38 Command Set
Note:
1. When you want to change the checksum or baud rate, the
DEFAULT* pin must be grounded at first.
2. Waiting a maximum of 7 seconds to perform auto calibration and
ranging after the analog input module is reconfigured. Please
don’t execute any other command during this time period.
@Example
User command: %0130050600<CR>
Response: !30<CR>
Item Meaning Description
% (Leading Code) Command leading code.
01 (OldAddr) Original address ID is 01(Hex).
30 (NewAddr) New address ID is 30(Hex).
05 (InputRange)
Analog input range is ±2.5V
06 (BaudRate) Baud rate is 9600.
00 (DataFormat) 00 means data format is engineering
units, checksum is disable and
integration time is 50 ms (60Hz).
<CR> Carriage return 0x0D.