Safewatch Pro ® 3000EN Entrepreneur 3000EN Security Manager 3000EN Security Systems Installation and Set-Up Guide ARMED READY 3 OFF 2 4 5 TEST 6 BYPASS 7 INSTANT 8 CODE 9 READY 0 1 AWAY STAY CHIME # ARMED READY 3 OFF 2 4 5 TEST 6 BYPASS 7 INSTANT 8 CODE 9 READY 0 1 AWAY STAY CHIME # Meets ADT Security Services Triple Standards Requirements: C LISTED US Standards for Security and Fire Standard for False Alarm Reduction 7 167-0495:110 California State Fire Marsha
RECOMMENDATIONS FOR PROPER PROTECTION The Following Recommendations for the Location of Fire and Burglary Detection Devices Help Provide Proper Coverage for the Protected Premises. Recommendations For Smoke And Heat Detectors With regard to the number and placement of smoke/heat detectors, we subscribe to the recommendations contained in the National Fire Protection Association's (NFPA) Standard #72 noted below.
Table Of Contents • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Features and Installation Highlights ...................................................................................................................1-1 Capabilities .............................................................................................................................................................................................. 1-1 Functions ..............................................
Table Of Contents (continued) Function Key Programming .................................................................................................................................8-1 About Function Key Programming ........................................................................................................................................................... 8-1 Programming Function Keys............................................................................................................
S E C T I O N 1 Features and Installation Highlights • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This ADT system is a SIA-compliant control (in accordance with ANSI/SIA standard CP-01-2000 control unit standard-features for false alarm reduction). This system is a 2-partition control with the following major features: Capabilities • 2 partitions; can protect two independent areas, as if each area had its own separate control.
3000EN Series: Installation and Setup Guide Compatible Devices • Supports up to 8 Addressable Touchpads: English Display Touchpad (6150ADT), Custom English Display Touchpad (6160ADT), and Custom English Display Voice Touchpad (6160VADT) • Supports up to four iCenter (AUI) or 6270ADT touch screen devices in addition to up to 8 touchpads (described above).
S E C T I O N 2 Mounting and Wiring the Control • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • This section describes the procedures for mounting and wiring this control and its peripheral devices. In the following subsections, procedures are listed in the left column, while notes and pertinent explanations are provided in the right column. Cabinet and Lock 1.
3000EN Series: Installation Instructions Mounting Board with RF Receiver 1. a. Remove the receiver board from its case, then insert the top of the board into the slots at the top of the cabinet, as shown in Detail A in Figure 3. Make sure that the board rests on the correct row of tabs. b. Swing the base of the board into the mounting clips and secure it to the cabinet with the accompanying screws. c.
Mounting and Wiring the Control Wiring to Touchpads 1. Connect touchpads to the control’s touchpad terminals as shown on the Summary of Connections diagram. Determine wire size using the Wire Run Chart on the next page. 2. Set Touchpad Addresses (first touchpad is address 16). Refer to the address setting instructions included with the touchpads and set each touchpad device address according to the Touchpad Addresses chart below. 3.
3000EN Series: Installation Instructions UL Use a UL Listed, battery-backed supply for UL installations. The battery supplies power to these touchpads in case of AC power loss. The battery-backed power supply should have enough power to supply the touchpads with the UL required minimum standby power time. Touchpads powered from supplies that do not have a backup battery will not function if AC power is lost.
Mounting and Wiring the Control Wiring the AC Transformer 1321 Transformer Connect the 1321 Transformer to terminals 1 and 2 on the control board. See Wire Run Chart below for wire size to use. Use 1321CN in Canada. 1361X10 Transformer (required if using Powerline Carrier devices) 1. Splice one end of a 3-conductor cable to the wire ends of the SA4120XM-1 Cable. 2.
3000EN Series: Installation Instructions Backup Battery 1. Place the 12-volt backup battery in the cabinet. 2. After all connections to the control are completed, connect the red and black flying leads on the control board to the battery. Do not attach these leads to the battery terminals until all connections are completed. Battery Saver Feature: The battery will disconnect from the system after its voltage decreases below 9VDC. This assists the control panel in recharging the battery when AC is restored.
Mounting and Wiring the Control AUXILIARY DEVICE CURRENT DRAW WORKSHEET DEVICE 6150ADT Touchpad 6160VADT Voice Touchpad 6270ADT Touch Screen 8132ADT iCenter 5881/5882 RF Receiver CURRENT # UNITS 40mA (70mA alarm) 60mA (190mA alarm) 180mA/220mA†† (280mA alarm) 150mA/350mA†† (200mA/400mA†† alarm) 60mA 5883 Transceiver 80mA 4219 Zone Expander 30mA 4204 Relay Unit 15/180mA‡ 4229 Zone Expander/Relay Unit 4286 Phone Module 30/100mA‡ TOTAL CURRENT * If using hardwire devices such as PIRs, refer to th
3000EN Series: Installation Instructions Hardwire Zones Normally Open Zones/ Normally Open EOLR Zones 1. Connect open circuit devices in parallel across the loop; for EOLR zones, connect the EOLR across the loop wires at the last device. 2. Enable normally open/EOLR zones using Zone Programming mode, “Hardwire Type” prompt. Normally Closed Zones/Normally Closed EOLR Zones 1.
