the front door(s).
E3 Wrong SCSI bus connection is detected. A Single Ended SCSI device is
connected to Library Port 0 Differential Adapter.
Check the library configuration and make sure that all devices on the library
SCSI port 0 have the same SCSI type.
If the problem is not corrected or persists, contact ATAC.
E4 Wrong SCSI bus connection is detected. A Single Ended SCSI device is
connected to Library Port 1 Differential Adapter.
Check the library configuration and make sure that all devices on the library
SCSI port 1 have the same SCSI type.
If the problem is not corrected or persists, contact ATAC.
Table 7-1
SAC Reporting
Reported
SAC
Perform these actions