Advanced Energy® AE 3TL Inverters 600 Series and 1000 Series Installation and Operation User Manual October 2013 570-1002542-05B
Advanced Energy® AE 3TL Inverters 600 Series and 1000 Series Installation and Operation User Manual October 2013 570-1002542-05B
Advanced Energy COPYRIGHT This manual and the information contained herein are the proprietary property of Advanced Energy Industries, Inc. No part of this manual may be reproduced or copied without the express written permission of Advanced Energy Industries, Inc. Any unauthorized use of this manual or its contents is strictly prohibited. Copyright © 2013 Advanced Energy Industries, Inc. All Rights Reserved.
Advanced Energy® AE 3TL Inverters Belden® is a registered trademark of Belden, Inc. Modbus® is a registered trademark of Schneider Electric USA, Inc. Power Factor Pro™ is a trademark of Advanced Energy Industries, Inc. Windows® is a registered trademark of the Microsoft Corporation. PATENTS Subject to patents listed at http://www.advanced-energy.com/en/Patents.html.
Advanced Energy vi 570-1002542-05B
Advanced Energy® AE 3TL Inverters Table of Contents Chapter 1. Safety and Product Compliance Guidelines Important Safety Instructions ................................................................................ Save These Instructions ........................................................................................ Danger, Warning, and Caution Boxes in the Manual ............................................ Safety Guidelines .......................................................................
Advanced Energy Utility Connection Requirements .................................................................... Contacting Your Local Utility .......................................................................... Voltage Output ................................................................................................ Connection Box Overview ..................................................................................... 3-3 3-4 3-4 3-4 Chapter 4. Installing Handling and Unpacking ....
Advanced Energy® AE 3TL Inverters To Change the Menu Language ................................................................... To Select the Communications Settings ....................................................... To Configure the Portal Settings .................................................................. Data Logger ........................................................................................................ To Configure the Data Logger Settings ................................
Advanced Energy Appendix C. Inverter Startup Checklist Inverter Startup Checklist .....................................................................................
Advanced Energy® AE 3TL Inverters List of Tables Table 1-1. Branch breaker size recommendations ............................................... 1-7 Table 1-2. Acronyms and frequently used terms .................................................. 1-9 Table 3-1. Mounting clearances ............................................................................ 3-2 Table 4-1. Maximum DC operating data ............................................................. 4-16 Table 4-2. DC conductor sizing ...............
Advanced Energy xii List of Tables 570-1002542-05B
Advanced Energy® AE 3TL Inverters List of Figures Figure 2-1. AE inverter installed in a utility grid PV system ................................... 2-2 Figure 2-2. Main components of the AE 3TL inverter ........................................... 2-3 Figure 2-3. Inverter controls and display ............................................................... 2-4 Figure 3-1. Required clearances ........................................................................... 3-2 Figure 3-2. Inverter dimensions ......
Advanced Energy xiv List of Figures 570-1002542-05B
Advanced Energy® AE 3TL Inverters Chapter 1 Safety and Product Compliance Guidelines IMPORTANT SAFETY INSTRUCTIONS To ensure safe installation and operation of the Advanced Energy AE 3TL unit, read and understand this manual before attempting to install and operate this unit. At a minimum, read and follow the safety guidelines, instructions, and practices.
Advanced Energy WARNING: WARNING indicates a potentially hazardous situation that, if not avoided, could result in death or serious injury, and/or property damage. AVERTISSEMENT: AVERTISSEMENT indique une situation potentiellement dangereuse qui, si elle n’est pas évitée, pourrait provoquer la mort ou des blessures graves et/ ou des dommages matériels. CAUTION: CAUTION indicates a potentially hazardous situation that, if not avoided, could result in minor or moderate injury, and/or property damage.
Advanced Energy® AE 3TL Inverters • Always be careful around this equipment. • Never remove the upper inverter lid. • Safe operation requires correct transport, storage, assembly, installation, and operation. PERSONAL SAFETY Ensure that any personnel entering a safety zone within a four foot area around any operating inverter wear appropriate Personal Protective Equipment (PPE) as mandated by national, state, and local authorities.
Advanced Energy Protective Earth ground 1029 Hazardous voltage 1028 Hot surface 1309 Refer to manual for more information 1027 Heavy object—can cause muscle strain or back injury Electrocution hazard 3054 Hazardous voltage PRODUCT COMPLIANCE The following sections include information about unit compliance and certification, including the conditions of use required to be in compliance with the standards and directives.
Advanced Energy® AE 3TL Inverters ☞ Important This equipment must be installed and used in accordance with the Conditions of Use described in this manual. If this equipment is expanded, modified, or installed into a larger system, the user is responsible to guarantee the compliance of the overall system. If this equipment is used with external components, the user must ensure that the Safety and EMC requirements are not violated.
Advanced Energy DANGER: Risque de choc électrique. Le boîtier de l’onduleur contient de hautes tensions. La source de tension CC (DC Disconnect) doit être à la position OFF lorsque des travaux sont effectués sur l’appareil. Attendre cinq minutes pour que les composants haute tension se déchargent avant d’ouvrir la boîte de jonction de l’onduleur. CAUTION: Risk of electrical shock. All electrical installations should be accomplished in accordance with applicable national or local standards.
