User manual
37 APAX-5000 I/O User Manual
Chapter 2 Analog Input
/
Output Modules
 Sampling Rate: 12 samples/second (total)
 CMR @ 50/60 Hz: 90 dB
 NMR @ 50/60 Hz: 67 dB
 Noise Suppression for Frequency: Hardware Filter (50/60 Hz)
 Span Drift: ±25 ppm/°  C
 Zero Drift: ±6 μV/°  C
 Thermocouple Wire Burn-out Detection: Yes 
(When the loop resistance > 1KΩ, it will detect as wire burn-out)
 Input Characteristic Curve: According to IEC 61131-2
 Common Mode Voltage: up to 200 VDC
Protection
 Isolation: 2,500 VDC (Between channels and backplane bus)
Environment
 Operating Temperature: -10 ~ 60°  C (when mounted vertically)
 Storage Temperature: -40 ~ 70°  C
 Relative Humidity: 5 ~ 95% (non-condensing)
General
 Dimensions (W x H x D): 30 x 139 x 100 mm
 Weight: 170 g
 Power Consumption: 3.5 W @ 24 VDC (typical)