User manual
51 Appendix C 
C.16 Read Digital Input Data — BASE+1CH
D15 ~ D0 Digital input data
D0  LSB of the input data
D15  MSB of the input data
C.17 Write Calibration Command — BASE+1EH
D7 ~ D0 Calibration result data
D0  the least significant bit (LSB) of the data
D7  the most significant bit (MSB)
Table C.16: Register for Read Digital Input Data
Base 
Addr.
1514131211109876543210
1CH R Read digital input data
D1
5
D1
4
D1
3
D1
2
D11 D1
0
D9 D8 D7 D6 D5 D4 D3 D2 D1 D0
Table C.17: Register for write calibration command
Base 
Addr.
1514131211109876543210
1EH W Write calibration command
X X X X X X X X D7 D6 D5 D4 D3 D2 D1 D0
Note: If you want to calibrate the range of the specific 
channel, be sure to write the value to BASE+14H 
first. Next, write the data to this register for calibra-
tion purposes. Lastly, write the value to BASE+18H 
to strobe the parameters into EEPROM.