Advanced Energy® AE 3TL Inverters You must meet the following requirements when wiring the AE 3TL inverter: Table 1‑1. Branch breaker size recommendations Model Breaker Size AE 3TL-12kW 20 A AE 3TL-16kW 30 A AE 3TL-20kW 35 A AE 3TL-23kW 40 A WIRING INFORMATION ☞ Important You must use National Electrical Code (ANSI/NFPA 70) wiring methods. • All wiring methods and materials shall be in accordance with the National Electrical Code ANSI/NFPA 70 as well as all state and local code requirements.
Advanced Energy Grounding Requirements Determine the appropriate grounding method with the responsible authority having jurisdiction. • System grounding, if required by Section 250 of the National Electrical Code, ANSI/NFPA 70, is the responsibility of the installer. • The photovoltaic system grounding shall be installed per the requirements of Section 690.41 through 690.47 of the National Electrical Code, ANSI/NFPA 70, and is the responsibility of the installer.
Advanced Energy® AE 3TL Inverters Heat Hazard The AE 3TL cabinet surface and heat sink can reach temperatures up to 75°C (167°F). WARNING: Risk of burn. The inverter components can become extremely hot during normal operation. Use caution when working around the heat sink area. AVERTISSEMENT: Risque de brulure. Certaines parties de l’onduleur peuvent atteindre des températures considérables durant une exploitation normale. Soyez prudent durant les travaux autour du puits thermique.
Advanced Energy Table 1‑2.
Advanced Energy® AE 3TL Inverters Table 1‑2. Acronyms and frequently used terms (Continued) Term Description UTC Universal time coordinate. Also known as Greenwich mean time.
Advanced Energy 1‑12 Safety and Product Compliance Guidelines 570-1002542-05B
Advanced Energy® AE 3TL Inverters Chapter 2 Product Overview OVERVIEW OF THE AE 3TL THREE-PHASE INVERTER The Advanced Energy AE 3TL three-phase inverter converts direct current (DC) power generated by a PV panel into alternating current (AC) compatible with the local electrical distribution network (also called the public utility or the grid system). The grid-tied, three-phase AE 3TL inverter is designed with a transformerless topology.
Advanced Energy The AE inverter provides conventional RS-485 and Ethernet communication interfaces. The screen provides the feed-in power progression and other operating data. The control panel buttons facilitate ease of operation. Utility grid PV array Meter Inverter Figure 2‑1. AE inverter installed in a utility grid PV system IDENTIFYING THE PARTS OF THE AE 3TL INVERTER The inverter has two main sections: the main housing and the connection box.
Advanced Energy® AE 3TL Inverters Heatsink Main inverter housing Display, LEDs, and control buttons Connection box DC Disconnect Figure 2‑2. Main components of the AE 3TL inverter The name plate on the right side of the AE 3TL inverter can be used to identify a specific unit. The name plate provides general electrical information for the inverter. A warning label is located on the right side of inverter. The warning label includes important notices to prevent electric shock and damage to the unit.
Advanced Energy • DC disconnect switch: The built-in disconnect switch allows you to disconnect DC input from the inverter. LED indicators Display Control buttons DC disconnect switch Figure 2‑3.
Advanced Energy® AE 3TL Inverters Chapter 3 Planning MOVING AND STORING THE INVERTER Store the inverter in a clean and dry room in the original packaging. Always transport the inverter in its original packaging. If the storage period exceeds two years, contact AE Solar Energy Technical Support prior to connecting the inverter. • The moving and storage temperature must be between -25°C (-13°F) and +70°C (+158°F). • Temperature fluctuations may not exceed 20°C (35°F) per hour.
Advanced Energy SPACING AND CLEARANCES The inverter requires adequate space for proper cooling. When installed, the inverter must have the following clearances: Table 3‑1. Mounting clearances Location Minimum Clearance Top 51 cm (20″) Bottom 51 cm (20″) Side 15 cm (6″); right side of last inverter is 5 cm (2") clearance Rear 00 cm (0″) Front Clearance as specified by NEC 110.26. 15 cm (6”) 5 cm (2”) 50 cm (20”) 15 cm (6”) Figure 3‑1.
Advanced Energy® AE 3TL Inverters DIMENSIONS The following figure shows the unit dimensions. 27 cm (11”) 94 cm (37”) 53 cm (21.1”) Figure 3‑2. Inverter dimensions UTILITY GRID INTERCONNECTION DANGER: Risk of electrical shock. Before connecting the inverter to the electrical utility grid, your utility company must grant approval. Only qualified electricians should make the connection to the utility grid. DANGER: Risque d’électrocution.
Advanced Energy Contacting Your Local Utility Contact your electrical utility before connecting the inverter to ensure there are no local restrictions or special requirements. Your local utility company may require specific inspections, equipment, or other procedures not covered in this document. Voltage Output The AC output voltage is available on the inverter nameplate for available output voltage configurations. AC and DC power requirements are included in the specifications.
Advanced Energy® AE 3TL Inverters Communication board RS-485 connection DC disconnect RJ-45 Ethernet connection Sensor connection (analog) AC input Grounding stud DC inputs Figure 3‑3. Components of the 600 series connection box Communication board RS-485 connection DC disconnect RJ-45 Ethernet connection Sensor connection (analog) AC input Grounding stud DC inputs Figure 3‑4.
