Manual

Command Set 53
3.16 Read All Analog Data Channel
@Description
Read all the enable analog input channel value of a specified from an
analog input module at specified address in a NuDAM network.
@Syntax
#(Addr)A<CR>
# Command leading code. (1-character)
(Addr) Address ID. (2-character)
A
All the enable channel
@Response
>(InputData)(InputData)(InputData)<CR>
>
Delimiter character
(InputData)
Input value from a specified channel number, the
data format is a + or - sign with five decimal digits
and a fixed decimal point.
@Example
User command: #06A<CR>
Response: >+100.88+020.66+006.79<CR>
Read the analog input of AD module at address 06 (Hexadecimal) in the
network. The analog input data are +100.88 °C for channel 0, +020.66
°C for channel 1 and +006.79°C for channel 3. (Data format is
engineering unit).
(6013, 6017, 6018)