RB304 Installation Instructions
P/D 040501
A10 277/480 VAC, Box Mount Receiver
RB304
BEFORE YOU BEGIN...
READ ALL INSTRUCTIONS
Make sure your installation will conform to all applicable codes and requirements.
INSTALLATION
POWER CONNECTIONS:
1. Warning, shock hazard: To service the load, disconnect main power. Do not use the manual ON/
OFF override switch to disconnect load for service.
2. If single phase connection (277V) perform the following steps:
a) Connect the power supply neutral wire to the White wire marked “N” on the board.
b) Connect the line wire to the Orange wire marked “L1” on the board.
c) Connect White wire “N” to Pink wire marked “PCC” on the board .
d) There should be no connection to the Brown wire marked “L2” on the board.
3. If leg to leg connection (480V) perform the following steps:
a) Connect one line wire to the Orange wire marked “L1” on the board.
b) Connect the second line wire to the Brown wire marked “L2” on the board.
c) Connect Brown wire “L2” to Pink wire marked “PCC” on the board.
d) There should be no connection to the White wire marked “N” on the board.
OUTPUT CONNECTIONS:
1. Connect the load to the GREY wire (normally open), or the BLUE wire (normally closed)
lead, and the VIOLET wire (common) lead.
2. See the "Relay Output" section in the specifications for maximum current and voltage
ratings.
EXTERNAL SWITCH:
1. Connect a switch to the removable terminal block. The switch may be any dry-contact switch
or relay. When the contact is closed the output relay will remain energized. When the switch
is opened the relay will default back to the last PCC command received.
2 The External Switch is only operational while the ON/OFF/AUTO switch is in the "AUTO”
position.
3. The External Switch is not required for proper operation of the unit - only use if this feature
is desired.