Advanced Energy 3‑6 Planning 570-1002542-05B
Advanced Energy® AE 3TL Inverters Chapter 4 Installing HANDLING AND UNPACKING This section describes the required safe handling and unpacking procedures for the AE 3TL inverter. Always follow the recommendations in this section to prevent accidental damage or injury. Unpacking the Unit Multiple handles are located on both sides of the inverter to facilitate lifting the unit during installation. Due to the length and weight of the inverter, two people are required to lift the unit.
Advanced Energy WARNING: Do not attempt to lift the full weight of the unit from the left or right sides only. Attempting to lift from just the left or right sides only will result in an unstable and unsafe condition. AVERTISSEMENT: Ne pas tenter de soulever l’unité uniquement à partir du côté gauche ou droit. Toute tentative de soulever l’unité par le côté gauche ou droit pourrait occasionner une situation d’instabilité dangereuse. TOOLS REQUIRED • Utility knife TO UNPACK THE INVERTER 1.
Advanced Energy® AE 3TL Inverters Upper handle Central handle Central handle Lower handle Figure 4‑1. Handle locations 2. Carefully open the box. 3. Use the central handles on each side of the inverter to lift the inverter from the box. The cardboard flap remains attached to the inverter housing and can be used to protect the unit when it is placed on the floor to prevent damage to the lid.
Advanced Energy • User manual To Inspect the Inverter 1. Inspect the shipping materials and the inverter for any cosmetic or structural damage. 2. Inspect the screen for any visible damage. If no damage is apparent, proceed with the inverter installation. If you do see signs of shipping damage, contact Advanced Energy and the carrier immediately. If you need to return the inverter, it must be shipped in the original shipping container. INSTALLATION REQUIREMENTS DANGER: RISK OF DEATH OR BODILY INJURY.
Advanced Energy® AE 3TL Inverters WARNING: Maintenance personnel must receive proper training before installing, troubleshooting, or maintaining high-energy electrical equipment. Potentially lethal voltages could cause death, serious personal injury, or damage to the equipment. Ensure that all appropriate safety precautions are taken. AVERTISSEMENT: Le personnel d’entretien doit recevoir une formation appropriée avant d’installer, de dépanner ou d’entretenir un équipement électrique à haute énergie.
Advanced Energy • The display should be located approximately 160 cm (63″) above the ground for ease of use and operation. An elevated mounting position is permitted if easy access to the display is provided. Viewing the display using a ladder, an aerial platform or the equivalent is acceptable. • Minimum clearances for each inverter must be observed. ☞ Important Do not impair or block the heat sink cooling fins. Never install the units above one another.
Advanced Energy® AE 3TL Inverters AVERTISSEMENT: Avant de percer des trous pour installer l’onduleur, vérifier qu’iln’y a aucun fil électrique ou plomberie dans le secteu. CAUTION: When rack mounting the AE 3TL unit, you must use support rails to support the unit. The AE 3TL unit face plate will not support the weight of the unit. ATTENTION: Si vous effectuez un montage sur rails de l’appareil AE 3TL , il est nécessaire d’utiliser un dispositif d’appui pour supporter l’appareil.
Advanced Energy 2. Use a pencil to draw a level, horizontal line approximately 40 cm (16″) above the position intended for the display. The inverter is designed only for vertical installation. The following illustration shows the required dimensions and drilling locations to attach the wall mount bracket to the wall. M5 FLAT WASHER M5 LOCKNUT WALL M5 X 20 SCREW SEE CHART FOR ANCHORS Figure 4‑3. Wall mount bracket 3. Hold the wall mount bracket with the end with mounting hooks to the pencil line.
Advanced Energy® AE 3TL Inverters Heatsink cooling fins Lower edge of heatsink Figure 4‑4. Mounting the inverter on the wall mount bracket 9. Fasten the heatsink to the wall mount bracket using two washers and two of the included screws. AC AND DC WIRING FEEDTHROUGH CAUTION: For outdoor installations make liquid-tight connections to the unit. ATTENTION: Pour les installations extérieures, effectuer des connexions étanches à l’unité.
Advanced Energy ☞ Important All conductors must enter the connection box through the available feedthrough locations which are for the sole purpose of providing a safe and convenient way to route wiring in to and out of the inverter. Penetrating the inverter housing in any other location voids the warranty. Installing a Feedthrough TOOLS AND MATERIALS REQUIRED • NEMA 3R conduit hubs with rubber seals TO INSTALL A FEEDTHROUGH 1.
Advanced Energy® AE 3TL Inverters To Connect the Grounding Stud The grounding stud is located in the same place in both the 600 and 1000 series. 1. Strip 20 mm (3/4″) of protective covering from the grounding conductor. 2. Connect the separate equipment grounding conductor from the grounding stud to an earth ground. Grounding stud Figure 4‑5. Grounding stud in the connection box 3. Pull test the ground conductor.
Advanced Energy AVERTISSEMENT: Risque d’endommagement matériel. L’onduleur est équipé de circuits sensibles aux décharges d’électricité statique (DES). Déchargez toute accumulation d’électricité statique en mettant la peau nue en contact direct avec la terre avant de toucher un composant interne. WARNING: Do not open the connection box during damp or dusty conditions. Working with exposed electrical components in damp weather may result in dangerous electrical shock.