Mounting and Wiring the Control + 5 _ PROGRAM RELAY AS ZONE TYPE 54 (FIRE ZONE RESET) 4 RELAY AUX PWR OUTPUT TERMINALS BLK _ RED + EOL POWER SUPERVISION RELAY MODULE A77-716B. USE N.O. CONTACT, WHICH CLOSES WHEN POWER IS APPLIED. N.O. N.C. CONTACT OPENS MOMENTARILY UPON FIRE ALARM RESET + _ VIOLET 2000 OHMS EOLR 4_wiresmk-007-V0 4-WIRE SMOKE OR COMBUSTION DETECTOR TO ZONE TERM. (+) TO ZONE TERM. (_) HEAT DETECTOR Figure 7a.
3000EN Series: Installation Instructions 4219/4229 Expansion Zones 1. Connect each module to the control’s touchpad terminals. 2. Assign each module a unique device address (07-11) using its DIP switches. Device addresses are based on the zone numbers being used, as shown below. Expander Module Addresses For Zones… Set Module to Device Address… (see DIP chart) 09-16 07 17-24 08 25-32 09 33-40 10 41-48 11 3. Connect sensors to the module’s loops. 4.
Mounting and Wiring the Control Installing the RF Receiver Use any 5800 Series Wireless Receivers, such as: RF Receiver No. of Zones 5881L/5882L up to 8 5881M/5882M up to 16 5881H/5882H up to 40 plus 16 button zones 5883, 6150RFADT Zone Nos.: transmitters = 9-48; buttons = 49-64 1. Set Device Address to “00” as described in its instructions (set all switches to the right, “off” position). 2.
3000EN Series: Installation Instructions Installing a 5800TM Module 1. Mount the 5800TM next to the RF receiver (between one and two feet from the receiver’s antennas) using its accompanying mounting bracket. Do not install within the control cabinet. 2. Connect the 5800TM to the control panel’s touchpad connection terminals as shown on the Summary of Connections diagram and set to address 28. 3. For additional information, refer to the 5800TM’s instructions.
Mounting and Wiring the Control Installing a Keyswitch 1. Connect the 4146 keyswitch's normally open momentary switch to a zone’s (2-8) terminals. Remove the 2000 ohm EOL resistor if connected across the selected zone. 2. Using a standard touchpad cable as shown: Connect the yellow and white keyswitch wires to trigger connector pin 3 (+12V). Connect the Red and Green LED wires to the appropriate output 17/output 18 trigger connector pins. 3. Connect a 2000 ohm EOL resistor across the momentary switch. 4.
3000EN Series: Installation Instructions Connecting Relay Modules 1. Mount either remotely or in the control panel. Use 4204 or 4229 modules. 2. Connect to control’s touchpad terminals using the connector harness supplied with the module. Use standard 4-conductor twisted cable for long wiring runs. 3. Set each module’s device address according to the following table (and see DIP Switch chart). Relay Module Addresses 4204 Address 4229 Address no. 1 12 no. 1 (zn 09-16) 07 no. 2 13 no. 2 (zn 17-24) 08 no.
Mounting and Wiring the Control Powerline Carrier Devices 1. Install the powerline carrier devices according to the instructions included with each. 2. Use Programming Mode to enter the device house ID in data field*27, and enter the unit code using *79 Output Device menu Mode. See connections diagram in the AC Wiring paragraph for connecting the 1361X10 transformer.
3000EN Series: Installation Instructions On-Board Triggers Connect field wiring to the desired trigger pin on the 8-pin trigger connector centrally located above the terminal strip. • If using 1361X10 transformer and powerline carrier devices, use the SA4120XM-1 cable (part of 4120TR Trigger Cable). See Wiring the AC Transformer section for transformer-to-trigger connections. • If only using the on-board triggers, you can use a 4-wire cable (N4632-4, supplied with the control) as shown below.
Mounting and Wiring the Control Phone Line/Phone Module Connections 1. Connect incoming phone line and handset wiring to the main terminal block (via an RJ31X jack) as shown in the Summary of Connections diagram at the back of this manual. Wire colors represent the colors of the cable to the RJ31X jack. If using a phone module, continue with the following steps. 2.
3000EN Series: Installation Instructions INCOMING HANDSET TELCO LINE GROUND { { IMPORTANT NOTE FOR EXISTING INSTALLATIONS: EXISTING WIRES CONNECTED TO THE "HANDSET" TERMINALS ON CONTROL MUST BE MOVED FROM THERE TO TERMINALS 3 AND 4 ON THE 4285/4286. LOUDER 24 TO EARTH GROUND (COLD WATER PIPE, ETC.
