Total Access 850 System Manual Section 5 DLP-16
64203376L1-1B © 2004 ADTRAN, Inc. 263
2. Alarm relay contacts are open during normal operation. The alarm relay contacts close in the event of
a local alarm condition or the receipt of an alarm from the T1 Carrier.
3. In a carrier alarm condition such as a Red, Yellow, or Blue (unframed all 1s), various alarm contacts in
the PSU close.
4. Carrier alarm conditions cause the Total Access 850 to initiate trunk processing. The following chain of
events then occur:
MJ will be directly shorted to MJR.
MJV will be directly shorted to MJVR.
5. Contacts MJ and MJR can be overridden manually during an alarm condition by pressing the ACO
pushbutton on the PSU faceplate.
6. If the 3-Amp power fuse on the PSU trips, the -48 ALM relay will close, providing a -48 VDC signal on
that pin. This alarm cannot be overridden by the ACO pushbutton. Refer to the table below for alarm
notifications.
Alarm Condition Relays Activated
MJR MJVR -48 ALM
RED ALARM X X
YELLOW ALARM X X
AIS ALARM X X
PSU POWER FUSE FAILS X X X
ALARMS ACO
DEACTIVATES
X X
Note: ACO will not deactivate MJR after a power fuse
failure.