Pollution degree (PD)
PD2
6.2 ADX DAS Installation Procedure
6.2.1 HE Installation Procedure
CAUTION: ADX DAS HE should be installed inside building only.
6.2.1.1 Installing a ADX DAS HE in a rack
The ADX HE chassis mounts in a standard 19” (483mm) equipment rack. Allow clearance of 3” (76mm) at the
front and rear, and 2” (51mm) on both sides for air circulation. No top or bottom clearance is required.
x Consideration:
- Eight mounting holes are located on 4 corners of ADX HE to attach it to the 19” rack. The ADX HE
must be securely attached to a rack that can support the weight of the ADX.
x Mount procedure
- The following steps should be followed while mounting the ADX HE
! Detach the wall mount bracket assembled located at the base of the ADX-HE chassis
! Verify that the HE and Mounting holes are in good condition
! Set the ADX DAS HE against the 19”rack and secure the unit with screws
! Verify that ADX HE is securely attached
! Connect the GND cable
! Connect the RF cable
! Connect the Power
! Connect the Optic cable