Technical information

2
1
3
4
5
6
7
8
9
10
2
1
3
4
5
6
7
8
9
10
16-channel output modules 8 or 16-channel output modules
Connection via cage clamp, screw clamp or spring-type removable block terminal
c transistor a triac c relay c/a relay
2
4 V VV 100…240 V VV 100…150 V VV 24 V VV c, 24…240 V a V aV a
0.5 A 0.6 A AA 0.3 A (Ith) A (Ith)A (Ith) 2 A (Ith) A (Ith)A (Ith)
16 protected outputs and
1 common
16
non-protected outputs
and 4 commons
8 non-protected outputs,
without common
16 non-protected outputs and
2 commons
Via BMX
FTB 2000/2010/2020 20-way cage clamp, screw clamp or spring-type removable block terminal
Configurable output fallback, continuous monitoring
of output control and resetting of outputs in case of
internal fault
Configurable output fallback
Yes Yes
Yes
Positive (source) Negative (sink)
19…30 V 100…240
V 100…150 V 19...30 V c
24...240 V a
Use one 6.3 A
fast-blow fuse per group of channels
Use one 3 A fast-blow
fuse per group of
channels
Use one 0
.5 A, 250 V DC
fast-blow fuse on each
relay
Use one 3 A fast-blow
fuse on each channel
Use one 12 A fast-blow
fuse on each group of
channels
4 W 2.26 W 3.17 W 2.7 W 3 W
0…60°C -25…70°C 0…60°C
BMX DDO 1602 BMX DDO 1612 BMX DAO 1605 BMX DRA 0804T BMX DRA 0805 BMX DRA 1605