User Manual
Modbus 9-9
Note: Refer to the manufacturer’s documentation for the
device to which you a re connecting the ExPAC to
determine the appr opriate pin-out for the RS -232 input
connector on the device end of the cable (similar to the
table above).
Note: If the DTR input is not available/supported on the
device, connect the RTS output to pin 7 and pin 4 as well
to ensure the ExP AC D TR input is activated and
communications are enabled. The TRITON+ monitor
connected to the ExPAC will not operate if the DTR or the
DCD lines are no t a c tivated.
Setting Up a Wire less Connect ion
Establishing a wireless Mo dbus connection enables the TRITON+
to provide the updated Modbus registers to the SC ADA or process
control system.
Consider the following when using a wireless co nnectio n:
• While not required , ADS stro ngly recommends p owering the
TRITON+ for any continuous Modbus communications
thro ugh an exter nal source using an ExPAC or XBUS.
• Establishing wireles s TCP/IP communication may take several
minute s. Therefore, consider this initial delay in
communication when setting up the host pro gram.
• Verify that the monitor has been configured for Modbus output
through Qstart with a wireless co nnection type and the proper
IP address for the monitor.
• Verify that the process control system ha s the proper Modbus
slave ID, is configured for wireless TCP communication, and
has the correct IP address for the TRITON+.
• Once b o th systems are configured and activated, verify that the
process control system is receiving the appropriate Modbus
register values.