Mounting and Wiring the Control Audio Alarm Verification Connections (AAV, “Listen-In”) Using the UVS System with UVCM Module Refer to the connection diagrams below. One diagram shows connections when a 4286 Phone Module is used, the other shows connections when the 4286 is not used. Connections use one of the on-board triggers. UL UL installations using the AAV feature must use the ADEMCO UVCM module (part of the ADEMCO UVS system).
3000EN Series: Installation Instructions OUTPUT 18 5 CONTROL AUXILIARY AUDIO LEVEL ADJUSTMENT TRIM POT +12VDC GND 21 5 22 24 25 RING TIP RED (R) GREEN (T) GREY (R) OPTIONAL MONITORING ZONE CONNECTION (USE ZONE TYPE 81) RJ31X 9 BROWN (T) INCOMING PHONE LINE 4286 2 3 +12VDC IN 2 Figure 16.
Mounting and Wiring the Control Using the AVS System with AVS-ADT Module and AVST-ADT Remote Stations The AVS system provides audio alarm verification via the phone line or via AlarmNet if the GSMV-ADT module is used as the communication device. Refer to the instructions included with the AVS-ADT system for installation procedures. The following is a summary.
3000EN Series: Installation Instructions 3 6 4 5 TIP RING 2 7 RJ31X TIP INCOMING TELCO 8 1 RING PREMISES PHONES DIRECT CONNECT CORD 4 5 6 7 INCOMING PHONE LINE (TIP) DATA DATA OUT GND AUX IN (RING) HANDSET ECP TERMINALS BRN GRY 8 (RING) 3 (TIP) 2 (EARTH GND TRIGGER HEADER 1 RED GRN CONTROL PANEL TOUCHPAD VOLUME / ID BUTTON YEL GRN BLK SPEAKERS LED RED AVST-ADT STATION IMPORTANT: DO NOT CONNECT ANY OTHER ECP DEVICES TO PANEL.
S E C T I O N 3 Programming Overview • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Programming • You can program the system at any time, even at the installer's premises prior to installation. • Programming can also be performed remotely from the installer’s office/home, using an IBM personal computer, a modem, and Compass downloading software. • The Real-Time Clock must be set before completing the installation.
00EN Series: Installation Instructions Touchpads Touchpads are identified by predefined addresses as follows: Address 16 17 18 19 20 21 22 23 Touchpad touchpad 1 touchpad 2 touchpad 3 touchpad 4 touchpad 5 touchpad 6 touchpad 7 touchpad 8 Program Field • always enabled for partition 1, all sounds enabled. • data field *190 • data field *191 • data field *192 • data field *193 • data field *194 • data field *195 • data field *196 NOTE: First touchpad is address 16. To enable touchpads: 1.
Function Keys To assign functions to the function keys, use *57 Function Key menu mode. To assign emergency key functions (function key option “00”), first program the respective emergency zone number (95 for “A” key, 96 for “C” key, 99 for “B” key) with the desired zone type using *56 Zone Programming mode, then use *57 Function Key menu mode to assign the desired key.
3000EN Series: Installation Instructions Type 06 24-hour Silent Alarm Type 07 24-hour Audible Alarm Type 08 24-hour Auxiliary Alarm Type 09 Supervised Fire Type 10 Interior w/Delay Type 12 Monitor Zone Type 14 24 Hour Carbon Monoxide Monitor Type 16 Fire w/Verification Type 20 Arm-Stay (BR only) Type 21 Arm-Away (BR only) Type 22 Disarm (BR only) Type 23 * No Alarm Response Type 24 Silent Burglary 3-4 • Usually assigned to a zone containing an emergency button.
Type 25 * 24-Hour Non-Alarm Monitor Type 77 Keyswitch Type 81 AAV Monitor Zone Types 90-93 Configurable • For use with sensors designed to provide a trouble display (but no trouble sounding) when an oil tank is low, or other similar application for critical condition monitoring where a non-alarm response is required. • When this zone type is faulted and remains faulted for the programmed time duration (field *53), a special event message is sent to the central monitoring station.
3000EN Series: Installation Instructions AVS QUICK PROGRAMMING COMMANDS (for AAV sessions using the AVS-ADT system) For controls with the firmware revision level 7.0 or higher, these commands automatically configure the control for AVS operation.
S E C T I O N 4 Data Field Programming • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Data Field Programming The following pages list this control’s data fields in numerical order. Field numbers are listed in the left column followed by a “Title and Data Entries” column, which lists the valid entries for each field. Experienced installers can simply follow this column when programming the data fields.
3000EN Series: Installation Instructions FIELD TITLE and DATA ENTRIES EXPLANATION *27 Powerline Carrier Device (X-10) House ID Powerline Carrier devices require a House ID, identified in this field. Program Powerline Carrier devices in interactive modes ∗79, *80 and *81. Not intended for fire or UL installations.
*36 Entry Delay 2 *38 Confirmation Of Arming Ding *39 Power-Up In Previous State See *35 above for explanation. See *35 above for entries. 0 = no ding 1 = confirmation ding after arming system 2 = confirmation ding after arming from RF button or RF touchpad only (except 5827, 5827BD) Feature always enabled; field removed in this control. Confirmation of arming is 1/2 second external sounder “ding.
