Instruction manual
Maximum Series Portable Chiller : Air & Water-Cooled : M1 Series Instrument
Page: 53
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
5.6 CHECKING THE REFRIGERANT CHARGE
A. All standard chillers are
manufactured with thermostatic
expansion valves as the metering
device to the evaporator.
B. All standard chillers have a
refrigerantsightglass(gure5.6A)
with a moisture indicator. To check
the refrigerant charge under normal
operating conditions:
1. Remove the plastic cap
covering the sight glass.
2. Start the chiller and allow system pressures and
temperatures to stabilize.
3. With the unit operating at 100% capacity (not in the
“capacity control” mode) the sight glass should appear clear
with no foam or bubbles evident. If foam or bubbles are
evident, the chiller has suffered from a loss of refrigerant
andshouldbecheckedbyaqualiedrefrigeration
technician.
4. The “dot” in the middle of the sight glass is the moisture
indicator. It should appear green at all times. A white or
yellow color indicates moisture has invaded the refrigeration
system, which is detrimental to the life of the compressor.
Thelter-driershouldbereplacedbyaqualiedrefrigeration
technician.
5.7 PROPER CLEANING PROCEDURE FOR BRAZED PLATE
EVAPORATORS
A. The brazed plate evaporator is
made of stamped stainless steel
plates, furnace brazed together with
copper based joints. The complex
geometryoftheowpassages
promotesturbulentowwhichgives
highefciencyandreducesfouling
by mineral deposits. Large solids
such as plastic pellets or chunks of
mineral deposits will collect at the
water inlet port at the evaporator
andrestrictowthroughsomeof
the passages. If this possibility
exists, the Manufacturer recommendsltersorstrainers
be added to the “from process” line. If the evaporator becomes
fouled there are a couple of methods for cleaning.
Sight Glass
Figure 5.6A
Evaporator
Figure 5.6A










