ADAM-2000 Series User Manual 4
1.1.6 Industrial Standard Modbus Protocol
Modbus is an industrial standard serial communication protocol, and a commonly
available means of connecting industrial electronic devices. Modbus allows for com-
munication between many devices connected to the same network. Modbus RTU is
used in serial communication and makes use of a compact binary representation of
the data for protocol communication. The RTU format follows the commands/data
with a cyclic redundancy check checksum as an error check mechanism to ensure
the reliability of data.
1.1.7 SCADA Software Support
ADAM-2000 supports industrial standard Modbus protocol and can be integrated into
Advantech HMI, WOP, SCADA - WebAccess and 3rd party HMI. With the different
ADAM-2000 modules, it is able to acquire signal from digital input, analog input, tem-
perature, humidity, luminance and CO2 concentration then the signals can be apply
to your application.
1.1.8 Advantech Software Alignment
As with all other ADAM devices, the ADAM-2000 integrates into the ADAM .NET Util-
ity, therefore users will have an identical user experience. With the powerful Advan-
tech software, only a few steps are required to search and configure the ADAM-2000
series.
1.2 Specifications
1.2.1 ADAM-2000 Series Hardware Specification
IEEE Standards: IEEE 802.15.4
Modulation Type: OQPSK
Frequency Band: 2.4GHz ~ 2.4835GHz
Channels: 11 - 26
RF Data Rate: 250 kbps
Transmit Power: 3dBm (1.6mW) & 19dBm(79mW)
Receiver Sensitivity: -97 dBm
Transmission Power:
ADAM-2031Z, 2051Z: 3
± 1dBm
ADAM-2051PZ, 2510Z, 2520Z: 19
± 1dBm
Outdoor Range:
ADAM-2031Z, 2017Z, 2051Z: 110m
ADAM-2051PZ, 2510Z, 2520Z: 1000m
Topology: Star/Tree/Mesh
Network Depth/Scale: 6 Routers x 6 Routers
Function: Coordinator/Router/End Device
Operating Temperature Range: -20°C ~ 70°C (-4°F ~ 157.9°F)
Operating Temperature Range (Battery Powered): 0
o
C ~ 50
o
C (32
o
F~122
o
F)
Storage Temperature: -40
o
C ~ 85
o
C (-40
o
F~185
o
F)
Operation Humidity: 20% ~ 95%