Troubleshooting guide
Section 7, User Interface Guide - DLP-723, Verifying Fan Module Alarm Connection to the SCU
61186003L1-1D 7-97
8. Check the System Alarm log to verify the AUX3 fan failure alarm clears. The original AUX3
fan failure active alarm remains in the System Alarm log, but should no longer be reversed
video. A new line should appear in the System Alarm log and indicate that the fan failure
alarm has cleared.
9. At the Master Alarm screen, select (C)lear to clear inactive alarms.
10. Repeat this test for each shelf with a Fan Module.
FOLLOW-UP PROCEDURES
Once this procedure is complete, return to the procedure which called out this DLP and
continue with the tasks indicated.