92 Data Format and Input Range
The following table shows the relation between the input range setting with the
data format and the resolution when using ND-6011/D or 6018 to measure
temperature by thermocouple.
Code
Input Range
Thermocouple
Data
Format
Maximum Minimum
Displayed
Resolution
0E
J (0°C to 760°C)
Eng. Units +760.00 +000.00
0.01°C
0F
K (0°C to 1000°C)
Eng. Units +1000.0 +0000.0
0.1°C
10
T (-100°Cto400°C)
Eng. Units +400.00 -100.00
0.01°C
11
E (0°C to 1000°C)
Eng. Units +1000.0 +0000.0
0.1°C
12
R (500°C to 1750°C)
Eng. Units +1750.0 +0500.0
0.1°C
13
S (500°C to 1750°C)
Eng. Units +1750.0 +0500.0
0.1°C
14
B (500°C to 1800°C)
Eng. Units +1800.0 +0500.0
0.1°C
15
N (-270°C to 1300°C)
Eng. Units +1300.0 -0270.0
0.1°C
16
C (0°C to 2320°C)
Eng. Units +2320.0 +0000.0
0.1°C
Code
Input Range
Thermocouple
Data
Format
Maximum Minimum
Displayed
Resolution
0E
J (0°C to 760°C)
% of FSR +100.00 +000.00 0.01%
0F
K (0°C to 1000°C)
% of FSR +100.00 +000.00 0.01%
10
T (-100°Cto400°C)
% of FSR +100.00 -025.00 0.01%
11
E (0°C to 1000°C)
% of FSR +100.00 +000.00 0.01%
12
R (500°C to 1750°C)
% of FSR +100.00 +028.57 0.01%
13
S (500°C to 1750°C)
% of FSR +100.00 +028.57 0.01%
14
B (500°C to 1800°C)
% of FSR +100.00 +027.27 0.01%
15
N (-270°C to 1300°C)
% of FSR +100.00 -020.76 0.01%
16
C (0°C to 2320°C)
% of FSR +100.00 +000.00 0.01%
Code
Input Range
Thermocouple
Data
Format
Maximum Minimum
Displayed
Resolution
0E
J (0°C to 760°C)
2’s Comp. 7FFF 0000 1 LSB
0F
K (0°C to 1000°C)
2’s Comp. 7FFF 0000 1 LSB
10
T (-100°Cto400°C)
2’s Comp. 7FFF E000 1 LSB
11
E (0°C to 1000°C)
2’s Comp. 7FFF 0000 1 LSB
12
R (500°C to 1750°C)
2’s Comp. 7FFF 2492 1 LSB
13
S (500°C to 1750°C)
2’s Comp. 7FFF 2492 1 LSB
14
B (500°C to 1800°C)
2’s Comp. 7FFF 238E 1 LSB
15
N (-270°C to 1300°C)
2’s Comp. 7FFF E56B 1 LSB
16
C (0°C to 2320°C)
2’s Comp. 7FFF 0000 1 LSB