7.1.3 Check Navigation Tree Status
x Check whether the status of navigation tree is Lock or Unlock.
x The navigation tree should be in the “Unlock” state in when adding or removing active ADX components.
Figure 7-2 Navigation tree Lock/Unlock
When the system is locked:
Unable to detect any hardware that is added
Able to detect any link fails (communication errors between NMS and components)
System should be locked after final commissioning
When the system is unlocked:
Unable to perform BCU, RFU, or HRU commissioning
System is continually scanning for new hardware
7.1.4 Set Location Info, Installer Info and Date & Time
x Go to the Install page of NMS
x Enter Location & installer information
x Set current Date & Time
7.1.5 Verify Navigation Tree Links
x Check whether all units connected to HE & HRU are being displayed in the navigation tree.
- Navigation tree is located on the left side of Web-GUI (Figure 7-3 )
Figure 7-3 Navigation tree
x Check whether link fails exist. Link fails status can be seen on the front panel of NMS module via the Link Fail-
H and Link Fail-R LED lights.
- If LINK-H fail exists, power cycle the HE PSU and check if LINK-H fail is still present and repeat this
step up to 3 times or until the alarm clears. If LINK-H fail still exists after 3 power cycles, then
contact ADRF Technical support.
- If LINK-R fail exists, power cycle the ADX-H-ODU module which is connected to the Master HRU
with link fail and check to see if the LINK-R fail is still present and repeat this step up to 3 times or
until the alarm clears. If LINK-R fail still exists after 3 power cycles, contact ADRF Technical
support.