Troubleshooting guide

Section 5, User Interface Guide - UIG-510, Status
61186003L1-1D 5-19
SCU ALARMS
View the status of SCU alarms by selecting the following options:
Select SYSTEM CONTROLLER, from the MX2820 Main Menu, and press ENTER.
Select STATUS, from the System Controller menu, and press ENTER.
Return to the MX2820 Main Menu, by pressing ESC until the menu appears.
Figure 5-7 shows the SCU Status screen. The following subsection describes the fields in the
External Inputs section.
Figure 5-7. SCU Status Screen
External Inputs
The External Inputs section provides the status of environmental alarm connections on the
backplane of the MX2820. A description of these is provided in Table 5-1.
Table 5-1. SCU Alarm Status Screen, External Inputs
Input Name Severity Description
Ext ACO N/A The Alarm Cutoff acknowledges any unacknowledged alarms.
AUX #1, #2 User Definable These alarms are user definable alarms. The severity as well as
the description string can be modified.
AUX #3A User Definable When acting as a fan alarm, this input will generate a solid
alarm signal which indicates a complete failure of the fan mod
-
ule.
Shelf: 1 ADTRAN MX2820 System 04/21/04 23:09
Unacknowledged Alarms: None TID: HTVLALEXD16
Status
Hardware LEDs
Ethernet Link : Up ACT : Grn/Ylw
ALM : Red
Alarm Relays
Critical Inactive
Major Active
Minor Inactive
External Inputs Status Level
Ext ACO Inactive N/A
AUX #1 INPUT Inactive MAJOR
AUX #2 INPUT Inactive MAJOR
AUX #3A INPUT Inactive MAJOR
AUX #3B INPUT Inactive MAJOR
PWR Bus A Active MAJOR
PWR Bus B Inactive MAJOR
'?' - System Help Screen