Instruction manual
Maximum Series Portable Chiller : Air & Water-Cooled : M1 Series Instrument
Page: 16
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
installed, all such devices must be open and clean during unit
operation.
2.4 MAKE-UP WATER SUPPLY CONNECTION
A. The automatic water make-up system continually monitors the
reservoirtankandllsitwhenneeded.Connectasfollows:
1. Usingappropriatelyratedhoseoruid
piping connect the “water make-up”
connectiontotheplant’swater
source.
2. Minimum make-up water supply pressure is normally 20 psi.
3. Install an owner supplied shut off valve in the make-up
water supply line. Install this valve on the outside of the unit.
4. Useabackowpreventiondeviceasmayberequiredby
local codes to prevent possible contamination of potable
water.
B. Do not use automatic water make-up system when operating
with glycol below 48°F.
2.5 AIR COOLED CONDENSER
A. Air-cooled condensers require ambient air temperatures between
60°Fand95°Fforefcientoperation.Operatingabove95°Fmay
result in elevated condensing pressures and eventual shut-down
on the high pressure limit switch. Air temperatures below 60°F
may result in over condensing pressures and cause a low pressure
refrigerantfault.ConsultwiththeManufacturer’s service department
for more information on operating with ambients air temperatures
above 95°F or below 60°F.
B. Airowisgeneratedbythemotor
mountedfans(gure2.4A)or
centrifugalblowers(gure2.4B).
Airowisfromtheoutsideofthe
chiller, through the condenser and
exhausted through the top of the
unit. On centrifugal blowers models,
exhaust air can be ducted outside
oftheplant’sinteriorenvironment.
Special duct work is required and
Figure 2.4A
Typical fan assembly
From ProcessTo Process
Condenser
Water In
Condenser
Water Out
Water Make-up
This label marks the Water
Make-up connection
WARNING: Check local codes to determine proper use of back ow prevention
device in water make-up supply line.