4.2 External Alarms
The PSR-78-8527 supports dry contact alarms and can be connected to a fire alarm control panel (FACP). The user can program
the repeater to either create an open or closed circuit when an alarm is present in the system. The repeater must be installed
within 30m (98.4ft) from the FACP.
4.2.1 External Alarm Output interface
Fire Alarm Control Panel
FACP
Digital Board
24V DC
ADRF PSR Repeater
ADRF
Digital Board
External Alarm Name
Set Condition
Likely Causes
Donor Antenna Malfunction
- UL Return Power Fail
- Damaged Donor Antenna
Active RF Device Malfunction
- RF Power Fail
- DL Return Power Fail
- DL/UL Over Power Fail
- DL/UL Input Fail
- Degrading Amplifier
- Open or Disconnected Server Port
- Oscillation
- Strong RF Input Signal
Low Battery Capacity (70% depleted)
- Low Battery Fail
- Battery Depleted
System Component Malfunction
- Over Current Fail
- Over Temperature Fail
- DSP Fail
- Out-band Overload Fail
- Faulty or Damaged PSU
- Ambient Temperature
- DSP Filter Fault
- Strong RF Input Signal
Normal AC Power
- AC Normal Set
- AC Fail Clear
- Powered by AC Power
- Powered by DC Power
Loss of Normal AC Power
- AC Fail Set
- AC Normal Clear
- Powered by DC Power
- Powered by AC Power
Battery Charger Failure
- Battery Fail
- Battery Not Connected fail
- Battery Not Charge Fail
- Low Battery Charging Voltage
- Battery Cable Disconnected
- Degraded Batteries
Summary Alarm
- Any Active Alarm
- Any Active Alarm Present in the System
Donor Antenna Disconnect
- No DL Signal Detected
- Disconnected Donor Line
Oscillation Alarm
- Oscillation
- Gain Set Too High or Lack of Isolation