9 WISE-221X User Manual
Chapter 2 Product Specification
2.6 I/O Specifications
WISE-2210
Channel: 3 (for CT, 0-100mA, AC)
Input Range: 0-100mA, Alternating current
Resolution: 11 bits
Accuracy: ±0.2 % of FSR
Drift: 40ppm
WISE-2211
Channel: 3 (for sensor, 4-20mA, DC)
Input Range: 4-20mA, Direct current
Resolution: 11 bits
Accuracy: ± 0.2 % of FSR
Drift: 40ppm
2.7 Configuration Interface
Configuration Interface Micro-B USB
Note! WISE-221X modules can operate below 30% humidity. However, envi-
ronments with low relative humidity are prone to problems with electro-
static discharge. Therefore, you should ensure that you take adequate
precautions by using ground straps, anti-static floor coverings, or similar
equipment whenever you handle this equipment, especially in low-
humidity environments.
Note! User can order Advantech’s accessory: CT(Current Transformer),
please see chapter 2.11.Accessory: CT(Current Transformer).
If user want to choose CT by themselves, please choose Turns Ratio
Np:Ns is above 1:3000, and the output range of CT Secondary Current
Value should choose 0-100(mA).
Note! A USB cable is used for configuration only.