Advanced Energy® AE 3TL Inverters TO REMOVE THE CONNECTION BOX COVER 1. Turn the DC disconnect switch to the OFF position. 2. Remove the screws with spring lock washers on the two left corners of the connection box cover. 3. Open the cover. The connection box cover swings to the right on its hinge. ☞ Important Handle the cover with care.
Advanced Energy DC1 1 2 3 4 5 1 DC2 2 3 4 5 1 Module 1 Module 1 Module n Module n 2 3 4 5 1 2 4 5 3 4 5 Figure 4‑6. 600 series DC connection example 1000 SERIES 1 2 3 4 5 6 1 2 3 6 Module 1 Module n Figure 4‑7.
Advanced Energy® AE 3TL Inverters DC Conductors DANGER: Electrical connections must comply with national and local standards. Voltage drop and other considerations may dictate that larger wire sizes be used. DANGER: Les connexions électriques doivent être conformes aux normes nationales et locales. Des chutes de tension et autres facteurs peuvent imposer l’usage de fils de plus gros calibre. WARNING: Use suitable precautions; this area contains high voltages that could cause serious injury or death.
Advanced Energy Table 4‑1. Maximum DC operating data Maximum per Fuse Bank 12TL 16TL 20TL 23TL 600 series: 500 V DC voltage 1000 series: 1000 V DC operating current 27.5 A 33 A 37.5 A 40 A DC Connections DANGER: Electrical connections must comply with national and local standards. Voltage drop and other considerations may dictate that larger wire sizes be used. DANGER: Les connexions électriques doivent être conformes aux normes nationales et locales.
Advanced Energy® AE 3TL Inverters DANGER: Avant d’effectuer les branchements CC, assurez-vous que les piles PV sont déconnectées de l’onduleur en utilisant le connecteur CC externe. DANGER: Make sure the PV array polarity and voltage between the positive and negative cables are correct before connecting the PV array cables to the DC terminal block.
Advanced Energy DC2 inputs DC1 inputs Figure 4‑8. 600 series DC terminal block locations 1000 SERIES The 1000 V series includes six string input pairs with no balancing requirements. DC inputs Figure 4‑9. 1000 series DC terminal block location DC FUSES The inverter uses string fuses to protect the solar modules. A decisive factor for fuse protection of solar modules is the maximum short-circuit current of the respective solar module. The inverter comes standard with 15 A fuses.
Advanced Energy® AE 3TL Inverters ☞ Important The size of the string fuses must not exceed the series fuse rating of the PV module. For example, if 15 A is specified on the data sheet of the PV module, this is the recommended fuse rating. If the data sheet does not contain specifications for the series fuse rating, contact the PV module manufacturer. If a string fuse with a lower trip value is used, the rated fuse current is lower than the short circuit current of the solar module.
Advanced Energy AVERTISSEMENT: Ne pas ouvrir la boîte de jonction dans un environnement humide ou poussiéreux. La manipulation de composants électriques exposés par temps humide peut entraîner un grave choc électrique. La poussière peut endommager les composants électriques de la boîte de jonction. WARNING: Risk of electrical shock. Replacing string fuses requires that the strings are fully de-energized and the DC disconnect is in the OFF position. AVERTISSEMENT: Risque de choc électrique.
Advanced Energy® AE 3TL Inverters ☞ Important The AE inverter is a transformerless unit. Do not connect the unit with PV modules that require positive (+) or negative (-) polarity to ground. Only the array or PV module frame may be grounded. 5. Route the PV array conductors through the conduit to the desired entry conduit hub on the DC side on the bottom of the inverter connection box. For the 500 V series, use separate feed-throughs for the DC1 and DC2 inputs.
Advanced Energy DC+ inputs DC- inputs Figure 4‑11. 1000 V series DC input terminal blocks in the connection box 8. For the 500 V series, ensure that the same number of strings are installed in DC1 and DC2 inputs. 9. Tighten each screw terminal. 10. Pull test each conductor. AC Conductors DANGER: Electrical connections must comply with national and local standards. Voltage drop and other considerations may dictate that larger wire sizes be used.
Advanced Energy® AE 3TL Inverters WARNING: All electrical installations should be completed in accordance with national and local electrical codes. The inverter must be connected to a dedicated circuit with no other outlets or devices connected to the same circuit. AVERTISSEMENT: Tous les travaux électrique doivent être effectués conformément aux codes de l’électricité national et local.
Advanced Energy DANGER: RISQUE DE MORT OU DE BLESSURES CORPORELLES. Débrancher et verrouiller/étiqueter toutes les sources de puissance d’entrée avant de travailler sur cette unité ou sur tout élément qui y est raccordé. CAUTION: Risk of electrical shock. All electrical installations should be accomplished in accordance with applicable national or local standards. ATTENTION: Risque d'électrocution.
Advanced Energy® AE 3TL Inverters AVERTISSEMENT: Ne pas ouvrir la boîte de jonction dans un environnement humide ou poussiéreux. La manipulation de composants électriques exposés par temps humide peut entraîner un grave choc électrique. La poussière peut endommager les composants électriques de la boîte de jonction. Tools Required • Torque wrench • Multi-meter • Flat-head screwdriver To Connect the AC Wiring 1.
