condenser coil if the panels are not in place. Starting the
unit without all the enclosure panels in place will result in a
high pressure refrigerant fault.
5. Units with a motor-driven fan may not use duct work unless
a booster fan of equal volume rating has been installed in
the duct.
2.3 TO AND FROM PROCESS CONNECTIONS
A. Useappropriatelyratedhoseoruidpipingto
connect the process piping going to your
process to the “to process” connection on the
chiller.
B. Useappropriatelyratedhoseoruidpiping
to connect the process piping coming back
from your process to the “from process”
connection on the chiller.
C. Install a high volume basket strainer in the
From Process line with isolation valves. A
basketstrainerorbaglterwithameshscreen
of 20-40 microns will protect the unit. A “wye”
type strainer is not recommended because
it does not have adequate debris holding
capacity.
D. Process water piping should be designed to avoid excessive elbows
and/orlengthsofpipeorhose.Ifusingexiblehoseavoidtight
twists or curls and excessive lengths.
E. Valvesandltersmaybeinstalledintheprocesswaterpiping
to facilitate service and maintenance provided that such devices
maintain the full inside diameter of the process connection. If
From Process
Make-Up Water Supply
To Process
To Process
From Process
Condenser Water Out
Make-Up Water Supply
Condenser Water In
From ProcessTo Process
This label marks the
To Process connection
From Process
This label marks the From
Process connection
Typical wye strainer -
Not recommended.