User's Manual

1 3/16”
7
1/4”
Installation Instructions:
1. Turn o all power to the light xtures by
switching o the circuit breaker.
2. Open the xture cover and remove the cover
for the ballast cavity. The ballast and its wiring
should now be visible. (See Figure #1)
3. With a volt meter, verify that power is o to the
light xture.
4. Place Light Controller in the desired location and
secure with the magnets on the rear of the Light
Controller or screw it down.
5. Disconnect the hot wire to the ballast
(black for 120 VAC or brown for 277 VAC).
6. Connect the black wire on the Light Controller
wires to the hot wire (black for 120 VAC or brown
for 277 VAC) using a wiring connector (see wiring
diagram #1 for one relay and wiring diagram #2
for two relays).
7. Connect the blue wire on the Light Controller
to the black wire on the ballast using a wiring
connector. For the LC-2R, connect the red wires
as shown in wiring diagram #2.
8. Connect the white wire on the Light Controller
to the white wire on the ballast and to the white
wire on the incoming power wiring using a
wiring connector.
9. Bend wires into place such that ballast cover
can easily be reattached.
10.Reattach the ballast cover and close the
luminaire cover.
11. Switch power on to the xture. Lights should
turn on.
12.Refer to the setup application instructions for
information on programming the light
controller.
Dimming Control (LC-1RD)
(See wiring diagram #3)
CAUTION: LOW VOLTAGE WIRING
MUST BE TREATED AS CLASS 1
1. Connect the gray wire on the LC-1RD to the gray
wire or gray terminal on the dimming ballast.
2. Connect the violet wire on the LC-1RD to the
violet wire or violet terminal on the dimming
ballast.
3. When switched on, lamps should turn on to full
brightness. (Approximately 10 VDC signal on the
violet wire to ground).
Dimensions:
6
11/16”
7
5/8”
1”
Wiring Diagram #1
LC-1R
FIGURE #1
ADURA TECHNOLOGIES™
San Francisco, CA 94105
Tel: 415.227.0868 • Toll Free 1-888-828-8281
TM
120 VAC /277 VAC
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
BALLAST
H
N
LC-1R
WHITE
N
BLACK
BLUE
WHITE
BLACK
Wiring Diagram #3
LC-1RD
Wiring Diagram #2
LC-2R
120 VAC /277 VAC
RED
RED
BLACK
WHITE
BLUE
BALLAST #2
N
H
N
LC-2R
WHITE
N
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
EXISTING WIRING
120 VAC /277 VAC
BLACK
BALLAST #1
N
H
BLACK
WHITE
120 VAC /277 VAC
EXISTING WIRINGEXISTING WIRING
EXISTING WIRING
N
LC-1RD
BALLAST (0-10VDC DIMMING)
H
N
BLACK
WHITE
BLUE
BLACK
WHITE
GRAY
VIOLET
EXISTING WIRING
LOW VOLTAGE (MUST BE TREATED AS CLASS 1 WIRING)