Advanced Energy AC inputs Figure 4‑13. 1000 V series AC connections 3. Connect the grounding conductor to one of the AC terminals marked GND. A Protective Earth (PE) feed-through terminal block is available in the AC connection area. The gauge of the AC grounded conductor must be sized in accordance with NEC requirements. GND L1 L2 L3 N GND Figure 4‑14. AC terminals 4. Connect the remaining grid-side conductors to the L1, L2, L3, and N locations on the AC terminal block 5.
Advanced Energy® AE 3TL Inverters 9. Turn off the utility grid circuit breaker. 10. Complete a final check of the connections to ensure they are snug and protected from rain. 11. Close the connection box cover.
Advanced Energy 4‑28 Installing 570-1002542-05B
Advanced Energy® AE 3TL Inverters Chapter 5 Operation FIRST TIME OPERATION WARNING: Before turning on the inverter, ensure that the connection box cover is properly installed. AVERTISSEMENT: Avant d’allumer l’onduleur, s’assurer que le couvercle de la boîte de jonction est bien installé. WARNING: Use suitable precautions; this area contains high voltages that could cause serious injury or death.
Advanced Energy AVERTISSEMENT: Ne pas mettre l’appareil AE 3TL en marche s’il n’a pas été mis à la terre. To Operate the AE 3TL Inverter for the First Time 1. Verify that the AC, DC, and ground connections are correctly and securely installed. 2. Verify that the connection box cover is secure. 3. Close the AC system circuit breakers or insert the external main fuse. 4. Turn the DC disconnect to the ON position.
Advanced Energy® AE 3TL Inverters ☞ Important The inverter automatically performs a self-test after completion of the initialization routine. The individual system components are checked and data is imported from the power control board (PCB). If there is a fault, the type of fault will indicate what corrective measures have to be taken. 6. Verify that the startup procedure has started by checking the following: ◦ Status LED Ready is continuously lit. ◦ Status LED ON flashes.
Advanced Energy WARNING: Do not attempt to turn on power until the AE 3TL unit is grounded. AVERTISSEMENT: Ne pas mettre l’appareil AE 3TL en marche s’il n’a pas été mis à la terre. To Start Up the AE 3TL Inverter 1. Verify the connection box cover is secure. 2. Close the AC system circuit breakers or insert the external main fuse. 3. Turn the DC disconnect to the ON position.
Advanced Energy® AE 3TL Inverters ◦ Status LED Ready is continuously lit. ◦ Status LED ON flashes. ☞ Important When the solar array voltage is greater than 200 V, the startup procedure starts. 6. Verify the feed-in operation has started by checking the following: ◦ Status LED Ready goes off. ◦ Status LED ON is continuously lit. Under normal operating circumstances, this procedure takes approximately five minutes.
Advanced Energy LED Indicators The AE 3TL inverter has four LED indicators that provide status information. All four LEDs light up for six seconds during the self test. Table 5‑1. LED indicators LED Indicator Color READY Green Description Lights up when the solar array voltage is greater than 200 V. Flashes during the initialization procedure. Persists on when the feed-in DC voltage from the PV array reaches the minimum operating voltage for the inverter. Turns off when the ON LED is continuously lit.
Advanced Energy® AE 3TL Inverters Table 5‑2. Control panel buttons (Continued) Screen Information Description This is the enter button. This button confirms the following: • Menu selection • Input value ►Right arrow button ◄ Left arrow button • Allows navigation within the current menu level. • Positions the cursor within a parameter. ◦ ◄ positions before the decimal point ◦ ► positions after the decimal point ▲Up arrow button Allows navigation to the previous or next menu.
Advanced Energy Table 5‑3.
Advanced Energy® AE 3TL Inverters To Set the Country Code Immediately after the DC voltage is switched on for the first time, a window appears on the display requesting confirmation of the country code. You can select one of the listed countries. The term "country code", however, is not shown in the menu. The display lights up the first time you press the button. 1. Highlight the country code for your install location using the ▲ and ▼ buttons.
Advanced Energy Selecting and confirming the country code also sets the language for the display menus. The language setting may be modified without changing the country code. NORMAL OPERATION Each time the unit powers on, the inverter runs a self-diagnostic procedure to ensure that it is performing correctly. This includes a check of the of the DC conductor insulation to verify the insulation is not damaged. If the insulation is damaged, the inverter automatically shuts down.
Advanced Energy® AE 3TL Inverters ABSOLUTE YIELD DATA • Press the ► button once. The current yield data and the accumulated operating hours through the current day display. READY ON Yield absolute Day: Month Year: Total: Oper. hr: F1-Menu ALARM EARTH FLT 36.2 kWh 864.2 kWh 956.6 kWh 956.6 kWh 313.1 h F1 F2 ESC Figure 5‑3. Display of absolute yield data NORMALIZED YIELD DATA The normalized yield data is used for a special form of scaling.
Advanced Energy NORMALIZATION INPUT To receive the normalized yield data, press the F2 button and enter the connected PV generator output at parameter P1155 as follows: 1. Select the position of the number you want to change by pressing the ◄ button to select a position left of the decimal point or by pressing the ► button to select a position after the decimal point. 2. Press the ▲ button to increase the number in the selected position or press the ▼ button to decrease the number in the selected position.
Advanced Energy® AE 3TL Inverters Figure 5‑7. Previous day's feed-in power 3. Press the ESC button to return to the basic operating screen. The inverter stores data which records measured values while the inverter is running. The default configuration includes 16 measurement channels. Table 5‑4. Data storage Logging Cycle Length of Storage Time 1 minute 6 months 5 minutes 2.