3000EN Series: Installation Instructions *48 Report Format - Field Deleted *49 Split/Dual Reporting 0 = standard/backup reporting only (all reports only to primary unless unsuccessful, then will attempt secondary) 1 - 5 = see table to right 1= 2= 3= 4= 5= *50 Burglary Dialer Delay Provides delay of “BURGLARY ALARM” report to the central station, which allows time for the subscriber to avoid a false alarm transmission.
*55 Dynamic Signaling Priority 0 = Primary dialer first / AAV via phone line 1 = Communication Device (LRR) first / AAV via communication device path (see AAV Path Select paragraph at right) UL Installations: For UL Commercial Burglary installations that use a DACT and LRR, the DACT must be programmed for priority (option “0”).
3000EN Series: Installation Instructions FIELD *59 TITLE and DATA ENTRIES Exit Error Alarm Report Code SIA NOTE: exit error report is always enabled The Contact ID message will contain the zone number and error code 374 (“ALARM–EXIT ERROR”). 4-6 EXPLANATION After arming the system, entry/exit and interior zones remaining open after exit delay expires cause an alarm sound at the touchpad and external sounder (touchpad also displays “EXIT ALARM”), and entry delay begins.
*69 Recent Closing Report Code SIA NOTE: Recent closing report is always enabled. The Contact ID message will contain the zone number and error code 459 (“RECENT CLOSING”). Similar to the Exit Error condition described in field *59, but occurs if any burglary zone is faulted within two minutes after the initial exit delay expires. Disarming the system within the two minutes stops the alarm sound and displays " ALARM CANCELED " or "CA" and the faulted zone number.
3000EN Series: Installation Instructions FIELD 4-8 EXPLANATION *80 TITLE and DATA ENTRIES Output Programming Menu Mode *81 Zone List Menu Mode Use the menu mode to define zone lists. See Zone List Programming section. *82 Use this menu mode to assign alpha descriptors to zones and/or create partition descriptors.
*91 Option Selection / Call Waiting Disable & ADT Pulse Enable Entry 1: Options 0 = none 1 = Bell Supervision Processing† 4 = using Audio Alarm Verification (AAV) unit 8 = Enable Exit delay restart/reset †† UL 1. UL installations using the AAV feature must use the ADEMCO UVCM module (part of ADEMCO UVS system). 2. Bell supervision is required for fire alarm installations. 3. Exit delay restart/reset must be disabled. FOR SIA INSTALLATIONS: Exit delay should be enabled.
3000EN Series: Installation Instructions *93 No. of Reports In Armed Period per Zone (Swinger Suppression) Entry 1: No. of Report Pairs 1 = 1 report pair per zone per armed period 2 = 2 report pairs per zone per armed period Entry 2 (SIA Installations): Unlimited Reports Enable 0 = restrict reports to the setting in entry 1 1 = unlimited reports for zones listed in zone list 7 *94 *95 Download Phone Number Enter up to 20 digits as follows: 0–9, # +11 for “∗”, # + 12 for “#”, # + 13 for a pause.
Pager Programming Fields FIELD TITLE and DATA ENTRIES EXPLANATION *160 Pager 1 Phone No. If you enter fewer than 20 digits, exit by pressing [∗] and next field number. To clear entries from this field, press ∗160∗. *161 Pager 1 Characters FIELD TITLE and DATA ENTRIES EXPLANATION *162 Pager 1 Report Options Enter the types of reports to be sent to Pager 1 for each partition.
3000EN Series: Installation Instructions *166 Pager 3 Phone No. *167 Pager 3 Characters *168 Pager 3 Report Options *169 Pager 4 Phone No. *170 Pager 4 Characters *171 Pager 4 Report Options *172 Pager Delay Option for Alarms Enter up to 20 digits Enter up to 16 characters see pager 1 reports, field *162 for entries, except use zone list 11. Enter up to 20 digits Enter up to 16 characters see pager 1 reports, field *162 for entries, except use zone list 12.
Configurable Zone Type Programming Fields The system allows you to define up to four custom zone types (zone types 90-93), based on the options described below, which can be assigned to zones that require customized responses. All of these zone types can be programmed via the downloader. Configurable zone types 90 and 91 can also be programmed from a touchpad using data fields *182-*185 described below. IMPORTANT: Be careful when selecting combinations of options for configurable zone types.
3000EN Series: Installation Instructions Configurable Zone Type Options Auto Restore Vent Zone Bypass when Disarmed Bypass when Armed Dial Delay Fault Delay Faults Display Power Reset/Verification Use Entry Delay 1/2 Use Exit Delay Interior Type Alarm Sounds Bell Timeout Fire Zone Trouble Sounds Chime Enable 4-14 Faults on zones set for this option are cleared and restore messages sent upon restoral of faults.
