User manual

23 Chapter 2
Figure 2.7:
Digital Input
Connector Pin Assignments
2.10.2
Isolated
Inputs
Each of isolated
digital input channels accepts 0
~ 50
VDC
voltage inputs,
and
accepts bi-directional
input. The voltage range is -3 ~ 3 VDC for logic
0 (low), -50 ~ -10 VDC and 10 ~ 50 VDC for logic 1 (high). It means that
you can apply
positive
or negative voltage to
an
isolated input
pin (Vin).
All
channels share two common
pins (I.GND). Figure
2.8 shows how to
connect an external
input
source to an UNO-4672 isolated input channel.
Please note
that DI0
and DI2
may be configured as
gate control pins of
Counter 0 and Counter 1;
While DI1
and DI3 may be configured as input
pins of Counter 0
and Counter 1.
Table 2.12: Digital Input Connector Signal Description
Signal Name Reference Direction Description
DI <0...7> I.GND Input Isolated DI signals
I.GND - - DI isolated ground