Analog Output 1 (2) Configure t he follo wing values for e ach
analog output device (maximum of two) connected to the XIO
device.
Entity Select the data entity whose value you want the XIO
device to outp ut as an anal og signal. While the list contains all
entities, choose only those entities which the monitor is
curr ently generating.
Min Value Enter the data value (for the selected entity) which
will correspond to the weakest analog output signal. The Min
Value will be used to translate a c tual d a ta into a nalog output
signals and should correspond to the lowest possible entity
value (weakest) in the scale (4mA).
Max Value Enter the data value (for the selected entity)
which will correspond to the strongest analog output
signal. The Max Value will be used to tra nslate actual data
values i nto anal og output signals and should correspond to the
highest possible entity value (strongest) in the scale (20mA).
Manual E nter the value to us e when manually te sting the
analog outp ut s ignal. This va lue will be used with the Enable
Manual checkbox for testing the analog output signal.
Important: Changes to the Manual or Enable Manual
parameter requires monitor activation in o r der to take
effect.
Enable Manual Sel ect this checkbox when you want to
manually test the analog output signal to output the value
desi gnated i n t he Manual field.
Digital Input 1 (2) Configur e the following values fo r each
digital input device (maximum of two) connected to the XIO
device.
Entity Select DI1 (DI2) from the drop-down list to enable the
associated digital input device connected to the XIO device.