Configurable Zone Type Charts ENTRY 1 ENTRY 2 Response when system disarmed and zone is: Intact EOL Open Shorted RF zone normal RF zone N/A 0 = normal 1 = alarm 2 = trouble 3 = fault Auto Restore Vent Zone RF zn off-normal 0 = normal 1 = alarm 2 = trouble 3 = fault 0 = no 4 = yes 0 = no 8 = yes 0 = normal 4 = alarm 8 = trouble 12 = fault see note 5 Entry 1 = EOL + Open Entry 2 = Short + auto restore + vent zone ENTRY 3 ENTRY 4 Response when armed STAY and zone is: Intact EOL Open Shorted RF z
3000EN Series: Installation Instructions Touchpad Programming Fields NOTE: Each touchpad must be assigned a unique address. Touchpads programmed with the same address will give unpredictable results. FIELD TITLE and DATA ENTRIES EXPLANATION Touchpad 2 *190 Touchpad 2 Device Address 17 Entry 1 – Partition Assignment: 0 = touchpad disabled Standard Touchpads 1 = partition 1 2 = partition 2 3 = partition 3 (common) Entry 1: Enter the partition in which the touchpad is located.
S E C T I O N 5 Zone Programming (∗56 and ∗58 Menu Modes) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Programming ∗56 Zone Programming is used to program zones, zone types, report codes, enroll 5800 RF Wireless Transmitter serial numbers, and identify the type of loop input device(s).
3000EN Series: Installation Instructions PROMPT Zn ZT P RC In: L 10 00 1 10 RF: 1 VALID ENTRIES EXPLANATION Summary Screen A summary display appears. “IN: L” appears for wireless zones and indicates input type and loop. “IN: AD” appears for hardwire expansion zones (AW) and indicates the module’s address (AD), which is based on the zone number. “HW: RT” appears for hardwire zones and indicates configuration (EOL, NO, NC ) and response time selection.
PROMPT 10 INPUT TYPE RF TRANS 3 VALID ENTRIES EXPLANATION Input Device type (In) All of the RF transmitters have one or more unique factoryassigned input (loop) ID codes. Each of the inputs requires its own programming zone (e.g., a 5804's four inputs require four programming zones). RF Transmitters can be enrolled as one of the following types: Type Description “RF” Sends periodic check-in signals, as well (Supervised RF) as fault, restore, and low-battery signals.
3000EN Series: Installation Instructions Entd A022-4063 1 Rcvd A022-4064 1 If Serial or Loop Numbers do not match after activating the transmitter [∗] to continue 10 INPUT S/N: A000-0000 L 0 Zn ZT RC In: L 10 03 10 RF: 1s PROGRAM ALPHA? 0 = NO 1 = YES 0 E N TE R Z N N U M. ( 0 0 = Q U I T) 1 1 5-4 To Delete a Serial No.
Completing Zone Programming When you have finished programming all zones, test each zone using the system’s TEST mode. Do not use the Transmitter ID Sniffer Mode for checking wireless transmitting devices, as it will only check for transmission of one zone on a particular transmitter, NOT the zones assigned to each additional loop.
3000EN Series: Installation Instructions PROMPT 10 INPUT S/N: A XXX- XXX L – VALID ENTRIES EXPLANATION Serial number Manually enter the serial number (found on the transmitter label), by typing digits in the “X” locations, using the [A] (advance) or [B] (back) keys as required. You can also perform two open and close sequences; for button-type transmitters that means pressing and releasing the button twice. NOTE: If you want to copy the previous zone’s serial number, press the [C] key.
Wireless Key Programming Templates This procedure programs the wireless keys, but a key is not active for arming/disarming until it is assigned to a user number (see Section 12 System Operation, assigning attributes command page 12-2). If the D key was previously pressed (from *58 Menu mode) to program 5804 and/or 5804BD wireless keys, the following screens appear. PROMPT TEMPLATE ? 1–6 L T 01 23 02 22 1 03 04 21 23 VALID ENTRIES EXPLANATION Template Number 1.
3000EN Series: Installation Instructions Confirm XMIT TO CONFIRM PRESS ✱ TO SKIP 13. If “Yes” was entered at the SET TO CONFIRM? prompt previously (see first prompt following entry into the ∗58 Expert Programming Mode), the display on the left will appear. Confirm serial and loop numbers by activating the wireless key. [∗] to continue IMPORTANT: When confirmed, the key is not active for arming/disarming until it is assigned to a user number (using the assigning attributes command, attribute “4”).
S E C T I O N 6 Output Device Programming (*79/*80 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Output Device Programming Output Devices: The system supports up to 16 relays and/or Powerline Carrier devices (X-10 devices) plus 2 built-in trigger outputs in any combination. These 18 “outputs” are assigned to system-wide output numbers (01-18). Use *79 Menu Mode to assign output numbers and map them to device addresses.
3000EN Series: Installation Instructions Start Output Device Mapping by pressing *79 while in Data Programming Mode. The following prompts are displayed: ∗79 Menu Mode PROMPT ENTER OUTPUT NO. 00 = QUIT xx 17 OUT NORM LOW 0 = NO 1 = YES 0 XX OUTPUT TYPE DELETE 0 VALID ENTRIES EXPLANATION Device Output Number This is the logical (or reference) relay number as used in the system.
