User Manual

Modbus 9-9
Note: Refer to the manufacturer’s documentation for the
device to which you a re connecting the ExPAC to
determine the appr opriate pin-out for the RS -232 input
connector on the device end of the cable (similar to the
table above).
Note: If the DTR input is not available/supported on the
device, connect the RTS output to pin 7 and pin 4 as well
to ensure the ExP AC D TR input is activated and
communications are enabled. The TRITON+ monitor
connected to the ExPAC will not operate if the DTR or the
DCD lines are no t a c tivated.
Setting Up a Wire less Connect ion
Establishing a wireless Mo dbus connection enables the TRITON+
to provide the updated Modbus registers to the SC ADA or process
control system.
Consider the following when using a wireless co nnectio n:
While not required , ADS stro ngly recommends p owering the
TRITON+ for any continuous Modbus communications
thro ugh an exter nal source using an ExPAC or XBUS.
Establishing wireles s TCP/IP communication may take several
minute s. Therefore, consider this initial delay in
communication when setting up the host pro gram.
Verify that the monitor has been configured for Modbus output
through Qstart with a wireless co nnection type and the proper
IP address for the monitor.
Verify that the process control system ha s the proper Modbus
slave ID, is configured for wireless TCP communication, and
has the correct IP address for the TRITON+.
Once b o th systems are configured and activated, verify that the
process control system is receiving the appropriate Modbus
register values.