WISE-221X User Manual 30
Modbus Address Table for WISE-2210 and 2211:
Address 4X Ch Description Attribute
40001 0
AI Value
Read
40002 1 Read
40003 2 Read
40004 3 Read
40005 4 Read
40006 5 Read
40007 6 Read
40008 7 Read
40009 Average Ch 0~7 Read
40131~40132 0
AI Floating Value
(IEEE754)
Read
40133~40134 1 Read
40135~40136 2 Read
40137~40138 3 Read
40139~40140 4 Read
40141~40142 5 Read
40143~40144 6 Read
40145~40146 7 Read
40147~40148 Average Ch 0~7 Read
40201 0
Type Code
(The type codes
of channels for
average value
can't be
changed.)
Read
40202 1 Read
40203 2 Read
40204 3 Read
40205 4 Read
40206 5 Read
40207 6 Read
40208 7 Read
40209 Average Ch 0~7 Read
40231~40232 0
Physical AI Floating
Value (IEEE754)
Read
40233~40234 1 Read
40235~40236 2 Read
40237~40238 3 Read
40239~40240 4 Read
40241~40242 5 Read
40243~40244 6 Read
40245~40246 7 Read
40247~40248 Average Ch 0~7 Read