*80 Menu Mode: Defining Output Functions Use this mode to program up to 48 output definitions that provide automated control of any of the 18 output devices, based on events occurring on individual zones or zones with certain zone types. Each output definition is identified by an output function number, and includes the following components: Output Definition Components Component Description Output Function No. A reference number from 01-48, which defines an output’s characteristics.
3000EN Series: Installation Instructions Activated By 01 Activated By: Zone List 0 = delete 1 = zone list 2 = zone type 3 = zone number [∗] to continue Select where the initiating event for this output definition is to occur as follows: 0 = delete (deletes the output function and any previous programming;-see prompt below) 1 = zone list (go to “A” prompt) 2 = zone type (go to “B” prompt) 3 = zone number (go to “C” prompt) If you enter “0,” the following prompt appears: Press 1 to delete this output defi
“C” Zone Number 01 Enter Zn No. 12 If zone number was selected, this screen appears. Enter the desired zone number associated with this output number. Press [✱] to continue. Enter the zone event that will activate this output. 0 = restore; 1 = alarm/fault/trouble 01 Enter Event Restore 0 Press [✱] to continue to the “Output Action” prompt 01 Output Action Close for 2 sec 1 Enter Output No. R02 02 02 A E P TRIG R02 1 1 3 ZL=00 Output Action 0-6 = see list at right.
3000EN Series: Installation Instructions 6-6
S E C T I O N 7 Zone Lists (∗81 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Zone Lists Zone lists let you group individual zones for use with certain system actions. The following table shows the available zone lists and their purposes: List No.
3000EN Series: Installation Instructions 01 Delete Zone? 0 = No 1 = Yes Deleting a Zone 0 01 Zn to Delete? (00 = Quit) 00 7-2 0 = don’t delete zones 1 = go to next prompt to delete zones [∗] to continue Delete the Zone 01-64 = zones to be deleted from list followed by [∗] to accept each zone 00 to continue To save the entire zone list, enter 0 and the system returns to the Zone List No. prompt. To delete a zone or zones in a zone list enter 1 to continue.
S E C T I O N 8 Function Key Programming (∗57 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Function Key Programming The system provides the ability to program each of the four touchpad function keys to perform one of 12 system operations. The end user can then activate the function by simply pressing and holding the programmed key for 2 seconds. Typical functions (listed below) include single-button arming, turning lights on/off, or single-button paging.
3000EN Series: Installation Instructions 8-2
S E C T I O N 9 Alpha Descriptor Programming (*82 Menu Mode) • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Descriptor Programming The system lets you assign zone descriptors for protection zones, touchpad panics, and RF receiver supervision faults. Each description can be composed of a combination of words (up to 3) selected from a vocabulary of 196 words stored in memory (see a following page).
3000EN Series: Installation Instructions ✱ ZN 01 Flashing Cursor [∗] to continue ✱ ZN 01 B ACK First 3-Digit Index No. see index for entries [∗] to continue To delete or change the default descriptor for zone 1, press [∗] plus the same zone number (01). This will clear that descriptor and allow changes to be made at the flashing cursor. NOTE: If you do not wish to change the existing descriptor for zone 1, enter [∗] plus the next zone number for which you wish to enter (or check) a descriptor.
Adding Custom Words (will not be annunciated by 4286 Phone Module) You can add up to 10 installer-defined words to the built-in vocabulary, which can then be used when programming zone descriptors. Each of the 10 words can actually consist of a word string of one or more words, but no more than ten characters can be used for each word or word string. When adding custom words, the touchpad keys perform the following functions: [4] Moves cursor one space to the left. [6] Moves cursor one space to the right.
Installation Instructions ALPHA VOCABULARY LIST 000 • 001 • 002 004 005 • 006 • 007 • 009 010 • • • • • • • 012 013 014 016 017 018 019 020 • 021 • 022 023 025 • 026 (Word Space) –A– AIR ALARM ∗ ALLEY AMBUSH AREA APARTMENT ATTIC ∗ AUDIO –B– BABY ∗ BACK ∗ BAR BASEMENT ∗ BATHROOM ∗ BED BEDROOM ∗ BELL BLOWER BOILER BOTTOM BREAK BUILDING 028 • 029 030 031 033 034 035 036 • 037 038 • 040 • 046 047 –C– CABINET CALL CAMERA CAR CASH CCTV CEILING CELLAR CENTRAL CIRCUIT CLOSED ∗ COMPUTER CONTACT • 048 049 • 05
S E C T I O N 1 0 Creating Schedules • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Schedules The system provides up to 32 schedules, which can be used to control up to 12 types of system events at pre-defined times. Sixteen schedules are intended for use by the end-user, and sixteen are reserved for the installer. In addition, some events are reserved for the installer only (see “Enter Event” prompt).
