Initialization & Installation 23
2
Initialization & Installation
2.1 Software Installation
1. If you have already installed “NuDAM Administration” then skip
other steps.
2. Backup your software diskette.
3. Insert “NuDAM Administration” disc into CD-ROM:
4. Change drive to the path of CD-ROM. For example, your drive of
CD-ROM is F:, then change the drive to F:
5. Find the setup of NuDAM Administration and run it.
6. Please follow the steps of setup program then you can successful
to install the nudism Administration.
2.2 Initializing a Brand-New Module
Objective of Initializing a Brand-New NuDAM
All NuDAM modules, except NuDAM-6520 and NuDAM-6510, in a
RS-485 network must have an unique address ID. Every brand-new
NuDAM has a factory default setting as following:
Address ID is 01.
Baud rate is 9600 bps
Check-sum disable
Host Watchdog timer is disable
Therefore, to configure the brand-new NuDAM before using is
necessary to avoid conflicting address. The baud rate may also be
changed according to user‘s requirements.