2kV PV Wire Datasheet
PV PHOTOVOLTAIC CABLE
PHONE: (800) 343 2579 • FAX: (828) 389 3922 • WWW.ADCABLE.COM
6
Cable Identification
Description
ADC’s Solarlink brand Photovoltaic cable has a chemically
cross-linked polyethylene insulation.
Applications
Appropriate for use in solar power applicatioins that require
2,000 volt rating. For use in grounded interconnection and
ungrounded Photovoltaic power systems.
Construction
Conductors: Stranded bare copper conductor per ASTM B-3, B-8.
Available in 7 or 19 stranded versions as well as tinned copper.
Insulation: Chemically Cross-linked polyethylene
Colors: Black, Green, White, Red. Print on one side with a
contrasting ink. An extruded stripe and other colors are avail
-
able upon request.
Industry Listings & Standards
UL Listed as Photovoltaic Cable per Standard Subject 4703 and 44
-40°C/90°C Wet and Dry Rated
Gasoline and Oil Resistant II
RoHS Compliant
Sunlight Resistant
VW-1 Flame Rating Optional
Cable Data
Part Number AWG Strand
Insulation Thick-
ness
(mils)
Nominal O.D.
(inch)
Approximate
Net Weight
lbs/1M’
3182NPV 18 7 75 .196 18
3162NPV 16 7 75 .208 22
3142NPV 14 7 75 .221 28
3122NPV 12 7 75 .242 38
3102NPV 10 7 75 .264 51
3082NPV 8 7 85 .314 78
3062NPV 6 7 85 .351 112
3042NPV 4 7 85 .399 166
3032NPV 3 7 85 .427 203
3022NPV 2 7 85 .459 249
3012NPV 1 19 105 .539 323
30102NPV 1/0 19 105 .572 390
30202NPV 2/0 19 105 .616 480
30302NPV 3/0 19 105 .667 590
30402NPV 4/0 19 105 .722 737
302502NPV 250 MCM 37 120 .798 879
303002NPV 300 MCM 37 120 .845 1045
303502NPV 350 MCM 37 120 .901 1198
304002NPV 400 MCM 37 120 .946 1365
305002NPV 500 MCM 37 120 1.029 1673
306002NPV 600 MCM 61 135 1.136 2011
307502NPV 750 MCM 61 135 1.238 2518
“ADVANCED DIGITAL CABLE INC. XX AWG (UL)
PV WIRE OR RHW-2 2000V OR USE-2 600V 90°C
WET OR DRY (-40C) SR GRII DIRECT BURIAL RoHS
E324841”
2kV Rated PV
Cross-Linked Polyethylene Insulated
18 - 750 MCM • 2000 Volts • -40°C to 90°C Wet and Dry
The information contained on this specification is intended to be used as a guide in product selection and is believed to be reliable.
ADC has made every effort to ensure the data shown above is accurate at the time of publication. This specification is subject to change anytime without notice. REV0618
Bare Copper
XLPE Insulation