Bill of Materials Re: 2250KW Item Install-US-Stat 2250DQKH A331-2 L090-2 L097-2 R002-2 B453-2 H611-2 H605-2 H606-2 H608-2 KP80-2 H666-2 C127-2 A334-2 A333-2 E041-2 H556-2 D041-2 H607-2 L028-2 0416-0527 BA BC VI CM EF EN FT Description Diesel Genset: 60Hz-2250kW Installation-In USA, Stationary Genset-Diesel, 60Hz, 2250kW-Standby Rating Duty Rating-Standby Power Listing-UL 2200 Emissions-EPA, Tier1, NR Levels CI Voltage-277/480,3 Phase,Wye,4 Wire Alt-60Hz,Y480V,150-105C-SPC,40C amb Set Control-PCC Display-C
Diesel generator set QSK60 series engine EPA emissions 1450 kW - 2250 kW 60 Hz 1200 kW - 2000 kW 50 Hz Description Features Cummins Power Generation commercial generator sets are fully integrated power generation systems providing optimum performance, reliability and versatility for stationary, prime power and continuous duty power applications. Cummins heavy-duty engine - Rugged 4-cycle, industrial diesel delivers reliable power, low emissions and fast response to load changes.
Generator set specifications Governor regulation class Voltage regulation, no load to full load Random voltage variation Frequency regulation Random frequency variation Radio frequency emissions compliance ISO8528 Part 1 Class G3 ± 0.5% ± 0.5% Isochronous ± 0.25% IEC 801.2 through IEC 801.5; MIL STD 461C, Part 9 Engine specifications Design Bore Stroke Displacement Cylinder block 4 cycle, V-block, turbocharged and low temperature aftercooled 158.8 mm (6.25 in) 190.0 mm (7.48 in) 3 60.
Control system Operator panel features Standard control functions Analog AC metering panel - Provides color-coded display of generator set output voltage, current, frequency, power factor and kW. All phases of voltage and current are simultaneously displayed. Easy to see output status from a distance. • Integrated Isochronous governing and fuel control system. • Integrated 3-phase sensing voltage regulation system with automatic single and three phase fault regulation.
Ratings definitions Emergency standby power (ESP): Applicable for supplying power to varying electrical load for the duration of power interruption of a reliable utility source. Emergency Standby Power (ESP) is in accordance with ISO 8528. Fuel Stop power in accordance with ISO 3046, AS 2789, DIN 6271 and BS 5514. Limited-time running power (LTP): Applicable for supplying power to a constant electrical load for limited hours. Limited Time Running Power (LTP) is in accordance with ISO 8528.
Model: DQKH Frequency: 60 Fuel type: Diesel h Generator set data sheet 2250 kW standby Exhaust emission data sheet: Emission compliance sheet: Sound performance data sheet: Cooling performance data sheet: Prototype test summary data sheet: Standard set-mounted radiator cooling outline: Optional set-mounted radiator cooling outline: Optional heat exchanger cooling outline: Optional remote radiator cooling outline: Fuel consumption Ratings Load US gph L/hr EDS-1014 EPA-1067 MSP-1001 MCP-126 PTS-155 0500-3
Air 3 Combustion air, m /min (scfm) Maximum air cleaner restriction, kPa (in H2O) 3 Alternator cooling air, m /min (cfm) Standby rating 183 (6455) 6.2 (25) 161 (5700) Prime rating Exhaust Exhaust gas flow at set rated load, m3/min (cfm) Exhaust gas temperature, °C (°F) Maximum exhaust back pressure, kPa (in H2O) 445 (15705) 479 (895) 6.
Optional remote radiator cooling1 Set coolant capacity, L (US gal) Max flow rate @ max friction head, jacket water circuit, L/min (US gal/min) Max flow rate @ max friction head, aftercooler circuit, L/min (US gal/min) Heat rejected, jacket water circuit, MJ/min (Btu/min) Heat rejected, aftercooler circuit, MJ/min (Btu/min) Heat rejected, fuel circuit, MJ/min (Btu/min) Total heat radiated to room, MJ/min (Btu/min) Maximum friction head, jacket water circuit, kPa (psi) Maximum friction head, aftercooler circu
Alternator data Voltage 380 380 440 440 480 480 480 480 600 600 600 600 4160 4160 4160 4160 12470 12470 13200-13800 13200-13800 13800 1 Connection Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Wye, 3-phase Temp rise degrees C 125 105 150 105 150 125 105 80 150 125 105 80 150 125 105 80 125 105
ALTERNATOR DATA SHEET Frame Size P734G CHARACTERISTICS Stator Assembly: Rotor Assembly: Complete Assembly: WEIGHTS: MAXIMUM SPEED: EXCITATION CURRENT: INSULATION SYSTEM: 3 ∅ RATINGS 3503 lb 2705 lb 9259 lb 2250 3.24 0.54 Full Load No Load 1589 kg 1227 kg 4200 kg rpm Amps Amps Class H Throughout 60 Hz Voltage (0.
Exhaust Emission Data Sheet 2250DQKH 60 Hz Diesel Generator Set Engine Information: Model: Cummins Inc. QSK60-G9 Nonroad 1 Bore: Type: 4 Cycle, 60°V, 16 Cylinder Diesel Stroke: Aspiration: Turbocharged and Low Temperature Aftercooled Displacement: Compression Ratio: 14.5:1 Emission Control Device: Turbocharged and Low Temperature Aftercooled 1/4 Standby PERFORMANCE DATA BHP @ 1800 RPM (60 Hz) Fuel Consumption (gal/Hr) Exhaust Gas Flow (CFM) Exhaust Gas Temperature (°F) 1/2 Standby 3/4 Standby 813 45.