Advanced Energy 4. Position the cursor over the first digit location for entering the five digit password. Use the ▲ or▼ buttons to scroll to the correct number. 5. Move the cursor one position to the right, the second position of the password. Use the ▲ or ▼ buttons to scroll to the correct number. Continue to enter the remaining digits of the password until all five numbers have been selected. 6. Press the enter button to confirm your entry.
Advanced Energy® AE 3TL Inverters To Select the Communications Settings The communications method must be configured before the inverter is connected to a network. 1. Press the F1 button to display the main menu. 2. Press the ▼ button until Configuration is highlighted, and then press the enter button. 3. Press the ▼ button twice to highlight Communication, and then press the enter button. 4. Use the ▼ and ▲ buttons to select the desired communication method.
Advanced Energy 4. Use the ▲ and ▼ buttons to select the following: ◦ Activation: ▪ 0 = off ▪ 1 = on ◦ Send configuration: ▪ 0 = no configuration data in the queue ▪ 1 = configuration data being sent ◦ Server IP: Displays the server IP address ◦ Server port: Displays the port number of the web server ◦ Portal test: Yes sends a data packet to the web server (portal). There is no acknowledgement. To verify that the data packet was sent, contact AE Solar Energy Technical Support. ◦ Password: ◦ Extended: 5.
Advanced Energy® AE 3TL Inverters Table 5‑6. Data logger parameters Parameter Number P450.00 Parameter Definition Data logger on or off Description Switches the data logger on and off: • 0: Off • 1: On (data is recorded regularly) P451.00 Data logger time interval Contains the time interval (60, 300, 600 seconds) frequency at which the data logger saves data. P452.00-39 Parameter number data logger Contains a list of all parameter numbers that are to be recorded.
Advanced Energy c. Press the enter button to confirm the setting. 6. Press ESC to return to the main menu.
Advanced Energy® AE 3TL Inverters Chapter 6 Data Monitoring and Controls DATA COMMUNICATIONS OVERVIEW The AE 3TL inverter is equipped with integrated data monitoring hardware for accessing inverter data. The KP board provides communication access to inverter performance data using the following methods: • AESiteLink using REFUlog: Inverter direct monitoring using the AE webbased monitoring solution • Third party monitoring: USS protocol is translated to Modbus via an external Obvius gateway (optional).
Advanced Energy All AE commercial inverters come standard with an Ethernet port that is intended to be connected to the Internet or to a local area network. Communication is one way – the inverter only communicates externally to the AE cloud hosted servers. Ethernet Network Layout AE offers a robust, direct web-based monitoring solution for the AE 3TL that allows you to remotely monitor the performance of your installation.
Advanced Energy® AE 3TL Inverters RS-485 NETWORK LAYOUT When multiple inverters or other Modbus slave devices are connected to a single Modbus master device, the multiple devices need to be connected in a daisy chain layout. ☞ Important When multiple devices are wired to the network, the network shield must be terminated to earth ground at one point on the network, typically at the beginning or the end.
Advanced Energy Ethernet (RJ-45) Analog (sensor) B = OUT A = IN RS-485 IN/OUT Figure 6‑2. Communication interface RS-485, Analog (Sensor), Ethernet (RJ-45) 2. Note that every bus user must have a unique address. 3. The bus termination on the last bus user (inverter "n") needs to be jumpered on terminal A (out) between pins 1 and 2 and pins 3 and 4.
Advanced Energy® AE 3TL Inverters Figure 6‑3. RS-485 connections ☞ 570-1002542-05B Important Use an Ethernet cable of S/FTP design (Shielded Foiled Twisted Pair).
Advanced Energy 6‑6 Data Monitoring and Controls 570-1002542-05B
Advanced Energy® AE 3TL Inverters Chapter 7 Maintenance WARNING: These servicing instructions are for use by qualified personnel only. To reduce the risk of electric shock, do not perform any servicing other than that specified in the operating instructions. AVERTISSEMENT: Ces instructions d’entretien sont destinées uniquement à un personnel qualifié. Pour réduire le risque d'électrocution, ne pas effectuer un entretien autre que celui spécifié dans les instructions de fonctionnement.
Advanced Energy VISUAL INSPECTION DANGER: Risk of electrical shock. High voltages are present in the inverter cabinet. Both AC and DC disconnects must be in the OFF position when working on the unit. Wait five minutes to discharge high voltage before opening the front panels of the inverter. DANGER: Risque d’électrocution. L’intérieur de l’onduleur est soumis à des hautes tensions. Les interrupteurs de courant alternatif et continu doivent être mis HORS TENSION durant les travaux sur l’unité.
Advanced Energy® AE 3TL Inverters Table 7‑1. Maintenance checklist Item # Check or Procedure Maintenance Cycle General inspection and cleaning 1 Record general site conditions. Annually 2 Record inverter performance data from inverter display. Annually 3 Record environmental conditions. Annually 4 Remove dirt and debris from underneath the inverter. Annually 5 Inspect and touch up damage to exterior paint. Annually 6 Inspect and clean interior of the connection box.