3000EN Series: Installation Instructions START Start Time STOP Stop Time SMTW TFS HH MMAM 0 0 1 0 0 0 0 SMTW TFS HH MMAM 0 0 1 0 0 0 0 01-12 = hour 00-59 = minute 0 = AM; 1 = PM Days = place “1” under days [∗] to continue 01-12 = hour 00-59 = minute 0 = AM; 1 = PM Days = place “1” under days [∗] to continue REPEAT OPTION 0-4 X Repeat Option 0 = do not repeat 1 = repeat schedule weekly 2 = repeat schedule biweekly (every other week) 3 = repeat schedule every third week 4 = repeat schedule every fo
S E C T I O N 1 1 ∗29 IP/GSM Menu Mode • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • ∗29 Communication Device Menu Mode (Pass-Through Programming) This mode is for programming an IP, GSM, or IP/GSM Communicator Module using a touchpad. Alternatively, these options can be programmed via the AlarmNet Direct website. After programming is complete, the module must be registered with AlarmNet before reporting via the communication device can occur.
Normal and SHIFT key Functions While in ∗29 Menu Mode Key (A) = BS/ESC Normal Key Function SHIFT Key Function [BS]: Press to delete entry [ESC]: Press to quit Program Mode Also, can reset EEPROM defaults † (B) = ↓/↑ [↓]: Scroll down programming [↑]: Scroll up programming (C) = N/Y [N]: Press for "NO" answer [Y]: Press SHIFT-Y for "YES" answer (D) = SHIFT Press before pressing a SHIFT key function. Will light READY LED. LED goes out once a key is pressed. Press again for each SHIFT function desired.
S E C T I O N 1 2 AVS System Enable and Quick Program Commands • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • AVS Command Procedure Applies to an AVS system using an ECP connection to the control. 1. Install the AVS module according to its instructions. 2.
3000EN Series: Installation Instructions 12-2
S E C T I O N 1 3 System Communication • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Report Code Format (Ademco Contact ID) Format Handshake Transmits Data Kissoff Transmit Time Contact ID 1400–2300Hz DTMF (10 cps) 1400Hz Under 3 secs. The Ademco Contact ID Reporting Format comprises the following: 4- or 10-digit subscriber number. 1-digit event qualifier (“new” or “restore”). 3-digit event code. 2-digit Partition No.
3000EN Series: Installation Instructions TABLE OF CONTACT ID EVENT CODES Code Definition Code 110 Fire Alarm 381 RF Sensor Supervision 121 Duress 382 Supervision Auxiliary Wire Zone 122 Alarm, 24-hour Silent 383 RF Sensor Tamper 123 Alarm, 24-hour Audible 384 RF Sensor Low-battery 131 Alarm, Perimeter 401 Disarmed, Armed AWAY 132 Alarm, Interior 403 Schedule Arm/Disarm AWAY 134 Alarm, Entry/Exit 406 Cancel by User 135 Alarm, Day/Night 407 Remote Arm/Disarm (Downloading) 1
Section 22. System Communication Uploading/Downloading via the Internet This control, when used with a compatible Internet/Intranet Communication Device, supports upload/download programming capability via the Internet using the AlarmNet network or, depending on the communication module used, a Private local area network (Intranet). This allows site maintenance independent of central station monitoring, and modification to sites globally via the Internet or through a private LAN.
13-4
S E C T I O N 1 4 System Operation • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • Security Codes The system supports up to 48 security codes, which can each be assigned one of 5 authority levels. The authority level determines the functions a particular user code can perform as follows: Authority Levels (authority levels can be assigned to users 3-49 only; users 1 and 2 cannot be changed) Level Installer User No.
3000EN Series: Installation Instructions Adding/Deleting Security Codes and Changing User Attributes The following lists the various command strings for adding user codes and attributes. NOTE: Partition Master codes apply only to those user numbers assigned to the partition master’s partition (default: users 03-32 = partition 1; users 33-49 = part. 2) Changing the System Master code...
Touchpad Functions The following is a brief list of system commands. For detailed information concerning system functions, refer to the User's Manual. For AUI users, refer to the separate AUI User’s Guide Voice Touchpads The 6160VADT Voice Touchpads provide the following voice features: • Message Center, which lets the user record and playback one message. • Voice Status, which can announce system status by using the STATUS key.
3000EN Series: Installation Instructions SUMMARY OF ARMING MODES Features for Each Arming Mode Arming Mode Exit Delay Entry Delay Perimeter Armed Interior Armed AWAY Yes Yes Yes Yes STAY Yes Yes Yes No INSTANT Yes No Yes No NIGHT-STAY Yes Yes Yes Only those zones listed in NightStay zone list Panic Keys There are three Panic keys (A, B, and C) that, if programmed, can be used to manually initiate alarms and send a report to the central station.
Various System Trouble Displays Alpha Display Fixed Disp. ALARM CANCELED CA EXIT ALARM EA CHECK CHECK ALARM 1xx FAULT 1xx CHECK 1xx 1xx 1xx 1xx (91) SYSTEM LO BAT LO BAT BAT BAT TELCO FAULT 94 Busy-Standby dl Modem Comm CC no display no display Comm.
