5.3.4 Alarm Settings
Figure 5-11 Alarm Settings
DL Signal Low Level: Allows the user to specify how low the signal can be before triggering a “Downlink Signal
Low” soft-fail alarm
DL Signal Not Detected Level: Allows the user to specify how low the signal can be before triggering a “Downlink
Signal Not Detected” soft-fail alarm
DL RF Power Level: Allows the user to set a maximum deviation value for the downlink RF power before
triggering a “DL RF Power Level” soft-fail alarm
- For example, if the input signal is -50 dBm and the gain is set to 60 dB, the expected output power should
be 10 dBm. If the Downlink RF Power alarm value is set to 6dB, then a soft-fail alarm will trigger if the
output power falls below 4 dBm
DL Over Power Level: DL Over Power Alarm will trigger when the DL output level exceeds this level
UL Over Power Level: UL Over Power Alarm will trigger when the UL output level exceeds this level
Battery Check:
Check AllAll battery related alarms are checked which include Battery Fail, Battery Not Installed, Low
Battery, and Battery Not Charge
Except Install Only Battery Fail, Low Battery, and Battery Not Charge alarms are checked
Check Off Does not perform any battery check
Battery Not Charge Check:
On Checks for the Battery Not Charge alarm
Off Disables the check for the Battery Not Charge alarm