ACCESS MODULE REMOVED ALARM LEVEL
The Access Module Removed Alarm Level option allows the alarm severity level to be set to
indicate that a module is removed from the MX2820 shelf.
For Service Affecting (SA) the default alarm severity level is MAJOR.
For Non-Service Affecting (NSA) the default alarm severity level is MINOR.
To access this option, perform the following steps:
1. Select SYSTEM ALARMS, from the MX2820 Main Menu, and press ENTER.
2. Select USER-DEFINABLE ALARMS, from the System Alarms menu, and press ENTER.
3. Select either
SA or NSA MODULE REMOVED LEVEL, from the User-Definable Alarms menu, and
press
ENTER.
Figure 5-108 provides an illustration of the SA Module Removed Level menu (NSA menu has
identical options).
Figure 5-108. Access Module Removed Level Menu
4. Input a number from 1 to 5, and press ENTER to set the desired alarm severity level.
5. Return to the MX2820 Main Menu screen by pressing
ESC until the screen appears.
Shelf: 1 ADTRAN MX2820 System 05/04/04 12:52
Unacknowledged Alarms: None TID: HTVLALEXD16
SA Module Removed Level : MAJOR
1 - INFO
2 - ALERT
3 - MINOR
4 - MAJOR
5 - CRITICAL
Selection : '?' - System Help Screen