3000EN Series: Installation Instructions 14-6
S E C T I O N 1 5 Testing the System • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • About Test Procedures After the installation is complete, you should perform the following tests: System Test: Checks that all zones have been installed properly and the system properly responds to faults. Dialer Test: Checks that the phone connection to the central station is working properly. Go/No Go Test: Checks that transmissions can be received from transmitters.
3000EN SERIES: INSTALLATION INSTRUCTIONS Checking Transmitter Enrollment (Sniffer Mode) Use this mode to verify that all transmitters have been properly programmed. Make sure both partitions are disarmed before trying to enter this mode, since this is a system-wide command. 1. From a touchpad in partition 1, Press [Installer code] + [#] + 3. Note: If the communicator is in the process of sending a report to the central station, the system will not go into the Sniffer mode.
Dialer Communication Test and Periodic Test Reports 1. Enter Installer Code + 5 [TEST], then press “1” at the prompt to start the Dialer Test (checks phone line integrity only; does not confirm report transmissions).
3000EN SERIES: INSTALLATION INSTRUCTIONS 15-4
S E C T I O N 1 6 Specifications & Accessories • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • SECURITY CONTROL 1. Physical: 12-1/2” W x 14-1/2” H x 3” D (318mm x 368mm x 76mm) 2. Electrical: VOLTAGE INPUT: 16.5VAC from plug-in 25VA transformer, Ademco No. 1321 (in U.S.A.) RECHARGEABLE BACKUP BATTERY: 12VDC, 17AH (sealed lead acid type). Charging Voltage: 13.8VDC. ALARM SOUNDER: 12V, 2.
3000EN SERIES: INSTALLATION INSTRUCTIONS 5800 Series Transmitter Input Loop Identification All of the transmitters illustrated below have one or more unique factory assigned input (loop) ID codes. Each of the input loops requires its own programming zone (e.g., a 5804's four inputs require four programming zones).
S E C T I O N 1 7 Regulatory Agency Statements • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • FEDERAL COMMUNICATIONS COMMISSION (FCC) PART 15 STATEMENTS The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User's Manual. Unauthorized changes or modifications could void the user's authority to operate the equipment.
3000EN SERIES: INSTALLATION INSTRUCTIONS – NOTES – 17-2
– NOTES – 17-3
3000EN SERIES: INSTALLATION INSTRUCTIONS – NOTES – 17-4
S E C T I O N 1 8 Limitations and Warranty • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • WARNING THE LIMITATIONS OF THIS ALARM SYSTEM While this System is an advanced design security system, it does not offer guaranteed protection against burglary, fire or other emergency. Any alarm system, whether commercial or residential, is subject to compromise or failure to warn for a variety of reasons. For example: • Intrusion detectors (e.g.
3000EN SERIES: INSTALLATION INSTRUCTIONS WARNING THE LIMITATIONS OF THIS ALARM SYSTEM (Continued) The most common cause of an alarm system not functioning when an intrusion or fire occurs is inadequate maintenance. This alarm system should be tested weekly to make sure all sensors and transmitters are working properly. The security touchpad (and remote touchpad) should be tested as well.
– INDEX – 1321 AC Transformer....... 1-2, 2-5, 2-15 24-Hour Audible Alarm ..................... 3-4 24-Hour Auxiliary Alarm ................... 3-4 24-Hour Silent Alarm........................ 3-4 2-Wire Smoke Detectors .................. 2-8 3-Digit Number................................. 9-2 4142TR Cable .................................. 2-5 4146............................................... 2-13 4204.... 1-2, 2-7, 2-8, 2-14, 3-1, 6-1, 6-2, 12-3, 14-1 4219........ 1-1, 1-2, 2-7, 2-10, 2-14, 14-1 4229..
3000EN SERIES: INSTALLATION INSTRUCTIONS R Receiver and Transmitters ............... 3-2 Relay Modules ............................... 2-14 Relay Programming ......................... 3-1 Report Code....................... 4-5, 5-2, 5-5 Report Format.................................. 4-4 Reports In Armed Period.................. 4-9 Response Time .............................. 2-10 RF House ID Code........................... 4-1 RF Interference .............................. 2-11 RF Jam Detection .........
CONNECTION OF THE FIRE ALARM SIGNAL TO A FIRE ALARM HEADQUARTERS OR A CENTRAL STATION SHALL BE PERMITTED ONLY WITH THE PERMISSION OF THE LOCAL AUTHORITY HAVING JURISDICTION. THE BURGLAR ALARM SIGNAL SHALL NOT BE CONNECTED TO A POLICE EMERGENCY NUMBER. THIS EQUIPMENT SHOULD BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FIRE PROTECTION ASSOCIATION'S STANDARD 72, CHAPTER 11 (NATIONAL FIRE PROTECTION ASSOCIATION, BATTERY-MARCH PARK, QUINCY,MA 02169).
• • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • • ADT Security Services, Inc. One Town Center Rd, Boca Raton, FL 33486 Copyright © 2003 ÊK5305V8sŠ K5305V8 11/10 Rev.