Maximum Series Portable Chiller : Air & Water-Cooled : M1 Series Instrument
Page: 81
ADVANTAGE ENGINEERING, INC.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
Email: service@AdvantageEngineering.com
Operating
Temperature
48° - 70°F
25° - 47°F
10° - 24°F
Glycol
0%
30%
40%
Freeze
Point
32°F
10°F
-5°F
Cut Out
Temp
32°F
10°F
-5°F
Cut In
Temp
36°F - 39°F
15°F - 18°F
0°F - 7°F
Cut-Out
58#
33#
20#
Cut-In
63#
38#
25#
Refrigerant
R22
R134A
R407C
R410A
R404A
Air-Cooled
380#
260#
405#
610#
405#
Water-Cooled
360#
260#
360#
550#
360#
R22
Cut-Out
28#
12#
4#
Cut-In
33#
17#
9#
R134A
Cut-Out
102#
63#
43#
Cut-In
111#
72#
52#
R410A
Operating
Temperature
48° - 70°F
25° - 47°F
10° - 24°F
Glycol
0%
30%
40%
Freeze
Point
32°F
10°F
-5°F
Cut Out
Temp
32°F
10°F
-5°F
Cut In
Temp
36°F - 39°F
15°F - 18°F
0°F - 7°F
Cut-Out
72#
44#
29#
Cut-In
79#
49#
34#
R404A
Cut-Out
52#
28#
16#
Cut-In
58#
34#
22#
R407C
Refrigerant Low Pressure Switch Cut-Out & Cut-In Settings
High Pressure Cut Out (maximum)
allowed to reduce the setpoint to 10°F or -11°C. To operate below
48°Fleavinguidtemperaturethejumperwillneedtobeinposition
2. See Figure 8.1A.
G. Once all safety provisions are made, the temperature control set
point may now be lowered to the desired operating temperature.
H. WARNING: do not use any type or brand of automotive antifreeze.
Automotive antifreeze contains corrosion inhibitors - silicates -
designed for compatibility with the materials in automotive engines.
Unfortunately, silicates can gel and cause deposits to foul and
insulate heat exchanger surfaces. In your chilling system that
can mean higher energy costs, high pumping costs, and possibly
even shut downs for system cleaning. We recommend the use of
DowFrost or Monsanto DFS-1.
Setpoint Lock Out Jumper
Figure 8.1A