WISE-221X User Manual 28
4.7.2 I/O Status
Please go to "End Devices \ IO Status" to configure the RF module by following
below instructions.
Channel: WISE-2210/2211 has three channel, user can choose channel 0~2.
CT Primary Current Value(A): It's input power current of CT. For instance, CT
Primary Current Value is the power current of facility equipment and machine
(See figure 1.1).
CT Secondary Current Value(mA): It's output power current of CT. In other
words, CT Secondary Current Value is the power current into WISE-2210.
Note! User can order Advantech’s accessory: CT(Current Transformer),
please see chapter 2.11.Accessory: CT(Current Transformer).
If user want to choose CT by themselves, please choose Turns Ratio
Np:Ns is above 1:3000, and the output range of CT Secondary Current
Value should choose 0-100(mA).