Advanced Energy To Replace the Fuses 1. Observe proper LOTO procedures to isolate the unit electrically. 2. Open the connection box cover. 3. Flip the fuse holder switch to expose the fuse. 4. Remove the fuse from the fuse cover. 5. Insert a new fuse into the fuse cover. Ensure that the new fuse is the recommended rating and brand. The inverter combiner box is equipped with standard 15 A string fuses. Contact AE Solar Energy Technical Support for information about replacement fuses. 6.
Advanced Energy® AE 3TL Inverters Chapter 8 Troubleshooting and Solar Energy Technical Support Before calling AE Solar Energy Technical Support, perform recommended checks and troubleshooting procedures. If you are still unable to resolve the issue and resume normal operation after following these checks and procedures, contact AE Solar Energy Technical Support. TROUBLESHOOTING CHECKLIST DANGER: RISK OF DEATH OR BODILY INJURY.
Advanced Energy The inverter provides four LEDs and a display that are the primary indicators of the system status. When the FAULT LED is on: 1. Record the message on the display. 2. Turn the DC disconnect switch to the OFF position. REVERSE CURRENT The inverter is equipped with string fuses at both positive and negative terminals, DC1 and DC2, to ensure that no dangerous reverse currents can occur in the event of a short circuit.
Advanced Energy® AE 3TL Inverters AVERTISSEMENT: Le personnel d’entretien doit recevoir une formation appropriée avant d’installer, de dépanner ou d’entretenir un équipement électrique à haute énergie. Des tensions potentiellement mortelles pourraient provoquer la mort, des blessures graves ou des dommages à l’équipement. S’assurer que toutes les consignes de sécurité appropriées ont été respectées. DANGER: This unit contains energy storage devices that take up to 5 minutes to discharge.
Advanced Energy READY ON ALARM EARTH FLT Analysis Actual Value Failure Memory Configuration Device Information F1-Menu F1 F2 ESC Figure 8‑1. Failure Memory menu item Clearing a Fault When the inverter shuts down due to a fault, the inverter is locked out of restarting until the fault is acknowledged. As long as the cause of the fault still exists, it is not possible to clear the fault. The fault can only be cleared after the cause has been eliminated. TO CLEAR A FAULT 1.
Advanced Energy® AE 3TL Inverters Overvoltage Fault 600 SERIES The inverter has two DC inputs, DC1 and DC2, each of which is limited to 500 V. A relay (combiner) inside the inverter connects the two arrays, in series, upon activation. This doubles the voltage level inside the inverter. A symmetry controller balances the voltages of the two terminals, positive of DC1 and negative of DC2, so they do not exceed 500 V with respect to ground under any condition.
Advanced Energy Table 8‑1. Inverter faults Display Screen Text ACTIVATION LT Operation Condition Timeout. Intermediate circuit is precharging. ACTIVATION LT 1 Failure of a power branch in the boost converter. ACTIVATION LT 2 Drop of intermediate circuit voltage below limit value P0024.0 (power section). ACTIVATION LT 3 Set point value for intermediate circuit symmetrization faulty. ACTIVATION LT 4 Timeout. Intermediate circuit symmetrization.
Advanced Energy® AE 3TL Inverters Table 8‑1. Inverter faults (Continued) Display Screen Text Operation Condition Description CONTROLLER VOLTAGE 3 Asymmetry in intermediate circuit low. Wait until the controller has restabilized. CONTROLLER VOLTAGE 4 Asymmetry in intermediate circuit high. Wait until the controller has restabilized. CONTROLLER VOLTAGE 5 Dropping of positive intermediate circuit below utility main connection peak value. Wait until the controller has restabilized.
Advanced Energy Table 8‑1. Inverter faults (Continued) Display Screen Text Operation Condition Description DEVICE FAULT LT Overload shutdown in power section. Acknowledge the fault by pressing the ESC button and de-energizeing the inverter. ETHERNET CONNECTION 1 Ethernet connection setup unsuccessful. Check the Ethernet connection. ETHERNET CONNECTION 2 Ethernet disconnected. ETHERNET CONNECTION 3 There is no 100 Mbit/s Ethernet connection. Set up Ethernet connection with 100 Mbit/ s.
Advanced Energy® AE 3TL Inverters Table 8‑1. Inverter faults (Continued) Display Screen Text Operation Condition Description GRID FREQUENCY LT Detection of a utility main frequency fault (ENS, power section). This fault indication is possibly caused by switching operation on the utility main. 1. Inverter will automatically restart when utility voltage and frequency returns within normal limits.
Advanced Energy Table 8‑1. Inverter faults (Continued) Display Screen Text Operation Condition Description GRID UNDERVOLT EXT CONDUCTOR Detection of utility main undervoltage on the external conductor (ENS, control section). This fault indication is possibly caused by switching operation on the utility main. 1. Inverter will automatically restart when utility voltage and frequency returns within normal limits.
Advanced Energy® AE 3TL Inverters Table 8‑1. Inverter faults (Continued) Display Screen Text OVERTEMPERATURE 6 Operation Condition Description Temperature in inverter too high. This fault is possibly caused by one or more of the following: Allow the inverter to cool down. • Over temperature shutdown of SR • Cooler temperature has exceeded 80°C (176°F) • Interior temperature has exceeded 75°C (167°F) OVERTEMPERATURE LT 1 Temperature in the right cooler section above limit value P0027.3.
