Manual

72 Command Set
3.34 Enable Alarm
@Description
Enable alarm to Latch mode or Momentary mode at specified analog
input module.
@Syntax
@(Addr)EA(Mode)<CR>
@
Command leading code.
(Addr)
Address ID
EA
Enable alarm command code
(Mode) M: enable alarm to MOMENTARY mode.
L: enable alarm to LATCH mode.
@Response
!(Addr)<CR>
!
Command is valid.
(Addr)
Address ID.
@Example
User command: @06EAL<CR>
Response: !06<CR>
Enable alarm to LATCH mode at address 06H.
User command: @06EAM<CR>
Response: !06<CR>
Enable alarm to MOMENTARY mode at address 06H.
(6011/D, 6012/D, 6014D)