Specifications
1-2 Introduction
For example, connecting relay devices to DO channels, the NuDAM-
6011/D can be used to control the high power devices.
The module provides another one digital input channel. This can be used
for general purpose such as monitor digital signal, or be used as input of
the event counter.
Features of NuDAM-6011/D
• 1 analog input channel with differential input
• programmable voltage range with high gain amplifier
• Self offset and gain calibration
• On board CJC for temperature measurement
• 5000 Vrms isolation voltage for AD channel (2500 Vrms for NuDAM-
6011/D)
• 2 digital output channels of open collector type
• Alarm function with high / low alarm output
• 1 digital input channel / event counter
• Programmable host watchdog timer for host failure protection
• Internal watchdog timer for device failure protection
• Easy programming by software
• Easy installation and wiring
• 5 1/2 digital LED Display (NuDAM-6011/D)
Specifications of NuDAM-6011/D
² Interface
• Interface : RS-485, 2 wires
• Speed (bps) : 1200, 2400, 4800, 9600, 19.2K, 38.4K,115.2K (115.2K
only for firmware reversion above A4.00)
² Analog Input
• Input type: Differential input
• Resolution: 16 bits
• Unit Convertion: Thermocouple, mV, V, or mA
• Thermocouple Type: J, K, T, E, R, S, B, N, C
J: 0°C~760°C K: 0°C~1000°C
T: -100°C~400°C E: 0°C~1000°C
R: 500°C~1750°C S: 500°C~1750°C
B: 500°C~1800°C N: -270°C~1300°C
C: 0°C~2320°C
• Voltage Range: Programmable 6 levels
±2.5V, ±1V, ±500mV, ±100mV, ±50mV, ±15mV
• Current Measurement: 20mA (with external 125Ω resistor)