solenoid valve to unload the compressor to a low as about 20%
capacity. Units without a digital scroll compressor use a hot gas
bypass solenoid valve to reduce the chiller capacity to about 50%.
I. HIGH/LOW PRESSURE SWITCH: The high and low pressure
switches protect the refrigeration system from usage operating
conditions. Units may be equipped with either an adjustable or
non-adjustable‘xed’highandlowpressureswitches.
The high pressure switch is factory set and protects the
refrigeration components and personnel from potential damage and
injury from excessive pressure. The high pressure safety must not
bealteredintheeldforanyreason(seesection8.1forfactory
settings.
The low pressure switch is factory set to open at 32°F and to close
at 36°F - 38°F*. The low pressure switch protects the chiller from
damage caused by low refrigerant pressure operating below the
coolinguid’sfreezepoint.
NEVER LOWER THE CUT OUT SETTING WITHOUT ADDING
GLYCOL TO THE CIRCULATING SYSTEM. EVAPORATOR
DAMAGE WILL RESULT AND WILL NOT BE COVERED BY THE
WARRANTY.
J.
Liquid receiver: (optional feature) located after the condenser,
this component receives and stores liquid refrigerant leaving the
condenser.
K. Service valves: These valves are located throughout the system.
Onlyaqualiedrefrigerationservicetechnicianshalloperatethese
valves.
* See Temperature-Pressure
chart in Section 8.5 for
refrigerant pressure.
Adjustable low
pressure switch
Typicalplacementofnon-adjustable“xed”pressureswitches.
Non-adjustable“xed”
low pressure switch
Non-adjustable“xed”
high pressure switch
Adjustable high
pressure switch