Advanced Energy Table 8‑1. Inverter faults (Continued) Display Screen Text VOLTAGE OFFSET LT Operation Condition Description Offset adjustment of the Acknowledge the fault by power section was outside the pressing the ESC button limits. and de-energizeing the inverter. AE SOLAR ENERGY TECHNICAL SUPPORT Please contact AE Solar Energy Technical Support if you have questions or problems that cannot be resolved by working through the provided troubleshooting.
Advanced Energy® AE 3TL Inverters Appendix A Specifications PHYSICAL SPECIFICATIONS Table 9‑1. Physical specifications for AE 3TL 600 series and 1000 series Description Specification General Physical Specifications Enclosure rating NEMA 4 Connection box: NEMA 3R Construction Transformerless design, integrated DC disconnect Size 535 mm x 895 mm x 280 mm (21″ x 35″ x 11″) Maximum weight 49 kg (108 lb) Clearance Front: Per NEC 110.
Advanced Energy Table 9‑2. Electrical specifications (Continued) Description Specifications for 600 Series Continuous AC power Specifications for 1000 Series AE 3TL-12kW: 12 kW AE 3TL-16kW: 16 kW AE 3TL-20kW: 20 kW AE 3TL-23kW: 23.2 kW Rated apparent power AE 3TL-12kW: 12 kVA AE 3TL-16kW: 16 kVA AE 3TL-20kW: 20 kVA AE 3TL-23kW: 23.2 kVA Maximum continuous current AE 3TL-12kW: 14.5 A AE 3TL-16kW: 19.3 A AE 3TL-20kW: 24.1 A AE 3TL-23kW: 27.9 A Short circuit fault current AE 3TL-12kW: 16.
Advanced Energy® AE 3TL Inverters Table 9‑2. Electrical specifications (Continued) Description Specifications for 600 Series Maximum DC power Specifications for 1000 Series AE 3TL-12kW: 15.6 kW AE 3TL-16kW: 20.8 kW AE 3TL-20kW: 26 kW AE 3TL-23kW: 30.
Advanced Energy COOLING SPECIFICATIONS Table 9‑5. Cooling specifications Description Specification for 600 Series Cooling method Specification for 1000 Series Natural convection ENVIRONMENTAL SPECIFICATIONS Table 9‑6.
Advanced Energy® AE 3TL Inverters Appendix B System and Mechanical Diagrams MECHANICAL DIAGRAMS Figure 10‑1.
Advanced Energy Figure 10‑2.
Advanced Energy® AE 3TL Inverters Figure 10‑3.
Advanced Energy B‑4 System and Mechanical Diagrams 570-1002542-05B
Advanced Energy® AE 3TL Inverters Appendix C Inverter Startup Checklist INVERTER STARTUP CHECKLIST WARNING: Maintenance personnel must receive proper training before installing, troubleshooting, or maintaining high-energy electrical equipment. Potentially lethal voltages could cause death, serious personal injury, or damage to the equipment. Ensure that all appropriate safety precautions are taken.
Advanced Energy Task Yes No The PV array Equipment Grounding Conductor (EGC) must be connected to the GNC stud bolt available in the connection box. The neutral conductor on the AC side of the system must be connected and solidly grounded to the X0 terminal of the service transformer. Monitoring If Ethernet communications are used (typically with REFUlog), ensure that each inverter has been assigned a different IP address and the protocol is set to "0".
Advanced Energy® AE 3TL Inverters Index A acronyms 1‑9 alert boxes in user manual 1‑1 anchoring hardware 4‑6 B bracket for wall mounting 4‑6 breaker protection 1‑6 buttons control panel 5‑6 C cable RS-485 6‑3 checklist startup C‑1 checklist for maintenance 7‑2 circuit breaker protection 1‑6 cleaning display and LEDs 7‑3 communications connections 6‑1 setting 5‑15 compliance directives and standards 1‑4 unit 1‑4 conductors AC 4‑22 DC 4‑15 conduit entry location 4‑23 configure inverter 5‑13 connection box
Advanced Energy F fault codes inverter 8‑5 faults clearing 8‑4 overvoltage 8‑5 feedthrough AC and DC wiring 4‑9 opening 4‑10 fuse DC 4‑13 sizing 4‑18 fuses replacing 7‑3 G general description 2‑1 ground connecting 4‑10 ground wire sizing 1‑8 grounding protection 1‑8 requirements 1‑8 guidelines safety 1‑2 H handles 4‑1 on inverter 2‑3 I icons in user manual 1‑1 on unit 1‑3 industry guidelines, compliance with 1‑4 inspecting inverter 7‑2 inspection troubleshooting 8‑2 installation conduit entry locations
Advanced Energy® AE 3TL Inverters N network daisy chain layout 6‑3 noise emissions A‑4 normal operation 5‑10 O opening connection box 4‑12 operation first time 5‑1 normal 5‑10 start up 5‑3 overvoltage faults 8‑5 P password default 5‑13 entering 5‑13 physical specifications A‑1 polarity PV modules 2‑1 preventative maintenance checklist 7‑2 procedure start up 5‑3 product compliance 1‑4 labels 1‑3 PV modules polarity 2‑1 R replacing fuses 7‑3 reverse current 8‑2 RS-485 network cable 6‑3 S safety directive
Advanced Energy V voltage output 3‑3 wye sizing 1‑6 configuration 3‑3 W warning in user manual 1‑1 wiring requirements 1‑6 iv Index 570-1002542-05B