User's Manual
Table Of Contents
- WISE-221X
- Contents
- 1 Product Overview
- 2 Product Specification
- 3 Mechanical and Hardware Installation
- 4 System Configuration
- 4.1 Connection
- 4.2 Configuring WISE-4210-AP with Browser
- 4.3 Install WISE Studio and Configure End Devices
- 4.4 Connection between AP and Nodes
- 4.5 Configure WISE-4210-AP
- 4.6 Setup WISE-221x Network
- 4.7 WISE-221x IO configuration
- 4.8 Access WISE-221x Data by Modbus/TCP Protocol
- 4.9 Push WISE-4210 data by RESTful Web Service
- 4.10 Access WISE-4210 I/O Data by RESTful API
7 WISE-221X User Manual
Chapter 2 Product Specification
2.2 General
I/O & Power connector: 3.5-mm spacing plug-in screw terminal block
Enclosure: PC
Mounting: DIN 35 rail, wall, pole
Dimensions (W x H x D): 71 x 52 x 30 mm (without Antenna)
Operation temperature: -25~70°C (-13~158°F)
Storage temperature: -40~85°C (-40~185°F)
Operating humidity: 5~95% RH (non-condensing)
Storage humidity: 0~95% RH (non-condensing)
2.3 Power
2.3.1 WISE-2210
1. Input power requirements:
WISE-2210 is a self-powered sensor node, power source is obtained from AI(Analog
input) which connected 0~100 mA current transformer. In other words, WISE-2210
measures data and gets power current from connected current transformer.
2. Charging time
Test Condition:
Data Rate: 50Kbps
Transmit Power: 5dBm
Frequency 920.8MHz
Distance: 500 meters, Line of sight
Note! Equipment will operate below 30% humidity. However, static electricity-
problems occur much more frequently at lower humidity levels. Make
sure you take adequate precautions when you touch the equipment.
Consider using ground straps, anti-static floor coverings, etc. if you use
the equipment in low humidity environments.
Data Transmission
Time Period
Minimum alternating current
of CT Primary Current Value
1st Charging Time
for WISE-2210
1s 18A 1 min
5s 6A 8 min
10s 3A 20 min
30s 2A 35 min
60s 2A 35 min