Manual

Command Set 37
3.3 Set Configuration
@Description
Configure the basic setting of NuDAM, including the address ID, input
range, baud rate, and data format. The new configuration will be
available after executing the command.
@Syntax
%(OldAddr)(NewAddr)(InputRange)(BaudRate)(DataFormat)<CR
>
% Command leading code. (1-character)
(OldAddr)
NuDAM module original address ID. The
default address ID of a brand new module is
01. The value range of address ID is 00 to FF
in hexadecimal.
(2-character)
(NewAddr)
New address ID, if you don’t want to change
address ID, let new address ID equals to the
old one. (2-character)
(InputRange)
Define analog input range, refers to Table 3-1
for details. (2-character)
(BaudRate)
Define communication baud rate, refers to
Table 3-2 for details. (2-character)
(DataFormat)
Define checksum, integration time and output
data format, refers to Figure 3-1 for details.
(2-character)
@Response
!(Addr)<CR>
or
?(Addr)<CR
>
(Addr)
Address ID.
!
Command is valid.
?
Command is invalid, parameter values are invalid, or
change the setting without grounding the DEFAULT*
pin.
(6011/D, 6012/D, 6013
6014D, 6017, 6018)