Instruction manual
64203376L1-1B © 2004 ADTRAN, Inc. 261
DLP-16 Connecting the Alarm Contacts and the External Input
Introduction
Alarm connections alert the user when a selected alarm condition exists. Pressing the Alarm Cut-Off
(
ACO) switch on the front panel of the Total Access 850 PSU clears the alarm. This procedure details the
steps which must be performed to use the Total Access 850 alarm connections and the
ACO switch.
This procedure should be performed at installation on each Total Access 850 shelf that is wired out to
external office alarm equipment.
Prerequisite Procedures
Before beginning this procedure, the Total Access 850 should be mounted in its permanent location.
Tools and Materials Required
• Wire strippers
• Small Phillips screwdriver
• 22 or 24 AWG 2-conductor twisted pair cross-connect wire
• VT100 terminal or PC with VT100 terminal emulation software
To prevent electrical shock, do not install equipment in a wet location or during a
lightning storm.
Electronic modules can be damaged by static electrical discharge. Before handling
modules, put on an antistatic discharge wrist strap to prevent damage to electronic
components. Place modules in antistatic packing material when transporting or storing.
When working on modules, always place them on an approved antistatic mat that is
electrically grounded.