Introduction 7
Digital Output
Channel numbers: 2
Output characteristic: open collector transistor
Maximum current sink: 50mA
Max. power dissipation: 300mW
Digital Input
Channel numbers: 1
Logical level 0: +1V maximum
Logical level 1: +2.0V~30V
Pull up resister: 10K
Maximum current: 0.5mA
Watchdog Function
Module internal watchdog timer: 150 ms
Power failure threshold: 4.65 V
Host programmable watchdog: 100 ms ~ 25.500 sec
Power
Power supply: +10V to +30V
Current consumption: 1.1 W(2.0W for NuDAM-6012/D)