member in pump casing
cavity(gure5.5I).The
operator must be certain
the stationary seal member
is fully squared and seated
in cavity.
13. Slide the rotating member
onto lubricated pump shaft
(gure5.5J).Theoperator
must be certain not to
damage or tear rubber
bellows assembly.
14. Place the spring onto the
rotating member.
15. Align the impeller, spring
and rotating member before
reinstalling the impeller
(gure5.5K).Theoperator
must be certain the spring
and rotating member are
aligned before the impeller
is fully tighten and the
impeller retaining screw is
reinstalled.
16. Clean pump casing,
cavities, impeller and O-ring
before reassembly.
17. Mate the motor and motor
adapter to the pump casing.
Reinstall the pump casing
bolts.
18. Reconnect the motor power
cord and leads.
19. Restore all cover panels as
were removed.
E. When the pump seal replacement
procedure is complete, the operator
may restart the unit according the
section 3.
Stationary member
Figure 5.5I
Stationary member
Figure 5.5J
Seal members
Figure 5.5K
Seal components
Figure 5.5H