Manual

90 Data Format and Input Range
4.2 Analog Input Range
The following table shows the relation between the input range setting
with the data format and the resolution.
Engineering Units Table:
Code
Input
Range
Data
Format
+Full
Scale
Zero
- Full
Scale
Displayed
Resolution
00
±15mV
Eng. Units +15.000
±00.000
-15.000
1µV
01
±50mV
Eng. Units +50.000
±00.000
-50.000
1µV
02
±100mV
Eng. Units +100.00
±000.00
-100.00
10µV
03
±500mV
Eng. Units +500.00
±000.00
-500.00
10µV
04
±1V
Eng. Units +1.0000
±0.0000
-1.0000
100.00µV
05
±2.5V
Eng. Units +2.5000
±0.0000
-2.5000
100.00µV
06
±20mA
Eng. Units +20.000
±00.000
-20.000
1µA
07 Reserved
08
±10V
Eng. Units +10.000
±00.000
-10.000 1mV
09
±5V
Eng. Units +5.0000
±0.0000
-5.0000
100.00µV
0A
±1V
Eng. Units +1.0000
±0.0000
-1.0000
100.00µV
0B
±500mV
Eng. Units +500.00
±000.00
-500.00
10µV
0C
±150mV
Eng. Units +150.00
±000.00
-150.00
10µV
0D
±20mA
Eng. Units +20.000
±00.000
-20.000
1µA
Code Input Range
Data
Format
+Full
Scale
Zero
- Full
Scale
Disp.
Reso.
20
Pt-100, -100°C to
+100°C, α=0.00385
Eng.
Units
+100.0
0
±000.0
0
-100.00
0.01°C
21
Pt-100, 0°C to
+100°C, α=0.00385
Eng.
Units
+100.0
0
+000.00
+000.0
0
0.01°C
22
Pt-100, 0°C to
+200°C, α=0.00385
Eng.
Units
+200.0
0
+000.00
+000.0
0
0.01°C
23
Pt-100, 0°C to
+600°C, α=0.00385
Eng.
Units
+600.0
0
+000.00
+000.0
0
0.01°C
24
Pt-100, -100°C to
+100°C, α=0.003916
Eng.
Units
+100.0
0
±000.00
-100.00
0.01°C
25
Pt-100, 0°C to
+100°C, α=0.003916
Eng.
Units
+100.0
0
+000.0
0
+000.0
0
0.01°C
26
Pt-100, 0°C to
+200°C, α=0.003916
Eng.
Units
+200.0
0
+000.00
+000.0
0
0.01°C
27
Pt-100, 0°C to
+600°C, α=0.003916
Eng.
Units
+600.0
0
+000.00
+000.0
0
0.01°C
28
Ni-100, 0°C to +100°C
Eng.
Units
+100.0
0
+000.00
+000.0
0
0.01°C
29
Ni-120, 0°C to +100°C
Eng.
Units
+100.0
0
+000.00
+000.0
0
0.01°C