2 Introduction
programming without handy adjustment. This features insure the best
performance under different environment.
The module provides the analog signal monitor or the alarm function.
The high and low bound of the alarm limit is programmable. The alarm
status can be sent to digital output channels if this function is ON. The
supervisor of a factory can ‘see’ or ‘hear’ the alarm if the digital output
channel control a real alarm device. The two digital output channels can
be set for general-purpose use if the alarm is disabled.
For example, connecting relay devices to DO channels, the
NuDAM-6011/D can be used to control the high power devices.
The module provides another one digital input channel. This can be
used for general purpose such as monitor digital signal, or be used as
input of the event counter.
Features of NuDAM-6011/D
1 analog input channel with differential input
Programmable voltage range with high gain amplifier
On board CJC for temperature measurement
5000 Vrms isolation voltage for AD channel (2500 Vrms for
NuDAM-6011/D)
2 digital output channels of open collector type
Alarm function with high / low alarm output
1 digital input channel / event counter
Programmable host watchdog timer for host failure protection
Internal watchdog timer for device failure protection
Easy programming by software
Easy installation and wiring
5 1/2 digital LED Display (NuDAM-6011/D)
Specifications of NuDAM-6011/D
Interface
Interface: RS-485, 2 wires
Speed (bps): 1200, 2400, 4800, 9600, 19.2K, 38.4K,115.2K
(115.2K only for firmware reversion above A4.00)
Analog Input
Input type: Differential input
Resolution: 16 bits
Unit Convertion: Thermocouple, mV, V, or mA
Thermocouple Type: J, K, T, E, R, S, B, N, C
J: 0°C~760°C K: 0°C~1370°C
(1)
T: -100°C~400°C E: 0°C~1000°C
R: 500°C~1750°C S: 500°C~1750°C
B: 500°C~1800°C N: -270°C~1300°C