EPA Stationary New Source Exhaust Emission Compliance Statement 2250DQKH 60 Hz Diesel Generator Set Compliance Information: The engine used in this generator set complies with U.S. EPA regulations under the provisions of 40 CFR 60, Stationary New Source emissions limits when tested per ISO 8178 D2. Engine Manufacturer: EPA Certificate Number: Effective Date: Date Issued: EPA Nonroad Diesel Engine Family: Cummins Inc. CEX-STATCI-07-46 05/04/07 05/07/07 7CEXL060.AAE Engine Information: Model: Cummins Inc.
Exported on: Jun 25 2007 and is an Un-Controlled Document
Exported on: Jun 25 2007 and is an Un-Controlled Document
Exported on: Jun 25 2007 and is an Un-Controlled Document
Exported on: Jun 25 2007 and is an Un-Controlled Document
Exported on: Jun 25 2007 and is an Un-Controlled Document
10" X 10" X 18" Long (2)
QTY - 2 ® Critical “300” Level Exhaust Silencers “F” Mounting Flange: Standard in sizes 4" to 22". Drilling matches 125/150# ASA standard. Typical Attenuation Curve dB(A)* (ACTUAL ATTENUATION MAY VARY ACCORDING TO APPLICATION) 35 “P” Male Pipe Threads: NPT ends offered in sizes 3/4" through 4". 30 25 Companion flanges available for 4" to 22". 20 Construction Features: Double wrapped body is standard on all "300" Level Critical Silencers. 15 10 5 Pressure Drop 31.
Type 1 Type 3 D C G D C H B A E F A F B E A G A Part Number 41307* 41310* 41313* 41315* 41320* 41325* 41330* 41335* 41340* 41350* 41360* 41380* 41382* 41384* 41386* 41388* 41399* 41321* 41322* A Nominal Inlet Diameter .75 1.00 1.25 1.50 2.00 2.50 3.00 3.50 4.00 5.00 6.00 8.00 10.00 12.00 14.00 16.00 18.00 20.00 22.00 C B Body Dia. Body O.D. Length 4.2 21.3 5.0 23.4 6.1 27.5 8.1 30.7 9.0 40.8 10.1 47.2 11.1 49.5 12.1 51.3 12.1 58.3 14.1 63.5 16.1 72.0 22.1 78.7 26.2 79.7 30.2 104.8 42.2 108.
. Batteries and Accessories Part Number 0416-0439 0416-0579 0416-0579-01 0416-0774 0416-0796 0416-0823 0416-0848 0416-0965 0416-0980 0416-1040 0416-1051 0416-1264 0416-1330 Battery Dry Dry Wet Dry Wet Wet Dry Wet Wet Dry Wet Dry Dry Cold Cranking Amps 1400 420 500 390 725 725 1080 800 1000 800 530 730 810 Voltage 12 12 12 12 12 12 12 12 12 12 12 12 12 Qty - 4 Reserve Capacity Length 370 20.75 60 10.25 75 10.25 90 13.00 150 13.00 150 13.45 270 20.80 120 10.26 200 13.00 NA 13.00 80 8.20 420 20.
SMART benefits: EnerGenius solves the No. 1 problem with generator sets - failure to start. Simple. Intuitive adjustments allow quick field reconfiguration for any battery. Modern. Ingenious BatterySENS feature provides advance warning of battery system problems. Accurate. EnerGenius offers the most precise, fully automatic charging of lead and nickel-cadmium batteries.
EnerGenius Specifications Figure 1 Electrical Performance Input Selection: Dual input range switch select Nominal: 120/208-240 VAC Full output: 60 Hz: 50/60 Hz: 94-132 VAC, 57-63 Hz 187-264 VAC 94-132 VAC, 47-63 HZ 187-264 VAC Extended low line: 85/170 VAC Output Nominal voltage: 12-volt 24-volt 12/24-volt field programmable (optional) Battery compatibility: 6 or 12-cell lead-acid; flooded or VRLA. 9, 10, 18, 19, 20-cell nickel cadmium. Voltage adjustment: 6 discrete programs.
Environmental Easy field set up Operating temperature: -20C to +60C. Full output available to +40C. Overtemperature protection provided. Humidity: 5% to 95%, non-condensing. Circuit card is conformally coated. Altitude: 0-2000 meters with no derating. Automatic derating above 2000 meters. Vibration: 2G sinusoidal from 10 Hz to 150 Hz per UL 991. Controls & Adjustments Battery setting: 6 discrete programs for flooded, VRLA and Ni-Cd batteries.
EnerGenius Battery-Interactive Closed-Loop Feedback EnerGenius examines the battery to provide the correct charge at all times, and issues appropriate alarms. Parameters monitored include: -Actual battery voltage -Charger volt set point -Battery current demand -Temperature -Battery polarity -Battery connected -Loose connections -Open battery cell(s) EnerGenius Ordering Information Table Output Volts Amps Input VAC NFPA-110 Alarms Hz Model Number Net Weight LBS.
Exported on: Jun 25 2007 and is an Un-Controlled Document
Exported on: Jun 25 2007 and is an Un-Controlled Document
QTY-10 SERIES C Vibro Isolators Series C Vibro Isolators are rugged cast iron housed isolators with oil tempered steel springs for all purpose applications. Isolators are available with external (CK) or internal (CI) adjustment and also feature adjustable or non-adjustable resilient snubbers for varying degrees of damping and to limit oscillation. All isolators are provided with a bottom sound pad for maximum noise reduction.